PowMr 2KW Hybrid Solar Inverter User Manual

Model: POW-HVM2H-12V-N

1. About This Manual

1.1 Purpose

This manual describes the assembly, installation, operation, and troubleshooting of this unit. Please read this manual carefully before installations and operations. Keep this manual for future reference.

1.2 Scope

This manual provides safety and installation guidelines as well as information on tools and wiring.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION – To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION - Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Introduction

This is a multi-function inverter/charger, combining functions of inverter, solar charger and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

3.1 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible to mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/ Over temperature/ short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function
  • WIFI/GPRS (Optional)
  • Can connect to lithium battery

3.2 Basic System Architecture

The following illustration shows basic application for this inverter/charger. It also includes following devices to have a complete running system:

  • Generator or Utility.
  • PV modules

Consult with your system integrator for other possible system architectures depending on your requirements.

This inverter can power all kinds of appliances in home or office environment, including motor-type appliances such as tube light, fan, refrigerator and air conditioner.

Hybrid Power System Diagram
Figure 1: Hybrid Power System showing connections for solar power, generator/utility, battery, and home appliances.

3.3 Product Overview

Inverter Front and Side View with Labeled Components
Inverter Front and Side View with Labeled Components
  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Function buttons
  6. Power on/off switch
  7. AC input
  8. AC output
  9. PV input
  10. Battery input
  11. RS-232 communication port
Product dimensions and key specifications
Product dimensions and key specifications: 80A MPPT, 2000W PV, 30-400VDC PV range, Pure Sine Wave, 50/60Hz Auto, Lithium battery support.
Charging & Output Modes diagram
Charging & Output Modes: Four Charging Modes (Solar first, Utility first, Solar and Utility, Only Solar) and Three Load Output Working Modes (Utility first, Solar first, SBU first).
Multi-Protection Functions
Multi-Protection Functions: Short-circuit Protection, Surge Protection, Overload Protection, Over-Temp Protection, Low Voltage Protection, High Voltage Protection, Cold Start Function.
WIFI Monitoring Ready!
WIFI Monitoring Ready! You can see performance in real time without the need of checking on the controller's LCD. Note: WIFI module is not included in the package.

4. Setup (Installation)

4.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items inside of package:

  • The unit x 1
  • User manual x 1

4.2 Preparation

Before connecting all wirings, please take off bottom cover by removing two screws.

4.3 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.
Mounting dimensions and clearances
Mounting dimensions and clearances for proper air circulation.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.

4.4 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable as below.

Recommended battery cable size:

ModelWire SizeCable (mm²)Torque value (max)
2.0KVA 12V1 x 4AWG222 Nm
3.2KVA 24V1 x 6AWG142 Nm

Please follow below steps to implement battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as below chart.
Battery connection diagram
Battery connection diagram for 2.0KVA/12V and 3.2KVA/24V inverters.
  1. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard
Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.5 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 10A for 2.0kva and 32A for 3.2kva.
CAUTION!! There are two terminal blocks with "IN" and "OUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested cable requirement for AC wires:

ModelGaugeTorque Value
2.0KVA 12V14 AWG0.5~0.6Nm
3.2KVA 24V12 AWG1.2 Nm

Please follow below steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (Ground symbol) first.
  • Ground symbol Ground (yellow-green)
  • L→ LINE (brown or black)
  • N→ Neutral (blue)
AC Input Wiring Diagram
AC Input Wiring Diagram
WARNING:
Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
  1. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
  • L→ LINE (brown or black)
  • N→ Neutral (blue)
AC Output Wiring Diagram
AC Output Wiring Diagram

4.6 PV Connection

CAUTION: Appliances such as air conditioner are required at least 2-3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check manufacturer of air conditioner if it's equipped with time-delay function before installation. Otherwise, this inverter/charger will trig overload fault and cut off output to protect your appliance but sometimes it still causes internal damage to the air conditioner.
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Recommended PV module cable size:

ModelWire SizeTorque value (max)
2.0KVA 12V
3.2KVA 24V
1x16AWG1.2 Nm

PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
INVERTER MODEL2.0KVA/3.2KVA
Max. PV Array Open Circuit Voltage400Vdc
PV Array MPPT Voltage Range30Vdc-400Vdc

Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table.

