1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the SUMRY MPS VIII ECO Series Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference. This multi-function inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support in a compact size. Its comprehensive LCD display allows for user-configurable settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
1.1. Features
- Pure sine wave inverter
- Configurable input voltage range for home appliances and personal computers via LCD setting
- Configurable battery charging current based on applications via LCD setting
- Configurable AC/Solar Charger priority via LCD setting
- Compatible with mains voltage or generator power
- Auto restart while AC is recovering
- Overload/Over temperature/short circuit protection
- Smart battery charger design for optimized battery performance
- Cold start function
- Optional WIFI/GPRS communication
1.2. Basic System Architecture
The following illustration shows a basic application for this inverter/charger, including connections for solar panels, utility grid, generator, external battery packs, and home appliances. This inverter can power various appliances in home or office environments, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.
For detailed information, you may also refer to the User Manual (PDF).
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with battery. NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedures when you want to disconnect AC or DC terminals. Refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.
3. Product Overview
The SUMRY MPS VIII ECO Series Hybrid Solar Inverter is designed for both on-grid and off-grid applications, providing a 100% true output DC 24V/48V. It features a pure sine wave output, can run without a battery, and includes a built-in MPPT solar charger with high PV input voltage range.
4. Installation
4.1. Unpacking and Inspection
Before installation, please inspect the unit. Ensure that nothing inside the package is damaged. You should have received the following items:
- The inverter unit x 1
- User manual x 1
The product demonstration video below shows the unboxing and initial setup steps.
4.2. Preparation
Before connecting any lines, remove the screws under the machine and then remove the bottom cover plate.
4.3. Mounting the Unit
Consider the following points when selecting where to install the inverter:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to adhere it to the wall vertically.
- Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.
WARNING: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two M6 screws.
4.4. Battery Connection
CAUTION: For safety and regulatory compliance, it is required to install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for required fuse or breaker size.
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 3.6KW/4.2KW/6.2KW | 1 x 2AWG | 25 | 2 Nm |
WARNING! All wiring must be performed by qualified personnel. It's very important to use appropriate cable for battery connection to reduce risk of injury.
Follow these steps for battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the diagram below.
- Insert the battery wires flatly into the inverter's battery connectors and ensure the bolts are tightened with a torque of 2 Nm in a clockwise direction. Verify that the polarity is correct at both the battery and the inverter/charger, and that conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION: Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) is connected to negative (-).
4.5. AC Input/Output Connection
CAUTION: Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and fully protected from overcurrent. Recommended AC breaker specs: 32A for 3.6KW/4.2KW and 50A for 6.2KW.
CAUTION: There are two terminal blocks marked "IN" and "OUT". Do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel. It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, use the proper recommended cable size as below.
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 3.6KW/4.2KW | 12 AWG | 4 | 1.2 Nm |
| 6.2KW | 10 AWG | 6 | 1.2 Nm |
Follow these steps to implement AC input/output connection:
- Before making AC input/output connections, ensure the DC protector or disconnector is open first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3 mm.
- Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue))
WARNING: Ensure the AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to the polarities indicated on the terminal block and tighten the terminal screws. (L→LINE (brown or black), N→Neutral (blue))
- Make sure the wires are securely connected.
4.6. PV Connection
CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, use the proper recommended cable size as below.
| Model | Wire Size | Cable (mm²) | Torque value (max) |
|---|---|---|---|
| 3.6KW/4.2KW/6.2KW | 1 x 12AWG | 4 | 1.2 Nm |
PV Module Selection:
When selecting proper PV modules, consider the following parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
| INVERTER MODEL | 3.6KW/4.2KW | 6.2KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~450Vdc | |
Follow these steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Suggest putting bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.
4.7. Final Assembly
After connecting all wirings, put the bottom cover back by screwing the two screws.
4.8. Communication Connection
1. Wi-Fi Cloud Communication (Optional):
Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown on your mobile phone APP or computer webpage.
2. GPRS Cloud Communication (Optional):
Use the supplied communication cable to connect to the inverter and GPRS module, then apply external power to the GPRS module. Download the APP and install it from the APP store, and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown on your mobile phone APP or computer webpage.
