1. Introduction
This manual provides comprehensive instructions for the assembly, installation, operation, and troubleshooting of your SUMRY MPS-V MAX SERIES 10.2KW 48VDC Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference. This inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. Its user-friendly LCD display allows for configurable settings such as battery charging current, AC/solar charger priority, and acceptable input voltage for various applications.
1.1. Key Features
- Pure sine wave inverter.
- Configurable input voltage range for home appliances and personal computers via LCD setting.
- Configurable battery charging current based on applications via LCD setting.
- Configurable AC/Solar Charger priority via LCD setting.
- Compatible with mains voltage or generator power.
- Auto restart while AC is recovering.
- Overload, over temperature, and short circuit protection.
- Smart battery charger design for optimized battery performance.
- Cold start function.

Figure 1: Key Features of the SUMRY Hybrid Solar Inverter.
2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION: To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION: Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedures when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- One piece of 150A fuse is provided as over-current protection for the battery supply.
- GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

Figure 2: Comprehensive Protection Features.
3. Product Overview
The SUMRY MPS-V MAX SERIES 10.2KW 48VDC Hybrid Solar Inverter is designed for robust performance in solar power systems. Below is a visual overview of the unit and its components.

Figure 3: Product Overview with labeled components.
3.1. Basic System Architecture
The inverter/charger can be integrated into a basic hybrid power system as shown below. This system typically includes solar power (PV modules), external battery packs, and can connect to a generator or utility grid to power various home appliances.

Figure 4: Hybrid Power System Architecture.
3.2. Dimensions
The dimensions of the inverter are D*W*H 537*390*130 (mm).

Figure 5: Inverter Dimensions and Dual Output.
3.3. Appliance Compatibility
This inverter is capable of powering a wide range of appliances in both home and office environments, including various motor-type appliances.

Figure 6: Appliance Compatibility.
3.4. Usage Scenarios
The inverter provides reliable power for various scenarios, ensuring your home, office, and RV equipment remain operational even during power outages.

Figure 7: Inverter Usage Scenarios.
4. Installation
4.1. Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- User manual x 1
- Ring terminal x 1
- MC4 terminal head x 2
4.2. Preparation
Before connecting all lines, remove the screws under the machine and remove the bottom cover plate.
4.3. Mounting the Unit
Consider the following points before selecting where to install:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level in order to allow the LCD display to be read at all times.
- Proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Install the unit by screwing two screws. It's recommended to use M4 or M5 screws.
4.4. Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in below table as required fuse or breaker size.
| Model | Wire Size | Cable (mm²) | Torque Value (max) |
|---|---|---|---|
| 8.2KW/10.2KW | 1 x 2AWG | 25 | 2 Nm |
Follow these steps to implement battery connection:
- Remove insulation sleeve 18 mm for positive and negative conductors.
- Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
- Connect all battery packs as shown in the diagram below.
- Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with a torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charge is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.

Figure 8: Battery Connection Diagram.
WARNING: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
Video 1: Unboxing and Connection Demonstration.
4.5. AC Input/Output Connection
CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended specification of AC breaker is 63A for 8.2KW/10.2KW.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
| Model | Gauge | Cable (mm²) | Torque Value |
|---|---|---|---|
| 8.2KW/10.2KW | 10 AWG | 6 | 1.2 Nm |
Follow these steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor (⍃) first.
- Ground (yellow-green)
- L → LINE (brown or black)
- N → Neutral (blue)