Solar Panel Spec. (reference) 250WpSOLAR INPUT (Min in serial: 4 pcs, max. in serial: 12 pcs)Q'ty of panelsTotal input power
Vmp: 30.1Vdc
Imp: 8.3A
Voc: 37.7Vdc
Isc: 8.4A
Cells: 60
4 pcs in serial4 pcs1000W
6 pcs in serial6 pcs1500W
8 pcs in serial8 pcs2000W
10 pcs in serial10 pcs2500W

PV Module Wire Connection:
Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
PV Module Wire Connection Diagram
PV Module Wire Connection Diagram
  1. Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.
PV Input Connection Diagram
PV Input Connection Diagram

4.7 Final Assembly

After connecting all wirings, please put bottom cover back by screwing four screws.

5. Operating

5.1 Power ON/OFF

Power On/Off Switch Location
Side view of unit showing Power On/Off Switch.

Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit.

5.2 Operation and Display Panel

The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.

LCD Display and Function Keys
LCD Display and Function Keys.

LED Indicator:

LED IndicatorMessages
AC / INV (Green)Solid On: Output is powered by utility in Line mode.
Flashing: Output is powered by battery or PV in battery mode.
CHG (Green)Solid On: Battery is fully charged.
Flashing: Battery is charging.
FAULT (Red)Solid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3 LCD Display Icons

The LCD display information will be switched in turns by pressing "UP" or "DOWN" key. The selectable information is switched as below order: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, main CPU Version.

IconFunction description
Input Source Information
ACIndicates the AC input.
PVIndicates the PV input
INPUTBATT
888 kW
VA
Hz
Indicate input voltage, input frequency, PV voltage, charger current (if PV in charging for 2.0KVA models), charger power, battery voltage.
Configuration Program and Fault Information
88Indicates the setting programs.
8.8
ERROR
Indicates the warning and fault codes.
Warning: Warning icon flashing with warning code.
Fault: Fault icon lighting with fault code.
Output Information
OUTPUTBATTLOAD
888 kW
VA
Hz
Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
Battery Information
CHARGINGIndicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode.
Load Information
OVER LOAD
100%
25%
Indicates overload.
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
Mode Operation Information
Indicates unit connects to the mains.
Indicates unit connects to the PV panel.
BYPASSIndicates load is supplied by utility power.
Indicates the utility charger circuit is working.
Indicates the DC/AC inverter circuit is working.
Mute Operation
Indicates unit alarm is disabled.

5.4 LCD Setting

After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press "UP" or "DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.

Setting Programs:

