1. Introduction
Thank you for purchasing the SWEVY SW-362/SW-365 Non-contact Phase Sequence Indicator. This instrument represents a significant advancement in phase sequence detection, eliminating the need to strip wires or directly contact exposed high-voltage live wires. It utilizes clamp-type non-contact induction measurement, allowing for direct clamping onto the insulation outer skin of three-phase live wires.
The indicator provides both audible and visual indications for positive or reverse phase sequences. For convenience, four strong magnets are integrated into the back of the meter, enabling it to be securely attached to distribution boxes during testing. Beyond phase sequence detection, the SW-362/SW-365 also offers functions such as live line detection, simple power electricity detection, circuit break searching, breakpoint location, and line circuit maintenance. Its fast testing capabilities, clear display, and enhanced field test security effectively protect the operator's personal safety and improve productivity, making it an essential tool for three-phase power supply phase sequence, motor detection, and line maintenance.
2. Safety Precautions
Always pay special attention to safety when using the tester. Failure to comply with safety rules may result in electric shock, personal injury, or equipment damage.
- Read this instruction manual in detail before use.
- Comply with all safety regulations and cautions listed in this manual.
- Ensure that the insulation layer of the instrument, lead wires, and clamps are not damaged, exposed, or disconnected before use.
- During testing, it is absolutely forbidden to touch any exposed tested wire conductor.
- Do not place or store the meter in high temperature, high humidity, dewy places, or under direct sunlight for prolonged periods.
- If the indicator is not used for a long time, remove the batteries.
- When replacing batteries, pay close attention to their polarity. It is strictly forbidden to replace batteries while the clamp clips are still attached to the tested wire conductor.
- If the instrument appears dangerous to continue using, stop operation immediately, seal it, and have it handled by an authorized institution.
Electrical Symbols
| Symbol | Description |
|---|---|
| ! | Extremely Dangerous: Operators must strictly adhere to safety rules; otherwise, electric shock will result in death or injury. |
| ! | Warning: Operators must strictly adhere to safety rules; otherwise, personal injury or equipment damage will occur. |
| Π | Double Insulation |
| ~ | Alternate Current (AC) |
| --- | Direct Current (DC) |
3. Product Overview & Instrument Structure
The SWEVY Non-Contact Phase Sequence Indicator is designed for ease of use and safety. It features a compact body with clearly labeled controls and indicators.

Figure 1: Instrument Structure and Product Buttons (SW362 Body Dimensions)
Key Components:
- Operate indication panel
- Test Clamps
- Clamp Lead Wire
- Meter body
- L2 phase indicator lamp
- L1 phase indicator lamp
- L3 phase indicator lamp
- Phase sequence indicator lamp (4 lamps)
- Low battery voltage indication
- Power Supply indicator
- "ON" power up key
- "OFF" power off key
- Connecting screws
- Magnet (4PCS)
- Battery cover board
Magnetic Design
The meter incorporates a magnetic design for convenient operation. Four magnets are attached to the back of the instrument, allowing it to be securely hung on a distribution box. This feature supports a load weight of up to 800g, providing hands-free operation.

Figure 2: Magnetic Design for convenient attachment
4. Technical Specifications

Figure 3: Product Parameters for SW-362 and SW-365
| Feature | Description |
|---|---|
| Model | SW-362 / SW-365 |
| Function | Phase detection (positive, reverse, default phase), live line detection, simple power electricity detection, break point location, lines circuit maintenance |
| Power Supply | DC 3V AA alkaline batteries (LR6) x 2 PCS |
| Electricity Testing Range | AC 70~1000V, 45~65Hz (sine wave continuous input) |
| Available Clamp Wire Size | SW-362: Ø1.6mm~Ø16mm SW-365: Ø10mm~Ø40mm |
| LED Display |
|
| Buzzer |
|
| Battery Check | POWER indication lamp lights up after boot up. LOW BATTERY lamp lights up when low battery. |
| Magnet | 4pcs magnets installed on the bottom plate, can be hung on distribution box, load weight 800g. |
| Automatic Shutdown | 5 minutes after power up, the meter automatically shuts down. |
| Meter Dimension | 70mm x 75mm x 30mm |
| Clamp Lead Length | 0.6m |
| Meter Weight | SW-362: 190g (excluding battery), 330g (including accessories) SW-365: 220g (excluding battery), 360g (including accessories) |
| Working Temperature | -10°C ~ 55°C; below 80%RH |
| Store Temperature | -20°C ~ 60°C; below 90%RH |
| Max Measure Voltage | AC 1000V |
| Insulation Strength | 5.4kV/rms |
| Max Rated Power | 300mVA |
| Suitable Safety Standard | EN61010-1: 2001, EN61010-031: 2002, Pollution Grade 2, CAT III 1000V, Transient over voltage 6000V |
5. Setup: Battery Installation
Pay attention to the battery polarity!
The SWEVY Phase Sequence Indicator uses 2 AA alkaline batteries (LR6).
- Ensure the instrument is powered OFF by pressing the "OFF" key.
- Before installing or replacing batteries, ensure the clamp clips are removed from any tested wires. Do not replace batteries during a test.
- Loosen the screw on the backside of the meter.
- Remove the battery cover.
- Insert new AA batteries, paying close attention to the correct polarity (+/-) as indicated inside the battery compartment.
- Close the battery back cover and tighten the screw.
- Press the "ON" key to power on the instrument and check if it starts normally. If it does not start, verify battery power and correct installation.