3. Battery Communication:
Communication between the battery and the inverter is achieved through the battery communication interface, allowing the inverter and lithium battery to exchange information (Baud rate: 9600).
4. Lithium Battery and Inverter Connection:
If using a lithium battery with the inverter, only lithium batteries that have been matched with the BMS communication protocol are allowed.
- Connect the battery according to the recommended battery cable specifications.
- Insert the ring terminal of the battery cable into the inverter's battery connector flatly, ensuring the bolts are tightened with a torque of 2-3 Nm. Verify correct polarity and tight connection.
- Connect one side of the RJ45 cable to the BMS communication port of the inverter.
- Insert the other side of the RJ45 cable into the RS485 communication port on the lithium battery.
NOTE: If you choose a lithium battery, ensure to connect the battery and inverter with the BMS communication cable, and select the battery type as "LIB-485" mode.
Communication And Setting Of Lithium Battery
Connect the RJ45 communication cable between the inverter and battery. Confirm that the lithium battery BMS port's PIN corresponds with the inverter BMS communication port. The inverter BMS port PIN definition is below:
| Pin number | Port definitions |
|---|---|
| 1 | RS485B |
| 2 | RS485A |
| 3 | NG |
| 4 | NG |
| 5 | NG |
| 6 | NG |
| 7 | RS485A |
| 8 | RS485B |
5. Operation
5.1. Power ON/OFF
Once the unit is properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
5.2. Operation and Display Panel
The operation and display panel, located on the front of the inverter, includes three indicators, four function keys, and an LCD display, showing operating status and input/output power information.
| LED Indicator | Description | Messages |
|---|---|---|
| INV/AC (Green Solid On) | Output is powered by utility in Line mode. | Output is powered by battery or PV in battery mode. |
| CHG (Green Solid On) | Battery is fully charged. | Battery is charging. |
| FAULT (Red Solid On) | Fault occurs in the inverter. | Warning condition occurs in the inverter. |
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3. LCD Display Icons
The LCD display provides various icons to indicate the inverter's status and operation mode.
| Icon | Function description |
|---|---|
| AC Input Icon | Indicates the AC input. |
| PV Input Icon | Indicates the PV input. |
| 8.8.8 KW V Hz A | Indicates input voltage, input frequency, PV voltage, charger current (if PV in charging for 3.6KW models), charger power, battery voltage. |
| Program Icon | Indicates the setting programs. |
| Warning/Fault Icon | Indicates the warning and fault codes. (Warning: flashing with warning code; Fault: lighting with fault code) |
| Output Icon | Indicates output voltage, output frequency, load percent, load in VA, load in Watt and discharging current. |
| Battery Icon | Battery Information |
| Overload Icon | Indicates overload. |
| Mains Connection Icon | Indicates unit connects to the mains. |
| PV Panel Connection Icon | Indicates unit connects to the PV panel. |
| AC Bypass Icon | Indicates load is supplied by utility power. |
| Utility Charger Icon | Indicates the utility charger circuit is working. |
| DC/AC Inverter Icon | Indicates the DC/AC inverter circuit is working. |
| Mute Icon | Indicates unit alarm is disabled. |
5.4. LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the “UP” or “DOWN” buttons to select setting programs, then press “ENTER” to confirm or “ESC” to exit. Detailed settings are available in the PDF manual.
5.5. Display Setting
The LCD display information switches by pressing the “UP” or “DOWN” key. The selectable information includes input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, and main CPU Version.
5.6. Operating Mode Description
The inverter supports various operating modes, including Standby, Line Mode, and Grid-Tie operation, each with specific behaviors for power supply and battery charging.
5.7. Battery Equalization
The equalization function reverses the buildup of negative chemical effects like stratification and helps remove sulfate crystals, which can reduce battery capacity. It is recommended to equalize the battery periodically.
How to Apply Equalization Function:
Enable battery equalization in monitoring LCD setting program 30. Then, you can apply this function by:
- Setting the equalization interval in program 35.
- Activating equalization immediately in program 36.
