Renke RS-EC-N01-3-*-EX

Contents

Renke RS-EC-N01-3-*-EX Water Salinity, TDS, and EC Sensor Instruction Manual

Model: RS-EC-N01-3-*-EX | Brand: Renke

1. Introduction

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Renke RS-EC-N01-3-*-EX Water Salinity, TDS, and EC Sensor. This integrated sensor is designed for real-time monitoring of water quality, offering precise measurements of conductivity, salinity, and Total Dissolved Solids (TDS). It features automatic temperature compensation and a robust, waterproof design, making it suitable for various applications including aquaculture, sewage treatment, environmental protection, pharmaceuticals, food processing, and tap water monitoring.

2. Product Overview

2.1 Key Features

  • Integrated Design: Light, simple structure, and easy to use.
  • Wide Measurement Range: Conductivity up to 20000 μS/cm.
  • Automatic Temperature Compensation: Compensates current temperature conductivity to a specified temperature (default 25℃).
  • Waterproof Protection: IP68 protection level ensures durability in submerged environments.
  • Multi-Parameter Measurement: Provides conductivity, salinity, and TDS readings.
  • RS485 Communication: Standard ModBus-RTU protocol for reliable data transmission.
  • Configurable Settings: ModBus communication address and baud rate can be adjusted.
  • Wide Voltage Power Supply: Operates on DC 10~30V.
  • High Sealing and Anti-interference: Designed for stable and accurate measurements in challenging conditions.
Integrated water EC sensor with high sealing and anti-interference features
Figure 1: Integrated water EC sensor highlighting high sealing and anti-interference capabilities.
Diagram illustrating the waterproof IP68 design and integrated structure of the sensor
Figure 2: Sensor design emphasizing IP68 waterproof rating and integrated, easy-to-use structure.

2.2 Components

The Renke RS-EC-N01-3-*-EX sensor consists of an integrated probe and a cable for power and communication. No additional external components are typically required for basic operation.

Detailed view of the Renke EC sensor probe and cable
Figure 3: Detailed view of the Renke EC sensor.

3. Specifications

Parameter Value
Model Number RS-EC-N01-3-*-EX
Power Supply DC 10~30V
Power Consumption 0.4W
Communication Interface RS485; standard ModBus-RTU protocol
Communication Baud Rate Default 4800 (configurable: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200)
Measurement Range (K=1) 1~2000 μS/cm
Measurement Range (K=10) 10~20000 μS/cm
Resolution (K=1) 0.1 μS/cm
Resolution (K=10) 1 μS/cm
Measurement Error ±1%FS
Temperature Range -5~+80 ℃
Temperature Resolution 0.1 ℃
Temperature Error ±0.5 ℃
Temperature Compensation Range -5~+80 ℃ (default compensation temperature 25 ℃)
Temperature Compensation Coefficient Default 0.02
Salinity Range (K=1) 0~1000 ppm
Salinity Range (K=10) 0~11476 ppm
TDS Range (K=1) 0~1100 ppm
TDS Range (K=10) 0~13400 ppm
Transmitter Temperature Resistance -20~+80 ℃
Protection Level IP68
Pressure Resistance 0.6 MPa
Electrode Wire Length 5m (other lengths customizable)
Material Plastic
Certification CE
Dimensional drawing of the Renke EC sensor, showing a total length of 216mm and body length of 212mm
Figure 4: Sensor dimensions (216mm total length).
Table showing EC sensor applications: K=1 for freshwater aquaculture and tap water monitoring, K=10 for industrial water and sewage detection
Figure 5: EC sensor application guide based on electrode constant (K value).
Certifications for the Renke sensor, including CE and RoHS
Figure 6: Product certifications (CE, RoHS).

4. Setup and Installation

4.1 Electrical Connection

The sensor requires a DC 10~30V power supply. Connect the power lines according to the wiring diagram provided with your specific unit. Ensure correct polarity to prevent damage.

4.2 Communication Connection

The sensor communicates via RS485 using the standard ModBus-RTU protocol. Connect the RS485 A and B lines to your ModBus master device. The default baud rate is 4800, but it can be configured to other values (1200, 2400, 9600, 19200, 38400, 57600, 115200) as needed for your system.

