SUMRY MPS VIII ECO

Contents

SUMRY MPS VIII ECO Series Hybrid Solar Inverter User Manual

Models: 3.6KW / 4.2KW / 6.2KW

1. Introduction

This manual describes the assembly, installation, operation, and troubleshooting of the SUMRY MPS VIII ECO Series Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference. This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support in a compact size. Its comprehensive LCD display allows for user-configurable settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

1.1. Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/Over temperature/short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function
  • Optional WIFI/GPRS communication
List of key features of the SUMRY Hybrid Solar Inverter
Key features of the SUMRY Hybrid Solar Inverter.

1.2. Basic System Architecture

The following illustration shows a basic application for this inverter/charger, including connections for solar panels, utility grid, generator, external battery packs, and home appliances. This inverter can power various appliances in home or office environments, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

Basic System Architecture diagram showing connections for solar panels, utility grid, generator, inverter, battery, and AC loads.
Basic System Architecture for the Hybrid Solar Inverter.

For detailed information, you may also refer to the User Manual (PDF).

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  3. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  4. CAUTION – Only qualified personnel can install this device with battery. NEVER charge a frozen battery.
  5. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  6. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  7. Please strictly follow installation procedures when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
  8. One piece of 150A fuse is provided as over-current protection for the battery supply.
  9. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  10. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  11. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.
Safety protection icons including under-voltage, overvoltage, overload, overheating, and short circuit protection.
Comprehensive safety protections of the inverter.
Icons representing various protection features: Overload Protection, Overheating Protection, High Low Voltage protection, Battery Protection, Short Circuit Protection, Overcurrent Protection, Anti Reverse protection, Power Failure Protection.
Comprehensive protection features.

3. Product Overview

The SUMRY MPS VIII ECO Series Hybrid Solar Inverter is designed for both on-grid and off-grid applications, providing a 100% true output DC 24V/48V. It features a pure sine wave output, can run without a battery, and includes a built-in MPPT solar charger with high PV input voltage range.

Four views of the product: front, side, back, and a perspective view, showing the overall design and ports.
Product Overview: Front, Side, Back, and Perspective Views.
Key features of the On/Off Grid Solar Inverter, including pure sine wave output, battery-less operation, built-in 120A MPPT solar charge, high PV input voltage range, dual communication ports, and dual output.
Key features of the On/Off Grid Solar Inverter.
Dimensions of the inverter (420mm D x 310mm W x 110mm H) and a close-up of the communication ports: BMS RS485 and WiFi RS232.
Inverter Dimensions and Communication Ports.
Product overview showing the rear panel with numbered ports: 1 AC input, 2 Main output, 3 Second output, 4 Battery communication RS-485 port, 5 WIFI communication RS-232 port, 6 PV input, 7 Battery input.
Rear Panel Port Overview.

4. Installation

4.1. Unpacking and Inspection

Before installation, please inspect the unit. Ensure that nothing inside the package is damaged. You should have received the following items:

  • The inverter unit x 1
  • User manual x 1

The product demonstration video below shows the unboxing and initial setup steps.

Product Unboxing and Initial Wiring Demonstration.

4.2. Preparation

Before connecting any lines, remove the screws under the machine and then remove the bottom cover plate.

4.3. Mounting the Unit

Consider the following points when selecting where to install the inverter:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to adhere it to the wall vertically.
  • Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.

WARNING: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two M6 screws.

4.4. Battery Connection

CAUTION: For safety and regulatory compliance, it is required to install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for required fuse or breaker size.

Model Wire Size Cable (mm²) Torque value (max)
3.6KW/4.2KW/6.2KW 1 x 2AWG 25 2 Nm

WARNING! All wiring must be performed by qualified personnel. It's very important to use appropriate cable for battery connection to reduce risk of injury.

Follow these steps for battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
Diagram showing how to connect multiple 12V battery packs in series to 6.2KW and 4.2KW inverters.
Battery Pack Connection Diagram.
  1. Insert the battery wires flatly into the inverter's battery connectors and ensure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Verify that the polarity is correct at both the battery and the inverter/charger, and that conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.

CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).

Diagram showing battery types compatible with the inverter: GEL, FLD (Flooded), LI (Lithium-iron phosphate), LI (Lithium-ion), SLD (AGM/Sealed), and USER (User custom Battery).
Compatible Battery Types.