Figure 9: AC Input/Output Wiring Diagram.
WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
- L → LINE (brown or black)
- N → Neutral (blue)
- Make sure the wires are securely connected.
4.6. PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
| Model | Wire Size | Cable (mm²) | Torque Value (max) |
|---|---|---|---|
| 8.2KW/10.2KW | 1 x 10AWG | 6 | 1.2 Nm |
PV Module Selection
When selecting proper PV modules, please be sure to consider below parameters:
- Open circuit Voltage (Voc) of PV modules not exceeding max. PV array open circuit voltage of inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
| INVERTER MODEL | 8.2KW/10.2KW |
|---|---|
| Max. PV Array Open Circuit Voltage | 500Vdc |
| PV Array MPPT Voltage Range | 90Vdc~450Vdc |
Take 250Wp PV module as an example. After considering above two parameters, the recommended module configurations are listed as below table:
| Solar Panel Spec. (reference) | SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs) | Q'ty of panels | Total input power |
|---|---|---|---|
| 250Wp, Vmp: 30.1Vdc, Imp: 8.3A, Voc: 37.7Vdc, Isc: 8.4A, Cells: 60 | 6 pcs in serial | 6 pcs | 1500W |
| 8 pcs in serial | 8 pcs | 2000W | |
| 12 pcs in serial | 12 pcs | 3000W | |
| 13 pcs in serial | 13 pcs | 3250W | |
| 12 pieces in serial and 3 sets in parallel | 36 pcs | 8200W | |
| 10 pieces in serial and 4 sets in parallel | 40 pcs | 10200W |
PV Module Wire Connection
Step 1: Check the input voltage of PV array modules. The acceptable input voltage of the inverter is 90VDC-500VDC. Please make sure that the maximum current load of each PV input connector is 18A.
CAUTION: Exceeding the maximum input voltage can destroy the unit!! Check the system before wire connection.
Step 2: Disconnect the DC circuit breaker.
Step 3: Assemble provided PV connectors with PV modules by following the steps below:
Components for PV connectors and Tools:
- Female connector housing
- Female terminal
- Male connector housing
- Male terminal
- Crimping tool and spanner
Cable preparation and connector assembly process:
Strip one cable 8 mm on both end sides and be careful NOT to nick conductors.
Insert striped cable into female terminal and crimp female terminal. Insert assembled cable into female connector housing. Insert striped cable into male terminal and crimp male terminal. Insert assembled cable into male connector housing.
Then, use spanner to screw pressure dome tightly to female connector and male connector. Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.

Figure 10: PV Connector Assembly and Wiring.
4.7. Final Assembly
After connecting all wirings, please put bottom cover back by screwing two screws.
4.8. Communication Connection
Wi-Fi cloud communication (option):
Please use supplied communication cable to connect to inverter and Wi-Fi module. Download APP and installed from APP store, and Refer to "Wi-Fi Plug Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
GPRS cloud communication (option):
Please use supplied communication cable to connect to inverter and GPRS module, and then applied external power to GPRS module. Download APP and installed from APP store, and Refer to "GPRS RTU Quick Installation Guideline" to set up network and registering. The inverter status would be shown by mobile phone APP or webpage of computer.
Battery communication:
The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baud rate: 9600).
Lithium battery and inverter connection:
Use power cables, communication cables for lithium batteries, and inverters to connect.
Note: Lithium battery and inverter positive and negative positions, check the correct installation; The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery; Before connecting, make sure that the lithium battery and inverter are turned off. (It is recommended to install a circuit breaker for the power cables of the lithium battery and the inverter battery interface. Otherwise, a spark may occur.)

Figure 11: Monitoring and Control via Smart App (Optional).
The lithium battery communication cable interface is shown in the figure below:
| CONNECTION METHOD | A-01 | A-02 |
|---|---|---|
| 1 | 7 | |
| 2 | 8 | |
| EMPTY PIN IS NOT CONNECTED |
In order to communicate with the lithium battery BMS, you should press the “ENTER” button for a long time, and set the battery type as “LIB-485” in program 05. Then select the matching battery protocol in Program 43.
5. Operation
5.1. Power ON/OFF
Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.
5.2. Operation and Display Panel
The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

