SUMRY SP-3200/SP-4200

Contents

SUMRY SP Series Solar Inverter User Manual

Model: SP-3200/SP-4200

Brand: SUMRY

1. About This Manual

This manual describes the assembly, installation, operation, and troubleshooting of the SUMRY SP series inverter/charger. Please read this manual carefully before installation and operation. Keep this manual for future reference.

This manual provides safety and installation guidelines, as well as information on tools and wiring necessary for the inverter/charger.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION – To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION – Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It is very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedures when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
  10. GROUNDING INSTRUCTIONS – This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  11. NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  12. Warning!! Only qualified service persons are able to service this device. If errors still persist after following the troubleshooting table, please send this inverter/charger back to a local dealer or service center for maintenance.

3. Product Overview & Features

This is a multi-function inverter/charger, combining functions of inverter, MPPT solar charger, and battery charger to offer uninterruptible power support with portable size. Its comprehensive LCD display offers user-configurable and easy-accessible button operation such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.

Features

  • Pure sine wave inverter
  • Programmable supply priority for PV, battery, or Grid
  • High PV input voltage range (55~450VDC)
  • Built-in Max 110A MPPT solar charge
  • Compatible with lithium-ion battery
  • Support BMS communication with Lithium battery
  • Smart battery charge design to optimize battery life
  • Overload, high temperature, inverter output short circuit protection
  • Cold start function
  • Intelligent fan speed adjustment
  • WIFI (Optional)

Basic System Architecture

The following illustration shows the basic application for this inverter/charger. It also includes the following devices to have a complete running system: Generator or Utility, and PV modules (optional). Consult with your system integrator for other possible system architectures depending on your requirements.

This inverter can power all kinds of appliances in home or office environments, including motor-type appliances such as tube light, fan, refrigerator, and air conditioner.

Basic System Architecture Diagram
Figure 1: Hybrid Power System - Illustrates connections between solar panels, generator/utility, inverter, battery, and home appliances.

Product Components

Product Overview Diagram with Labeled Parts
Product Overview: Front, side, and bottom views with labeled components.
  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Function buttons
  6. Power on/off switch
  7. AC input
  8. AC output
  9. PV input
  10. Battery input
  11. RS-232/RS485 communication port
  12. Safety (Earth) ground

4. Installation

4.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:

  • The inverter unit x 1
  • User manual x 1

4.2 Preparation

Before connecting all wirings, please take off the bottom cover by removing two screws.

4.3 Mounting the Unit

Consider the following points before selecting where to install the unit:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level in order to allow the LCD display to be read at all times.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Be sure to keep other objects and surfaces as shown in the diagram to guarantee sufficient heat dissipation and to have enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Inverter Mounting Diagram
Mounting the Unit: Shows recommended clearances (50cm top/bottom, 20cm sides) for proper air circulation.

4.4 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between the battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to the typical amperage in the table below as required fuse or breaker size.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.

ModelWire SizeCable mm²Ring Terminal Dimensions D (mm)Ring Terminal Dimensions L (mm)Torque Value
3.8KW 24V1*3AWG226.433.22 Nm
6.2KW 48V1*4AWG226.433.22 Nm

Follow these steps to implement battery connection:

  1. Assemble battery ring terminal based on recommended battery cable and terminal size.
  2. Connect all battery packs as units require.
Battery Connection Diagram
Battery Connection: Shows wiring for 4.2KVA (2x12V) and 7.0KVA (4x12V) systems.
  1. Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and make sure the bolts are tightened with a torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charger is correctly connected and ring terminals are tightly screwed to the battery terminals.

WARNING: Shock Hazard – Installation must be performed with care due to high battery voltage in series.

CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.

CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.

CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

4.5 AC Input/Output Connection

CAUTION!! Before connecting to an AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended spec of AC breaker is 32A for 3.8KW and 50A for 6.2KW.

CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested Cable Requirement for AC Wires:

ModelGaugeTorque Value
3.8KW12 AWG1.2~1.6 Nm
6.2KW8 AWG1.4~1.6Nm

Follow these steps to implement AC input/output connection:

  1. Before making AC input/output connections, be sure to open the DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (yellow-green), L (brown or black), and N (blue).
AC Input/Output Connection Diagram
AC Input/Output Connection: Shows terminal block for AC input and output wiring.

WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.

  1. Then, insert AC output wires according to polarities indicated on the terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (yellow-green), L (brown or black), and N (blue).
  2. Make sure the wires are securely connected.

CAUTION: Important – Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.

CAUTION: Appliances such as air conditioners require at least 2~3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.

4.6 PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.

WARNING! All wiring must be performed by qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested Cable Requirement for PV Wires:

ModelWire SizeCable (mm²)Torque Value (max)
3.8KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection:

When selecting proper PV modules, please be sure to consider these parameters:

  1. Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
INVERTER MODEL3.8KW6.2KW
Max. PV Array Open Circuit Voltage450Vdc
PV Array MPPT Voltage Range55Vdc~450Vdc

Take a 250Wp PV module as an example. After considering the above two parameters, the recommended module configurations are listed in the table below.

Solar Panel Spec. (reference)SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 12 pcs)Q'ty of panelsTotal input power
250Wp
Vmp: 30.1Vdc
Imp: 8.3A
Voc: 37.7Vdc
Isc: 8.4A
Cells: 60
2 pcs in serial2 pcs500W
6 pcs in serial6 pcs1500W
8 pcs in serial8 pcs2000W
12 pcs in serial12 pcs3000W
13 pcs in serial13 pcs3250W
8 pieces in serial and 2 sets in parallel16 pcs4000W
10 pieces in serial and 2 sets in parallel20 pcs5000W

Follow these steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.
PV Connection Diagram
PV Connection: Shows how to connect PV input wires to the inverter.
  1. Make sure the wires are securely connected.
Solar Photovoltaic Panel Wiring Method
Solar Photovoltaic Panel Wiring Method: Diagrams for series and parallel connections, including voltage and current calculations. PV cable dimensions: 6-8A/mm².

4.7 Final Assembly

After connecting all wirings, please put the bottom cover back by screwing the two screws.

5. Operation

5.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.

5.2 Operation and Display Panel

The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

Operation and Display Panel
Operation and Display Panel: Shows LCD display, LED indicators, and function keys (ESC, UP, DOWN, ENTER).

LED Indicator:

LED IndicatorColorMessages
AC/INVGreenSolid On: Output is powered by utility in Line mode.
Flashing: Output is powered by battery or PV in battery mode.
CHGGreenSolid On: Battery is fully charged.
Flashing: Battery is charging.
FAULTRedSolid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

5.3 LCD Display Icons

LCD Function Description
LCD Function Description: Detailed breakdown of icons and their meanings on the LCD display, including PV input, AC input, input voltage/frequency, setting programs, fault codes, output voltage/frequency, load level, DC/AC inverter circuit, battery level, utility charger circuit, PV panel connection, mains connection, bypass, unit alarm, and overload.

Input Source Information:

IconFunction description
ACIndicates the AC input.
PVIndicates the PV input.
Input/Battery/ChargerIndicates input voltage, input frequency, PV voltage, battery voltage, and charger current.

Configuration Program and Fault Information:

IconFunction description
Setting ProgramsIndicates the setting programs.
Warning/Fault CodesIndicates the warning and fault codes. Flashing indicates warning, solid indicates fault.

Output Information:

IconFunction description
Output/LoadIndicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.

Battery Information:

IconFunction description
Battery Level/Charging StatusIndicates battery level by 0-24%, 25-49%, 50-74%, and 75-100% in battery mode and charging status in line mode.

In AC mode, it will present battery charging status. Refer to the manual for detailed status descriptions based on battery voltage.

Load Information:

IconFunction description
OverloadIndicates overload.
Load LevelIndicates the load level by 0-24%, 25-50%, 50-74%, and 75-100%.

Mode Operation Information:

IconFunction description
Mains ConnectionIndicates unit connects to the mains.
PV Panel ConnectionIndicates unit connects to the PV panel.
BYPASSIndicates load is supplied by utility power.
Utility ChargerIndicates the utility charger circuit is working.
DC/AC InverterIndicates the DC/AC inverter circuit is working.