ProgramDescriptionSelectable option
00Exit setting mode00 ESC (Escape)
01Output source priority: To configure load power source priority
  • 01 U56 (Utility first - default): Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available.
  • 01 S0L (Solar first): Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, utility will supply power to the loads at the same time. Battery provides power to the loads only when any one condition happens: Solar energy and utility is not available. Solar energy is not sufficient and utility is not available.
  • 01 SBU (SBU priority): Solar energy provides power to the loads as first priority. If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 12.
02Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current)
  • 02 10A
  • 02 20A
  • 02 30A
  • 02 40A
03AC input voltage range
  • 03 APL (Appliances - default): If selected, acceptable AC input voltage range will be within 90-280VAC.
  • 03 UPS (UPS): If selected, acceptable AC input voltage range will be within 170-280VAC.
05Battery type
  • 05 FLd (Flooded)
  • 05 USE (User-Defined): If "User-Defined" is selected, battery charge voltage and low DC cut-off voltage can be set up in program 26, 27 and 29.
06Auto restart when overload occurs
  • 06 LFd (Restart disable - default)
  • 06 LHE (Restart enable)
07Auto restart when over temperature occurs
  • 07 LFd (Restart disable - default)
  • 07 LHE (Restart enable)
09Output frequency
  • 09 50. (50Hz - default)
  • 09 60. (60Hz)
10Output voltage
  • 10 220 (220V)
  • 10 230 (230V - default)
  • 10 240 (240V)
11Maximum utility charging current
Note: If setting value in program 02 is smaller than that in program in 11, the inverter will apply charging current from program 02 for utility charger.
  • 11 2A
  • 11 10A
  • 11 20A
  • 11 30A (default)
  • 11 40A
  • 11 50A
  • 11 60A
12Setting voltage point back to utility source when selecting "SBU priority" or "Solar first" in program 01.Available options in 2.0KVA 12V model:
  • 12 10.5V
  • 12 11.0V
  • 12 11.5V (default)
  • 12 12.0V
  • 12 12.5V
  • 12 13.0V
  • 12 13.5V
  • 12 14.0V
  • 12 14.5V
  • 12 15.0V
13Setting voltage point back to battery mode when selecting "SBU priority" or "Solar first" in program 01.Available options in 2.0KVA 12V model:
  • 13 FUL (Battery fully charged)
  • 13 12.0V
  • 13 12.5V
  • 13 13.0V
  • 13 13.5V (default)
  • 13 14.0V
  • 13 14.5V
  • 13 15.0V
  • 13 15.5V
  • 13 16.0V
  • 13 16.5V
  • 13 17.0V
16Charger source priority: To configure charger source priorityIf this inverter/charger is working in Line, Standby or Fault mode, charger source can be programmed as below:
  • 16 C50 (Solar first): Solar energy will charge battery as first priority. Utility will charge battery only when solar energy is not available.
  • 16 SNU (Solar and Utility - default): Solar energy and utility will charge battery at the same time.
  • 16 050 (Only Solar): Solar energy will be the only charger source no matter utility is available or not.
If this inverter/charger is working in Battery mode or Power saving mode, only solar energy can charge battery. Solar energy will charge battery if it's available and sufficient.
18Alarm control
  • 18 600 (Alarm on - default)
  • 18 60F (Alarm off)
19Auto return to default display screen
  • 19 ESP (Return to default display screen - default): If selected, no matter how users switch display screen, it will automatically return to default display screen (Input voltage / output voltage) after no button is pressed for 1 minute.
  • 19 FEP (Stay at latest screen): If selected, the display screen will stay at latest screen user finally switches.
20Backlight control
  • 20 LON (Backlight on - default)
  • 20 LOF (Backlight off)
22Beeps while primary source is interrupted
  • 22 800 (Alarm on - default)
  • 22 AOF (Alarm off)
23Overload bypass: When enabled, the unit will transfer to line mode if overload occurs in battery mode.
  • 23 698 (Bypass disable - default)
  • 23 69E (Bypass enable)
25Record Fault code
  • 25 FEN (Record enable - default)
  • 25 FdS (Record disable)
26Bulk charging voltage (C.V voltage)2.0KVA 12V default setting: 14.1V
3.2KVA 24V default setting: 28.2V
If self-defined is selected in program 5, this program can be set up. Setting range is from 12.5V to 15.5V for 2.0KVA 12V model and 25.0V to 31.5V for 3.2KVA 24V model. Increment of each click is 0.1V.
27Floating charging voltage2.0KVA 12V default setting: 13.5V
3.2KVA 24V default setting: 27.0V
If self-defined is selected in program 5, this program can be set up. Setting range is from 12.5V to 15.5V for 2.0KVA 12V model and 25.0V to 31.5V for 3.2KVA 24V model. Increment of each click is 0.1V.
29Low DC cut-off voltage2.0KVA 12V default setting: 10.0 V
3.2KVA 24V default setting: 20.0 V
If self-defined is selected in program 5, this program can be set up. Setting range is from 10.0V to12.0V for 2.0KVA 12V model and 20.0V to 24.0V for 3.2KVA 24V model. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected.
30Battery equalization
  • 30 EEN (Battery equalization enable)
  • 30 EdS (Battery equalization disable - default)
If "Flooded" or "User-Defined" is selected in program 05, this program can be set up.
31Battery equalization voltage2.0KVA 12V default setting: 14.6V
3.2KVA 24V default setting: 29.2V
Setting range is from 13.0V to 16.2V for 2.0KVA 12V model and 25.0V to 31.5V for 3.2KVA 24V model. Increment of each click is 0.1V.
33Battery equalized time60min (default)
Setting range is from 5min to 900min. Increment of each click is 5min.
34Battery equalized timeout120min (default)
Setting range is from 5min to 900 min. Increment of each click is 5 min.
35Equalization interval30days (default)
Setting range is from 0 to 90 days. Increment of each click is 1 day.
36Equalization activated immediately
  • 36 AEN (Enable)
  • 36 EdS (Disable - default)
If equalization function is enabled in program 30, this program can be set up. If "Enable" is selected in this program, it's to activate battery equalization immediately and LCD main page will shows "E9". If "Disable" is selected, it will cancel equalization function until next activated equalization time arrives based on program 35 setting. At this time, "E9" will not be shown in LCD main page.