4.5. AC Input/Output Connection

CAUTION: Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and fully protected from overcurrent. Recommended AC breaker specs: 32A for 3.6KW/4.2KW and 50A for 6.2KW.

CAUTION: There are two terminal blocks marked "IN" and "OUT". Do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, use the proper recommended cable size as below.

Model Gauge Cable (mm²) Torque Value
3.6KW/4.2KW 12 AWG 4 1.2 Nm
6.2KW 10 AWG 6 1.2 Nm

Follow these steps to implement AC input/output connection:

  1. Before making AC input/output connections, ensure the DC protector or disconnector is open first.
  2. Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
  3. Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue))

WARNING: Ensure the AC power source is disconnected before attempting to hardwire it to the unit.

  1. Then, insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue))
  2. Make sure the wires are securely connected.
Wiring and technical specifications diagram for the inverter, showing connections for AC input, AC output, PV input, and battery, along with cable size recommendations.
Detailed Wiring and Technical Specifications.

4.6. PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, use the proper recommended cable size as below.

Model Wire Size Cable (mm²) Torque value (max)
3.6KW/4.2KW/6.2KW 1 x 12AWG 4 1.2 Nm

PV Module Selection:

When selecting proper PV modules, consider the following parameters:

  1. Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
INVERTER MODEL 3.6KW/4.2KW 6.2KW
Max. PV Array Open Circuit Voltage 500Vdc
PV Array MPPT Voltage Range 60Vdc~450Vdc

Follow these steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.
Diagram showing the inverter installed on a house with solar panels, highlighting the MPPT solar charge and high PV input range of 60-450VDC.
MPPT Solar Charge with High PV Input Range.

4.7. Final Assembly

After connecting all wirings, put the bottom cover back by screwing the two screws.

4.8. Communication Connection

1. Wi-Fi Cloud Communication (Optional):

Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown on your mobile phone APP or computer webpage.

2. GPRS Cloud Communication (Optional):

Use the supplied communication cable to connect to the inverter and GPRS module, then apply external power to the GPRS module. Download the APP and install it from the APP store, and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown on your mobile phone APP or computer webpage.

3. Battery Communication:

Communication between the battery and the inverter is achieved through the battery communication interface, allowing the inverter and lithium battery to exchange information (Baud rate: 9600).

4. Lithium Battery and Inverter Connection:

If using a lithium battery with the inverter, only lithium batteries that have been matched with the BMS communication protocol are allowed.

  1. Connect the battery according to the recommended battery cable specifications.
  2. Insert the ring terminal of the battery cable into the inverter's battery connector flatly, ensuring the bolts are tightened with a torque of 2-3 Nm. Verify correct polarity and tight connection.
  3. Connect one side of the RJ45 cable to the BMS communication port of the inverter.
  4. Insert the other side of the RJ45 cable into the RS485 communication port on the lithium battery.

NOTE: If you choose a lithium battery, ensure to connect the battery and inverter with the BMS communication cable, and select the battery type as "LIB-485" mode.

Communication And Setting Of Lithium Battery

Connect the RJ45 communication cable between the inverter and battery. Confirm that the lithium battery BMS port's PIN corresponds with the inverter BMS communication port. The inverter BMS port PIN definition is below:

Pin number Port definitions
1RS485B
2RS485A
3NG
4NG
5NG
6NG
7RS485A
8RS485B
Diagram illustrating the difference between single communication and dual communication ports on the inverter. Note: ECO 4.2KW/6.2KW models will be updated to Dual Communication after July 2024.
Communication Port Types (Single vs. Dual).

5. Operation

5.1. Power ON/OFF

Once the unit is properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2. Operation and Display Panel

The operation and display panel, located on the front of the inverter, includes three indicators, four function keys, and an LCD display, showing operating status and input/output power information.

LED Indicator Description Messages
INV/AC (Green Solid On)Output is powered by utility in Line mode.Output is powered by battery or PV in battery mode.
CHG (Green Solid On)Battery is fully charged.Battery is charging.
FAULT (Red Solid On)Fault occurs in the inverter.Warning condition occurs in the inverter.
Function Key Description
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3. LCD Display Icons

The LCD display provides various icons to indicate the inverter's status and operation mode.