Figure 4: Battery Compartment Design
6. Operation
6.1. Phase Sequence Detection
Danger! High voltage! Please pay attention to safety!
- Connection: Clamp the three test clamps onto the three phase wires respectively. Ensure the detected wire is clamped at the designated mark on the clamp.
- Power On: Press the red "ON" power key. The power indicator lamp should light up. If it does not, the battery may be low, or the instrument may require inspection (refer to troubleshooting).
- Detection:
- Positive Phase Sequence (L1-L2-L3 or U-V-W): If the four phase sequence indicators light up in a clockwise direction, and the instrument emits intermittent short chirps, the clamped phase line is in a positive phase sequence.
- Reverse Phase Sequence (L3-L2-L1 or W-V-U): If the four phase sequence indicators light up in a counterclockwise direction, and the instrument emits a continuous long sound, the clamped phase line is in a reverse phase sequence.
- Power Off: Press the white "OFF" key to shut down. The instrument will automatically shut down after approximately 5 minutes of inactivity to conserve battery power.
Video 1: Demonstration of Non-Contact Phase Sequence Detection, including compact design, non-contact jaws, magnetic attraction, and detection of positive, phase loss, and reverse phases.

Figure 5: Phase Sequence Detection in action (Positive Phase)

Figure 6: HD Indicator Light Indication for various phase states
6.2. Live Wire Check / Simple Electricity Detection
Danger! High voltage! Please pay attention to safety!
Use any of the clamps to clamp onto the tested wire. If the conductor has electricity (within the live line voltage range of AC70~1000V), the L1/U, L2/V, or L3/W lamp will light up, indicating that the wire is live.
| Clamp Mark | Lamp Light Up Symbol |
|---|---|
| L1/U (Red/Yellow) | L1/U lamp light up |
| L2/V (White/Green) | L2/V lamp light up |
| L3/W (Blue/Red) | L3/W lamp light up |
6.3. Breakpoint Location / Open Circuit Searching
Danger! High voltage! Please pay attention to safety!
- Use any of the clamps to clamp onto the three-phase line separately. If it is a default phase, the L1, L2, or L3 lamp will not light up.
- Clamp onto the tested wire along the maintenance line. If the lamp (L1, L2, or L3) at the tested point does not light up, it indicates an open circuit before this point.
- By shortening the position of the measuring point of the clamp, you can accurately pinpoint the open circuit location (breakpoint). This function is highly convenient and safe for line maintenance and troubleshooting.

Figure 7: Circuit Breakdown Troubleshooting
7. Maintenance
Regular maintenance ensures the longevity and accuracy of your SWEVY Phase Sequence Indicator.
- Keep the instrument clean and free from dust and moisture.
- Store the instrument in a cool, dry place, away from direct sunlight and extreme temperatures.
- If the instrument is not used for an extended period, remove the batteries to prevent leakage.
- Refer to the Battery Installation section (Section 5) for proper battery replacement procedures.
8. Troubleshooting (FAQ)
| Fault Phenomenon | Possible Causes | Solution |
|---|---|---|
| Cannot power on (LED power indicator is not lit, no display) | Without batteries | Install batteries |
| Wrong battery type | Replace with right type | |
| Low battery power | Replace the new batteries | |
| Faulty battery polarity | Install batteries in correct polarity | |
| Poor contact of battery contacts | Replace the battery contacts | |
| Start up normal, but cannot detect | The three phase wires are not electrified | This is not an instrument fault; ensure power is present. |
| Failed to clamp the wire | Clamp again, referring to the manual for correct placement. | |
| Lead wire break | Change the lead wire. | |
| Defect of circuit component | Repair or replace the PCB. |
9. User Tips
- Always Check Batteries: If the device doesn't power on or indicators are dim, the first step should always be to check and replace the batteries, ensuring correct polarity.
- Secure Clamping: For accurate readings, ensure the non-contact jaws are properly clamped onto the insulated wires at the designated mark. Loose connections can lead to incorrect or no detection.
- Utilize Magnetic Feature: Take advantage of the built-in magnets to secure the device to metal surfaces like distribution boxes. This frees up your hands for safer and more convenient testing.
- Understand Indicator Patterns: Familiarize yourself with the different LED light patterns and buzzer sounds for positive phase, reverse phase, phase loss, and live wire detection to quickly interpret results.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.
Manufacturer: Guangzhou Suwei Electronic Technology Co., Ltd
User Manual (PDF): A detailed user manual in PDF format is available for download. Please refer to the following link for the official document: SWEVY SW-362/SW-365 User Manual (PDF)