When to Equalize:
In the float stage, when the setting equalization interval is reached or equalization is activated immediately, the controller will enter the Equalize stage.
5.8. Mains and Lithium Battery Activation Function
- After 90 seconds of mains power connection to the inverter, the machine connects to the mains and starts to work.
- If the inverter is in lithium battery mode (item 05 is Llb or Llb-485), and the mains are connected but the battery is not, the mains activation function is automatically enabled.
5.9. Fault Reference Code
The inverter provides various fault codes to indicate specific issues. Refer to the table below for common fault codes and their descriptions.
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | 01 ERROR |
| 02 | Over temperature | 02 ERROR |
| 03 | Battery voltage is too high | 03 ERROR |
| 04 | Battery voltage is too low | 04 ERROR |
| 05 | Output short circuited or over temperature is detected by internal converter components. | 05 ERROR |
| 06 | Output voltage is too high. | 06 ERROR |
| 07 | Overload time out | 07 ERROR |
| 08 | Bus voltage is too high | 08 ERROR |
| 09 | Bus soft start failed | 09 ERROR |
| 51 | Over current or surge | 51 ERROR |
| 52 | Bus voltage is too low | 52 ERROR |
| 53 | Inverter soft start failed | 53 ERROR |
| 55 | Over DC voltage in AC output | 55 ERROR |
| 57 | Current sensor failed | 57 ERROR |
| 58 | Output voltage is too low | 58 ERROR |
| 59 | PV voltage is over limitation | 59 ERROR |
5.10. Warning Indicator
The inverter provides various warning indicators to alert users of potential issues. Refer to the table below for common warning codes and their descriptions.
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | 01 |
| 03 | Battery is over-charged | Beep once every second | 03 |
| 04 | Low battery | Beep once every second | 04 |
| 07 | Overload | Beep once every 0.5 second | 07 |
| 10 | Output power derating | Beep twice every 3 seconds | 10 |
| 15 | PV energy is low. | Beep twice every 3 seconds | 15 |
| E9 | Battery equalization | None | E9 |
| bP | Battery is not connected | None | bP |
6. Maintenance
6.1. Clearance and Maintenance for Anti-Dust Kit
Every inverter comes with an anti-dust kit installed from the factory. The inverter automatically detects this kit and activates an internal thermal sensor to adjust the internal temperature. This kit also keeps dust out of your inverter, increasing product reliability in harsh environments.
Step 1: Loosen the screw in a counterclockwise direction on the top of the inverter.
Step 2: Remove the dustproof case and take out the air filter foam as shown in the diagram below.
Step 3: Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back into the inverter.
NOTICE: The anti-dust kit should be cleaned every one month.
7. Specifications
The SUMRY MPS VIII ECO Series Hybrid Solar Inverter is available in 3.6KW, 4.2KW, and 6.2KW models, each with specific electrical and operational characteristics.
7.1. Line Mode Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | ||
| Nominal Input Voltage | 230Vac | ||
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | ||
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | ||
| High Loss Voltage | 280Vac±7V | ||
| High Loss Return Voltage | 270Vac±7V | ||
| Max AC Input Voltage | 300Vac | ||
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | ||
| Low Loss Frequency | 40±1Hz | ||
| Low Loss Return Frequency | 42±1Hz | ||
| High Loss Frequency | 65±1Hz | ||
| High Loss Return Frequency | 63±1Hz | ||
| Output Short Circuit Protection | Circuit Breaker | ||
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | ||
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | ||
7.2. Inverter Mode Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Rated Output Power | 3.6KW | 4.2KW | 6.2KW |
| Output Voltage Waveform | Pure Sine Wave | ||
| Output Voltage Regulation | 230Vac±5% | ||
| Output Frequency | 50Hz | ||
| Peak Efficiency | 93% | ||
| Overload Protection | 3s@≥150% load; 5s@101%~150% load | ||