4.3 Physical Installation

  1. Select Electrode Constant: Determine the appropriate electrode constant (K=1 or K=10) based on your application's expected conductivity range. K=1 is suitable for freshwater aquaculture and tap water, while K=10 is for industrial water and sewage.
  2. Mounting: Submerge the sensor probe completely into the water or solution to be measured. Ensure the sensor is securely mounted to prevent movement or damage.
  3. Cable Management: Route the sensor cable to avoid kinks, sharp bends, or exposure to excessive mechanical stress.

5. Operation

Once properly installed and powered, the sensor will begin measuring water conductivity, salinity, and TDS. Data can be read from the sensor using a ModBus master device (e.g., PLC, industrial computer, or dedicated ModBus data logger).

5.1 Data Acquisition

  • Use ModBus-RTU commands to query the sensor for its current readings. Refer to the ModBus communication protocol documentation for specific register addresses and data formats.
  • The sensor automatically applies temperature compensation to the conductivity readings, adjusting them to a reference temperature of 25℃ by default.
  • Salinity and TDS values are calculated internally by the sensor based on the conductivity and temperature readings.

5.2 Configuration

The ModBus communication address and baud rate can be modified via ModBus commands if necessary. Consult the detailed communication protocol for instructions on how to change these parameters.

6. Maintenance

Regular maintenance ensures the longevity and accuracy of your Renke EC sensor.

6.1 Cleaning the Electrode

  • Periodically inspect the electrode tip for any fouling, algae growth, or mineral deposits.
  • Gently clean the electrode using a soft brush or cloth and distilled water. For stubborn deposits, a mild detergent or appropriate cleaning solution may be used, followed by thorough rinsing with distilled water.
  • Avoid scratching or damaging the electrode surface during cleaning.

6.2 Calibration

While the sensor is designed for stability, periodic calibration with known conductivity standards is recommended to maintain optimal accuracy, especially in critical applications or after prolonged use.

6.3 Storage

When not in use, store the sensor in a clean, dry environment, preferably with the electrode tip protected. Avoid extreme temperatures or direct sunlight.

Note: Water quality sensors are consumables. Proper maintenance extends their lifespan, but eventual replacement will be necessary.

7. Troubleshooting

Problem Possible Cause Solution
No readings or incorrect data via RS485
  • Incorrect power supply (voltage or polarity)
  • Loose or incorrect RS485 wiring
  • Mismatched ModBus communication parameters (address, baud rate)
  • Sensor fault
  • Verify power supply is DC 10~30V and correctly connected.
  • Check RS485 A/B wiring for continuity and correct connection.
  • Ensure ModBus address and baud rate on the master device match the sensor's configuration.
  • If all connections and settings are correct, contact support.
Inaccurate or drifting readings
  • Fouling or deposits on the electrode
  • Sensor aging or damage
  • Interference from external electrical sources
  • Clean the electrode as described in Section 6.1.
  • Perform calibration using standard solutions.
  • Ensure proper grounding and shielding of cables to minimize interference.

8. User Tips

  • Optimal Placement: Position the sensor in an area of the water body that provides a representative sample and avoids stagnant zones or areas with excessive turbulence.
  • Regular Cleaning: Even if readings appear stable, periodic visual inspection and cleaning of the electrode can prevent buildup that might eventually affect accuracy.
  • Documentation: Keep a record of installation details, calibration dates, and any configuration changes for easier troubleshooting and maintenance.

9. Warranty and Support

9.1 Warranty Information

The Renke RS-EC-N01-3-*-EX sensor comes with a 1-year quality guarantee from the date of purchase. This warranty covers defects in materials and workmanship under normal use. Please note that water quality sensors are considered consumables, and the warranty does not cover damage due to improper use, lack of maintenance, or natural wear and tear.

9.2 Technical Support

For technical assistance, troubleshooting, or inquiries regarding your sensor, please contact Renke customer support:

  • Email: sales_phoebe@126.com
  • WhatsApp: +852 65705287

When contacting support, please have your product model number (RS-EC-N01-3-*-EX) and a detailed description of the issue ready.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.