Icon Function description
AC Input IconIndicates the AC input.
PV Input IconIndicates the PV input.
8.8.8 KW V Hz AIndicates input voltage, input frequency, PV voltage, charger current (if PV in charging for 3.6KW models), charger power, battery voltage.
Program IconIndicates the setting programs.
Warning/Fault IconIndicates the warning and fault codes. (Warning: flashing with warning code; Fault: lighting with fault code)
Output IconIndicates output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
Battery IconBattery Information
Overload IconIndicates overload.
Mains Connection IconIndicates unit connects to the mains.
PV Panel Connection IconIndicates unit connects to the PV panel.
AC Bypass IconIndicates load is supplied by utility power.
Utility Charger IconIndicates the utility charger circuit is working.
DC/AC Inverter IconIndicates the DC/AC inverter circuit is working.
Mute IconIndicates unit alarm is disabled.

5.4. LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the “UP” or “DOWN” buttons to select setting programs, then press “ENTER” to confirm or “ESC” to exit. Detailed settings are available in the PDF manual.

5.5. Display Setting

The LCD display information switches by pressing the “UP” or “DOWN” key. The selectable information includes input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, and main CPU Version.

5.6. Operating Mode Description

The inverter supports various operating modes, including Standby, Line Mode, and Grid-Tie operation, each with specific behaviors for power supply and battery charging.

5.7. Battery Equalization

The equalization function reverses the buildup of negative chemical effects like stratification and helps remove sulfate crystals, which can reduce battery capacity. It is recommended to equalize the battery periodically.

How to Apply Equalization Function:

Enable battery equalization in monitoring LCD setting program 30. Then, you can apply this function by:

  • Setting the equalization interval in program 35.
  • Activating equalization immediately in program 36.

When to Equalize:

In the float stage, when the setting equalization interval is reached or equalization is activated immediately, the controller will enter the Equalize stage.

5.8. Mains and Lithium Battery Activation Function

  1. After 90 seconds of mains power connection to the inverter, the machine connects to the mains and starts to work.
  2. If the inverter is in lithium battery mode (item 05 is Llb or Llb-485), and the mains are connected but the battery is not, the mains activation function is automatically enabled.

5.9. Fault Reference Code

The inverter provides various fault codes to indicate specific issues. Refer to the table below for common fault codes and their descriptions.

Fault Code Fault Event Icon on
01Fan is locked when inverter is off.01 ERROR
02Over temperature02 ERROR
03Battery voltage is too high03 ERROR
04Battery voltage is too low04 ERROR
05Output short circuited or over temperature is detected by internal converter components.05 ERROR
06Output voltage is too high.06 ERROR
07Overload time out07 ERROR
08Bus voltage is too high08 ERROR
09Bus soft start failed09 ERROR
51Over current or surge51 ERROR
52Bus voltage is too low52 ERROR
53Inverter soft start failed53 ERROR
55Over DC voltage in AC output55 ERROR
57Current sensor failed57 ERROR
58Output voltage is too low58 ERROR
59PV voltage is over limitation59 ERROR

5.10. Warning Indicator

The inverter provides various warning indicators to alert users of potential issues. Refer to the table below for common warning codes and their descriptions.

Warning Code Warning Event Audible Alarm Icon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9
bPBattery is not connectedNonebP

6. Maintenance

6.1. Clearance and Maintenance for Anti-Dust Kit

Every inverter comes with an anti-dust kit installed from the factory. The inverter automatically detects this kit and activates an internal thermal sensor to adjust the internal temperature. This kit also keeps dust out of your inverter, increasing product reliability in harsh environments.

Step 1: Loosen the screw in a counterclockwise direction on the top of the inverter.

Step 2: Remove the dustproof case and take out the air filter foam as shown in the diagram below.

Step 3: Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back into the inverter.

NOTICE: The anti-dust kit should be cleaned every one month.

7. Specifications

The SUMRY MPS VIII ECO Series Hybrid Solar Inverter is available in 3.6KW, 4.2KW, and 6.2KW models, each with specific electrical and operational characteristics.

Detailed product data sheet with specifications for MPS-VIII ECO 3.6KW, 4.2KW, and 6.2KW models, covering PV input, Grid-Tie output, AC input, Two Load Output Power, Battery Charger, and Hybrid Operation.
Product Data Sheet with Detailed Specifications.