Figure 12: LCD Display, Indicators, and Function Keys.
| LED Indicator | Messages |
|---|---|
| INV/AC (Green Solid On) | Output is powered by utility in Line mode. |
| INV/AC (Green Flashing) | Output is powered by battery or PV in battery mode. |
| CHG (Green Solid On) | Battery is fully charged. |
| CHG (Green Flashing) | Battery is charging. |
| FAULT (Red Solid On) | Fault occurs in the inverter. |
| FAULT (Red Flashing) | Warning condition occurs in the inverter. |
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
5.3. LCD Display Icons
The LCD display provides various icons to indicate the inverter's status and information.
| Icon | Function description |
|---|---|
| ⍃ | Indicates the AC input. |
| ☀ | Indicates the PV input. |
| 8.8.8 KW V Hz A | Indicate input voltage, input frequency, PV voltage, charger current (if PV in charging for 10.2KW models), charger power, battery voltage. |
| (8.8.8) | Indicates the setting programs. |
| ⚠ | Indicates the warning and fault codes. |
| 8.8.8 KW VA % | Indicate output voltage, output frequency, load percent, load in VA, load in Watt and discharging current. |
| ⚛ | Indicates overload. |
| ⚡ | Indicates unit connects to the mains. |
| ☀ | Indicates unit connects to the PV panel. |
| AC BYPASS | Indicates load is supplied by utility power. |
| ⚡ | Indicates the utility charger circuit is working. |
| ⚡ | Indicates the DC/AC inverter circuit is working. |
| 🔇 | Indicates unit alarm is disabled. |
5.4. LCD Setting
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the "UP" or "DOWN" buttons to select setting programs, then press "ENTER" to confirm or "ESC" to exit.
Key configurable settings include:
- Program 00: Exit setting mode (00 GOE for one-button restore, 00 GOH for exit).
- Program 01: Output source priority (Utility first, Solar first, SBU priority, MKS priority).
- Program 02: Maximum charging current (Configurable from 10A to 160A).
- Program 03: AC input voltage range (Appliances: 90-280VAC, UPS: 170-280VAC).
- Program 05: Battery type (AGM, Flooded, LIB, User-Defined, LIB-485).
- Program 06: Auto restart when overload occurs (Restart disable/enable).
- Program 07: Auto restart when over temperature occurs (Restart disable/enable).
- Program 09: Output frequency (50Hz/60Hz).
- Program 10: Output voltage (220V/230V/240V).
- Program 11: Maximum utility charging current (Configurable).
- Program 12: Setting voltage point back to utility source (Configurable from 42V to 58V).
- Program 13: Setting voltage point back to battery mode (Configurable from 48V to 58V).
- Program 16: Charger source priority (Solar first, Solar and Utility, Only Solar).
- Program 18: Alarm control (Alarm on/off).
- Program 19: Auto return to default display screen (Return to default/Stay at latest screen).
- Program 20: Backlight control (Backlight on/off).
- Program 22: Beeps while primary source is interrupted (Alarm on/off).
- Program 23: Overload bypass (Bypass disable/enable).
- Program 25: Record fault code (Record enable/disable).
- Program 26: Bulk charging voltage (C.V voltage) (Configurable from 48.0V to 61.0V).
- Program 27: Floating charging voltage (Configurable from 48.0V to 61.0V).
- Program 29: Low DC cut-off voltage (Configurable from 48.0V to 61.0V).
- Program 30: Battery equalization (Enable/Disable).
- Program 31: Battery equalization voltage (Configurable from 40.0V to 61.0V).
- Program 33: Battery equalized time (Configurable from 5min to 900min).
- Program 34: Battery equalized timeout (Configurable from 5min to 900min).
- Program 35: Equalization interval (Configurable from 1 to 90 days).
- Program 36: Equalization activated immediately (Enable/Disable).
- Program 37: GRID-tie operation (Off grid, Hybrid).
- Program 38: GRID-tie current (Configurable).
- Program 39: Led pattern light (Led pattern off/on).
- Program 41: Dual output (L2F/L20).
- Program 42: Enter the dual output functional voltage point (Configurable from 40.0V to 52.0V).
- Program 43: Lithium battery protocol (PYLON/PACE).
- Program 44: Delayed grid access (Disable/Enable).
- Program 45: Maximum Second Load (20%~70%).
5.5. Display Setting
The LCD display information can be switched in turns by pressing the “UP” or “DOWN" key. The selectable information includes: input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, and main CPU Version.
5.6. Operating Mode Description
The inverter supports various operating modes to suit different power requirements.
Standby Mode / Power Saving Mode
In standby mode, the inverter is not turned on yet but can charge the battery without AC output. In power saving mode, if enabled, the inverter's output will be off when the connected load is very low or not detected.
Line Mode
In Line Mode, the unit provides output power from the mains and charges the battery. This mode can also involve PV and mains charging, or mains charging only.
Grid-Tie Operation
When operating in Grid-Tie mode, the display will flash every 3 seconds.
Battery Mode
In Battery Mode, the unit provides output power from the battery and can also combine with solar power to supply loads.
5.7. Battery Equalization Description
Battery equalization reverses the buildup of negative chemical effects like stratification and helps remove sulfate crystals, which can reduce battery capacity. It is recommended to equalize the battery periodically.
How to Apply Equalization Function
Enable battery equalization in monitoring LCD setting program 30. Then, apply this function by either:
- Setting equalization interval in program 35.
- Activating equalization immediately in program 36.
When to Equalize
In the float stage, when the setting equalization interval is reached, or equalization is activated immediately, the controller will enter the Equalize stage.
Equalize Charging Time and Timeout
In the Equalize stage, the controller charges the battery until it reaches the battery equalization voltage. Constant-voltage regulation maintains this voltage until the set equalized time is reached. If the battery voltage is still lower than the equalization voltage after the timeout, the charge controller will extend the equalized time. If the voltage remains low after the extended time, the controller stops equalization and returns to float stage.
5.8. Mains and Lithium Battery Activation Function
- After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
- If the inverter is in lithium battery mode (item 05 is LIB or LIB-485), and the battery is not connected after mains connection, the mains activation function is automatically enabled.
6. Clearance and Maintenance for Anti-Dust Kit
6.1. Overview
Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust internal temperature. This kit also keeps dust from your inverter and increases product reliability in harsh environments.
6.2. Clearance and Maintenance
Step 1: Loosen the screw in a counterclockwise direction on the top of the inverter.