Mute Operation:

IconFunction description
Alarm DisabledIndicates unit alarm is disabled.

5.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press the “UP” or “DOWN” button to select setting programs. Then, press the “ENTER” button to confirm the selection or the “ESC” button to exit.

Refer to the original PDF manual (page 15-21) for a detailed table of all setting programs (00-39) and their selectable options, including output source priority, maximum charging current, AC input voltage range, power saving mode, battery type, auto restart settings, output voltage, output frequency, fault code recording, bulk/floating charging voltage, low DC cut-off voltage, solar power balance, battery equalization, and equalization interval.

5.5 Display Setting

The LCD display information will be switched in turns by pressing the “UP” or “DOWN” key. The selectable information is switched in the following order: input voltage, input frequency, PV voltage, MPPT charging current, MPPT charging power, battery voltage, output voltage, output frequency, load percentage, load in VA, load in Watt, DC discharging current, main CPU Version, and second CPU Version.

Refer to the original PDF manual (page 22-23) for detailed examples of each display screen.

5.6 Operating Mode Description

Refer to the original PDF manual (page 24-25) for a detailed table describing each operating mode (Standby, Power Saving, Fault, Line, Battery) and its corresponding LCD display behavior, including charging status and power flow.

5.7 Battery Equalization Description

Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.

How to Apply Equalization Function

You must enable the battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function in the device by either one of the following methods:

  1. Setting equalization interval in program 34.
  2. Active equalization immediately in program 39.

When to Equalize

In the float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter the Equalize stage.

Battery Equalization Cycle Diagram
Battery Equalization Cycle: Illustrates the stages of battery charging including Bulk, Absorption, Float, and Equalize.

Equalize Charging Time and Timeout

In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is arrived.

Equalize Charging Time Diagram
Equalize Charging Time: Shows how the battery voltage and charging current behave during the equalization process.

However, in the Equalize stage, when the battery equalized time is expired and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.

6. Troubleshooting

6.1 Fault Reference Code

When a fault occurs, the LCD display will show a fault code. Refer to the table below for explanations and corresponding icons.

Fault CodeFault EventIcon on
01Fan is locked when inverter is off.01
02Over temperature02
03Battery voltage is too high03
04Battery voltage is too low04
05Output short circuited or over temperature is detected by internal converter components.05
06Output voltage is too high.06
07Overload time out07
08Bus voltage is too high08
09Bus soft start failed09
11Main relay failed11
51Over current or surge51
52Bus voltage is too low52
53Inverter soft start failed53
55Over DC voltage in AC output55
56Battery connection is open56
57Current sensor failed57
58Output voltage is too low58

6.2 Warning Indicator

When a warning condition occurs, the LCD display will show a warning code and the corresponding icon will flash. An audible alarm may also sound.

Warning CodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
12Solar charger stops due to low battery.12
13Solar charger stops due to high PV voltage.13
14Solar charger stops due to overload.14

6.3 General Troubleshooting

ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer will be active for 3 seconds and then complete off.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. The battery voltage is far too low. (<1.4V/Cell)
2. Battery polarity is connected reversed.
1. Check if batteries and the wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.Green LED is flashing.Insufficient quality of AC power. (Shore or Generator)1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS→Appliance)
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Buzzer beeps continuously and red LED lights up.Fault code 07Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Temperature of internal converter component is over 120°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 02Internal temperature of inverter component is over 100°C.Return to repair center.
Fault code 03Battery is over-charged.
The battery voltage is too high.
Check if spec and quantity of batteries meet requirements.
Fault code 01Fan faultReplace the fan.
Fault code 06/58Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)1. Reduce the connected load.
2. Return to repair center.
Fault code 08/09/53/57Internal components failed.Return to repair center.
Fault code 51Over current or surge.Restart the unit, if the error happens again, please return to repair center.
Fault code 52Bus voltage is too low.
Fault code 55Output voltage is unbalanced.
Fault code 56Battery is not connected well or fuse is burnt.

7. Specifications

7.1 Product Parameters

Product Parameters Table
Product Parameters: Table comparing models SP-2200, SP-3200, SP-4200, and SP-7000 with details on rated power, MAX.PV Array Power, Surge Power, MAX.Charging Current, Battery Voltage, MPPT Range@Operating Voltage, MAX. Efficiency, Dimension, and Net Weight.