5.5 Operating Mode Description

Operation modeDescriptionLCD display
Standby mode / Power saving modeNo output is supplied by the unit but it still can charge batteries.Charging by utility and PV energy.
Charging by utility.
Charging by PV energy.
No charging.
Fault modePV energy and utility can charge batteries.Charging by utility and PV energy.
Charging by utility.
Charging by PV energy.
No charging.
Line ModeThe unit will provide output power from the mains. It will also charge the battery at line mode.Charging by utility and PV energy.
Charging by utility.
If "solar first" is selected as output source priority and solar energy is not sufficient to provide the load, solar energy and the utility will provide the loads and charge the battery at the same time.
Battery ModeThe unit will provide output power from battery and PV power.Power from battery and PV energy.
PV energy will supply power to the loads and charge battery at the same time.
Power from battery only.

5.6 Battery Equalization Description

Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize battery periodically.

How to Apply Equalization Function
You must enable battery equalization function in monitoring LCD setting program 30 first. Then, you may apply this function in device by either one of following methods:

  1. Setting equalization interval in program 35.
  2. Active equalization immediately in program 36.

When to Equalize
In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter Equalize stage.

Battery Equalization Stages Diagram
Battery Equalization Stages: Bulk, Absorption, Float, Equalize.

Equalize charging time and timeout
In Equalize stage, the controller will supply power to charge battery as much as possible until battery voltage raises to battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until setting battery equalized time is arrived.

Equalize Charging Time Diagram
Equalize Charging Time Diagram.

However, in Equalize stage, when battery equalized time is expired and battery voltage doesn't rise to battery equalization voltage point, the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage. If battery voltage is still lower than battery equalization voltage when battery equalized timeout setting is over, the charge controller will stop equalization and return to float stage.

Equalize Charging Timeout Diagram
Equalize Charging Timeout Diagram.

6. Maintenance

6.1 Overview (Anti-Dust Kit)

Every inverter is already installed with anti-dust kit from factory. Inverter will automatically detect this kit and activate internal thermal sensor to adjust internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environment.

6.2 Clearance and Maintenance (Anti-Dust Kit)

Step 1: Please remove screws as below.

Removing screws for anti-dust kit maintenance
Step 1: Remove screws to access the anti-dust kit.

Step 2: Then, dustproof case can be removed and take out air filter foam as shown in below chart.

Removing dustproof case and air filter foam
Step 2: Remove dustproof case and air filter foam.

Step 3: Clean air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

7. Troubleshooting

7.1 Fault Reference Code

Fault CodeFault EventIcon on
01Fan is locked when inverter is off.01
02Over temperature02
03Battery voltage is too high03
04Battery voltage is too low04
05Output short circuited or over temperature is detected by internal converter components.05
06Output voltage is too high.06
07Overload time out07
08Bus voltage is too high08
09Bus soft start failed09
51Over current or surge51
52Bus voltage is too low52
53Inverter soft start failed53
55Over DC voltage in AC output55
57Current sensor failed57
58Output voltage is too low58
59PV voltage is over limitation59

7.2 Warning Indicator

Warning CodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
OVER LOAD
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9

7.3 Troubleshooting Table

ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer will be active for 3 seconds and then complete off.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. The battery voltage is far too low. (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for replacing the fuse.
2. Re-charge battery.
3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.Green LED is flashing.Insufficient quality of AC power. (Shore or Generator)1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance)
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Fault code 07Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Fault code 02Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Buzzer beeps continuously and red LED is on.Fault code 03Battery is over-charged. The battery voltage is too high.Return to repair center. Check if spec and quantity of batteries are meet requirements.
Fault code 01Fan faultReplace the fan.
Fault code 06/58Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)1. Reduce the connected load.
2. Return to repair center
Fault code 08/09/53/57Internal components failed.Return to repair center.
Fault code 51Over current or surge.Restart the unit, if the error happens again, please return to repair center.
Fault code 52Bus voltage is too low.
Fault code 55Output voltage is unbalanced.