7.1. Line Mode Specifications

INVERTER MODEL 3.6KW 4.2KW 6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

7.2. Inverter Mode Specifications

INVERTER MODEL 3.6KW 4.2KW 6.2KW
Rated Output Power3.6KW4.2KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @load < 50%22.0Vdc44.0Vdc
Low DC Warning Voltage @load ≥ 50%21.0Vdc42.0Vdc
Low DC Warning Return Voltage @load < 50%22.5Vdc45.0Vdc
Low DC Warning Return Voltage @load ≥ 50%22.0Vdc44.0Vdc
Low DC Cut-off Voltage @load < 50%20.5Vdc41.0Vdc
Low DC Cut-off Voltage @load ≥ 50%20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption30W35W50W

7.3. Two Load Output Power

INVERTER MODEL 3.6KW 4.2KW 6.2KW
Full Load3600W4200W6200W
Maximum Main Load3600W4200W6200W
Second Load Range720W~2520W840W~2940W1240W~4340W
Main Load Cut Off Voltage22VDC44VDC
Main Load Return Voltage26VDC52VDC

7.4. Charge Mode Specifications

Utility Charging Mode 3.6KW 4.2KW 6.2KW
Charging Algorithm3-Step
AC Charging Current (Max)100Amp (@VI/P=230Vac)
Bulk Charging Voltage (Flooded Battery)29.258.4
Bulk Charging Voltage (AGM / Gel Battery)28.256.4
Floating Charging Voltage27Vdc54Vdc

MPPT Solar Charging Mode

INVERTER MODEL 3.6KW 4.2KW 6.2KW
Max. PV Array Power6200W6500W
Nominal PV Voltage240Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp120Amp120Amp

7.5. Grid-Tie Operation

INVERTER MODEL 3.6KW 4.2KW 6.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current15.7A18.2A26.9A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)97%

7.6. General Specifications

INVERTER MODEL 3.6KW 4.2KW 6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm358×442×116
Net Weight, kg8.08.08.9

8. Troubleshooting

Refer to the table below for common issues, their possible causes, and recommended solutions.

Problem LCD/LED/Buzzer Explanation / Possible cause What to do
Unit shuts down automatically during startup process. LCD/LEDs and buzzer will be active for 3 seconds and then complete off. The battery voltage is too low (<1.91V/Cell) 1. Re-charge battery.
2. Replace battery.
No response after power on. No indication. 1. The battery voltage is far too low. (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for replacing the fuse.
2. Re-charge battery.
3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing. Input protector is tripped Check if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode. Green LED is flashing. Insufficient quality of AC power. (Shore or Generator) 1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliance)
Green LED is flashing. Set "Solar First" as the priority of output source. Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly. LCD display and LEDs are flashing Battery is disconnected. Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on. Fault code 07 Overload error. The inverter is overload 110% and time is up. Reduce the connected load by switching off some equipment.
Fault code 05 Output short circuited. Check if wiring is connected well and remove abnormal load.
Fault code 02 Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 03 Battery is over-charged. Return to repair center. Check if spec and quantity of batteries are meet requirements.
Fault code 01 Fan fault Replace the fan.
Fault code 06/58 Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) 1. Reduce the connected load.
2. Return to repair center
Fault code 08/09/53/57 Internal components failed. Return to repair center.
Fault code 51 Over current or surge. Restart the unit, if the error happens again, please return to repair center.
Fault code 52 Bus voltage is too low.
Fault code 55 Output voltage is unbalanced.

9. User Tips

  • Voltage Compatibility: The inverter supports 24VDC or 48VDC battery input and provides 120VAC or 220VAC output. Some models may specifically offer 127V output. Always verify the output voltage matches your home's electrical system before connecting appliances.
  • Battery Type: Ensure your battery type (Lithium, Lead-acid, etc.) is correctly configured in the LCD settings (Program 05) for optimal charging and performance. For lithium batteries, use "LIB-485" mode and ensure BMS communication is established.
  • Cable Sizing: Always use the recommended cable sizes for battery, AC input/output, and PV connections to prevent overheating and ensure efficient operation.
  • Monitoring: Utilize the optional WIFI/GPRS communication features to monitor your inverter's status and performance via a mobile app or computer webpage.

10. Warranty and Support

All SUMRY products come with a 1-year warranty from the date of purchase. Our support team is available to provide assistance with any issues you may encounter. We aim for a 24-hour response time for inquiries.

SUMRY is a high-tech enterprise specializing in R&D, production, and sales of power supply products, with 17 years of experience in the field. We are committed to building high-efficiency products and high-end brands.

Images showing EU local warehouses, a 1-year warranty for all products, and 24-hour response time for customer service.
Warranty and Service Information.
Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.