7.2 Line Mode Specifications

INVERTER MODEL3.8KW 24V6.2KW 48V
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionLine mode: Circuit Breaker
Battery mode: Electronic Circuits
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)
Output power derating: When AC input voltage drops to 95V or 170V depending on models, the output power will be derated.
Output Power Derating Curve
Output Power Derating Curve: Shows how output power is reduced at lower input voltages.

7.3 Inverter Mode Specifications

INVERTER MODEL3.8KW 24V6.2KW 48V
Rated Output Power4.2KVA/3.8KW7.0KVA/6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency60Hz or 50Hz
Peak Efficiency94%
Overload Protection5s@≥150% load; 10s@110%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @load < 20%22.0Vdc44.0Vdc
Low DC Warning Voltage @20% ≤ load < 50%21.4Vdc42.8Vdc
Low DC Warning Voltage @load ≥ 50%20.2Vdc40.4Vdc
Low DC Warning Return Voltage @load < 20%23.0Vdc46.0Vdc
Low DC Warning Return Voltage @20% ≤ load < 50%22.4Vdc44.8Vdc
Low DC Warning Return Voltage @load ≥ 50%21.2Vdc42.4Vdc
Low DC Cut-off Voltage @load < 20%21.0Vdc42.0Vdc
Low DC Cut-off Voltage @20% ≤ load < 50%20.4Vdc40.8Vdc
Low DC Cut-off Voltage @load ≥ 50%19.2Vdc38.4Vdc
High DC Recovery Voltage29Vdc58Vdc
High DC Cut-off Voltage31Vdc62Vdc
No Load Power Consumption<25W<50W
Saving Mode Power Consumption<10W<15W

7.4 Charge Mode Specifications

Utility Charging Mode:

INVERTER MODEL3.8KW 24V6.2KW 48V
Charging Current (UPS) @Nominal Input Voltage80A80A
Bulk Charging Voltage (Flooded Battery)29.258.4
Bulk Charging Voltage (AGM / Gel Battery)28.256.4
Floating Charging Voltage27Vdc54Vdc
Charging Algorithm3-Step
Charging Curve
Charging Curve Diagram
Charging Curve: Illustrates the 3-step charging process (Bulk, Absorption, Maintenance) with battery voltage and charging current over time.

Solar Charging Mode:

INVERTER MODEL3.8KW 24V6.2KW 48V
Rated Power6000W6000W
PV Charge Current110A110A
Efficiency98.0% max.
Max. PV Array Open Circuit Voltage450Vdc450Vdc
PV Array MPPT Voltage Range55-450Vdc55-450Vdc
Min battery voltage for PV charge
Standby Power Consumption2W
Battery Voltage Accuracy±0.3%
PV Voltage Accuracy±2V
Charging Algorithm3-Step

7.5 General Specifications

INVERTER MODEL3.8KW 24V6.2KW 48V
Safety CertificationCE
Operating Temperature Range0°C to 55°C
Storage temperature-15°C~60°C
Dimension (D*W*H), mm423.4*290.4*100.7(mm)423.4*290.4*115.7(mm)
Net Weight, kg6.8KG7.8KG

8. User Tips

  • Battery Usage: The inverter can work with or without batteries, depending on your setup and desired functionality. If you choose to operate with batteries, ensure they are correctly connected and charged.
  • Solar Panel Sizing: When connecting solar panels, ensure the total power of the solar panels does not exceed the maximum power of the inverter. For series connections, the voltage must be within the PV voltage range (50-450VDC).
  • Communication: The inverter supports RS232/RS485 communication. For 485 communication with lithium battery BMS, only PACE and PYLONTECH's BMS are allowed.
  • Monitoring: Utilize the optional WiFi module and the 'Sun House' app for iOS and Android to monitor your system remotely.

9. Warranty and Support

For detailed warranty information and further support, please refer to the official user manual PDF available at User manual (PDF). If errors persist after following the troubleshooting guide, contact your local dealer or service center for maintenance.