8. Specifications

8.1 Table 1 Line Mode Specifications

INVERTER MODEL2.0KVA-12V
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)
Output Power Derating Curve
Output Power Derating: When AC input voltage drops to 170V, the output power will be derated.

8.2 Table 2 Inverter Mode Specifications

INVERTER MODEL2.0KVA-12V
Rated Output Power2000VA/1600W
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac ±5%
Output Frequency50Hz
Peak Efficiency94%
Overload Protection5s@ >150% load; 10s@ 100%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage12Vdc
Cold Start Voltage11.5Vdc
Low DC Warning Voltage @ load < 50%11.0Vdc
Low DC Warning Voltage @ load > 50%10.5Vdc
Low DC Warning Return Voltage @ load < 50%11.5Vdc
Low DC Warning Return Voltage @ load > 50%11.0Vdc
Low DC Cut-off Voltage @ load < 50%10.2Vdc
Low DC Cut-off Voltage @ load > 50%9.6Vdc
High DC Recovery Voltage14.0Vdc
High DC Cut-off Voltage16.0Vdc
No Load Power Consumption<25W

8.3 Table 3 Charge Mode Specifications

INVERTER MODEL2.0KVA-12V
Utility Charging Mode
Charging Algorithm3-Step
AC Charging Current (Max)60Amp (@Vi/p=230Vac)
Bulk Charging Flooded Battery Voltage14.6
AGM / Gel Battery14.1
Floating Charging Voltage13.5Vdc
MPPT Solar Charging Mode
Max. PV Array Power2000W
Nominal PV Voltage240Vdc
PV Array MPPT Voltage Range30~400Vdc
Max. PV Array Open Circuit Voltage400Vdc
Max Charging Current (AC charger plus solar charger)80Amp

8.4 Table 4 General Specifications

INVERTER MODEL2.0KVA-12V
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~ 60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm357X273X95
Net Weight, kg4.6

9. Warranty & Support

For technical support, warranty claims, or any inquiries, please contact:

SHENZHEN HEHEJIN INDUSTRIAL CO.,LTD
Tel/Fax: +86 755-28219903
Email: support@powmr.com
Web: www.powmr.com
Add: Henggang Street, Longgang District, Shenzhen, Guangdong, China

All products have a 1-year warranty from our store.

10. User Tips

  • Seamless UPS Mode: Users report fast transfer times when grid power drops, preventing reboots of sensitive electronics.
  • Flexible Settings: The inverter allows for easy configuration of custom charging profiles, especially useful for LiFePO4 batteries (bulk/float voltages and cut-off limits).
  • Stable Power Output: Provides a clean sine wave output, ensuring smooth operation for sensitive motors and compressor-based appliances.
  • Clear Monitoring: The LCD screen offers clear real-time monitoring of input/output voltage and load percentages.
  • Fan Operation: The cooling fan typically activates around 500 watts of load. At approximately 700 watts, the fan noise becomes noticeable.
  • Idle Power Consumption: The standard idle power consumption is around 33W.

11. Frequently Asked Questions (FAQ)

Q: Does the inverter have Wi-Fi connectivity?
A: The inverter is "WIFI Monitoring Ready!" allowing real-time performance monitoring. However, the Wi-Fi module is not included in the standard package and must be purchased separately.

12. Product Video Overview

This video provides an unboxing and feature overview of the PowMr Hybrid Solar Inverter, demonstrating its components and basic functionalities.

13. Additional Resources

For a detailed user manual in PDF format, please refer to the official document: PowMr 2KW Hybrid Solar Inverter User Manual (PDF)


Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.