| Surge Capacity | 2* rated power for 5 seconds | ||
| Nominal DC Input Voltage | 24Vdc | 48Vdc | |
| Cold Start Voltage | 23.0Vdc | 46.0Vdc | |
| Low DC Warning Voltage @load < 50% | 22.0Vdc | 44.0Vdc | |
| Low DC Warning Voltage @load ≥ 50% | 21.0Vdc | 42.0Vdc | |
| Low DC Warning Return Voltage @load < 50% | 22.5Vdc | 45.0Vdc | |
| Low DC Warning Return Voltage @load ≥ 50% | 22.0Vdc | 44.0Vdc | |
| Low DC Cut-off Voltage @load < 50% | 20.5Vdc | 41.0Vdc | |
| Low DC Cut-off Voltage @load ≥ 50% | 20.0Vdc | 40.0Vdc | |
| High DC Recovery Voltage | 32Vdc | 62Vdc | |
| High DC Cut-off Voltage | 33Vdc | 63Vdc | |
| No Load Power Consumption | 30W | 35W | 50W |
7.3. Two Load Output Power
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Full Load | 3600W | 4200W | 6200W |
| Maximum Main Load | 3600W | 4200W | 6200W |
| Second Load Range | 720W~2520W | 840W~2940W | 1240W~4340W |
| Main Load Cut Off Voltage | 22VDC | 44VDC | |
| Main Load Return Voltage | 26VDC | 52VDC | |
7.4. Charge Mode Specifications
| Utility Charging Mode | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Charging Algorithm | 3-Step | ||
| AC Charging Current (Max) | 100Amp (@VI/P=230Vac) | ||
| Bulk Charging Voltage (Flooded Battery) | 29.2 | 58.4 | |
| Bulk Charging Voltage (AGM / Gel Battery) | 28.2 | 56.4 | |
| Floating Charging Voltage | 27Vdc | 54Vdc | |
MPPT Solar Charging Mode
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Max. PV Array Power | 6200W | 6500W | |
| Nominal PV Voltage | 240Vdc | 360Vdc | |
| PV Array MPPT Voltage Range | 60Vdc~500Vdc | ||
| Max. PV Array Open Circuit Voltage | 500Vdc | ||
| Max Charging Current (AC charger plus solar charger) | 120Amp | 120Amp | 120Amp |
7.5. Grid-Tie Operation
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Nominal Output Voltage | 220/230/240 VAC | ||
| Feed-in Grid Voltage Range | 195~253VAC | ||
| Feed-in Grid Frequency Range | 50±1Hz/60±1Hz | ||
| Nominal Output Current | 15.7A | 18.2A | 26.9A |
| Power Factor Range | >0.99 | ||
| Maximum Conversion Efficiency (DC/AC) | 97% | ||
7.6. General Specifications
| INVERTER MODEL | 3.6KW | 4.2KW | 6.2KW |
|---|---|---|---|
| Safety Certification | CE | ||
| Operating Temperature Range | -10°C to 50°C | ||
| Storage temperature | -15°C~60°C | ||
| Humidity | 5% to 95% Relative Humidity (Non-condensing) | ||
| Dimension (D*W*H), mm | 358×442×116 | ||
| Net Weight, kg | 8.0 | 8.0 | 8.9 |
8. Troubleshooting
Refer to the table below for common issues, their possible causes, and recommended solutions.
| Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. |
1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS/Appliance) |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Temperature of internal converter component is over 120°C. Internal temperature of inverter component is over 100°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 03 | Battery is over-charged. | Return to repair center. Check if spec and quantity of batteries are meet requirements. | |
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | 1. Reduce the connected load. 2. Return to repair center |
|
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. |
9. User Tips
- Voltage Compatibility: The inverter supports 24VDC or 48VDC battery input and provides 120VAC or 220VAC output. Some models may specifically offer 127V output. Always verify the output voltage matches your home's electrical system before connecting appliances.
- Battery Type: Ensure your battery type (Lithium, Lead-acid, etc.) is correctly configured in the LCD settings (Program 05) for optimal charging and performance. For lithium batteries, use "LIB-485" mode and ensure BMS communication is established.
- Cable Sizing: Always use the recommended cable sizes for battery, AC input/output, and PV connections to prevent overheating and ensure efficient operation.
- Monitoring: Utilize the optional WIFI/GPRS communication features to monitor your inverter's status and performance via a mobile app or computer webpage.