Figure 13: Loosening the Anti-Dust Kit Screw.
Step 2: Then, the dustproof case can be removed, and the air filter foam taken out as shown below.

Figure 14: Removing Dustproof Case and Air Filter Foam.
Step 3: Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back to the inverter.
NOTICE: The anti-dust kit should be cleaned from dust every one month.
7. Troubleshooting
Refer to the table below for common issues and their solutions. If problems persist, contact qualified service personnel.
| Problem | LCD/LED/Buzzer | Explanation / Possible cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Internal fuse tripped. | 1. Contact repair center for replacing the fuse. 2. Re-charge battery. 3. Replace battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance) |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. | |
| Output short circuited. | Check if wiring is connected well and remove abnormal load. | ||
| Fault code 05 | Temperature of internal converter component is over 120°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | |
| Fault code 02 | Internal temperature of inverter component is over 100°C. | Return to repair center. | |
| Buzzer beeps continuously and red LED is on. | Fault code 03 | Battery is over-charged. | Check if spec and quantity of batteries are meet requirements. |
| Fault code 01 | The battery voltage is too high. | Replace the fan. | |
| Fault code 06/58 | Fan fault | 1. Reduce the connected load. 2. Return to repair center. | |
| Fault code 08/09/53/57 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | Return to repair center. | |
| Fault code 51 | Internal components failed. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 52 | Over current or surge. | ||
| Fault code 55 | Bus voltage is too low. | ||
| Output voltage is unbalanced. |
8. Specifications
Detailed technical specifications for the SUMRY MPS-V MAX SERIES 10.2KW 48VDC Hybrid Solar Inverter are provided in the tables below.
8.1. Line Mode Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 230Vac | |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
| High Loss Voltage | 280Vac±7V | |
| High Loss Return Voltage | 270Vac±7V | |
| Max AC Input Voltage | 300Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) | |
| Low Loss Frequency | 40±1Hz | |
| Low Loss Return Frequency | 42±1Hz | |
| High Loss Frequency | 65±1Hz | |
| High Loss Return Frequency | 63±1Hz | |
| Output Short Circuit Protection | Circuit Breaker | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
8.2. Inverter Mode Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Rated Output Power | 8.2KW | 10.2KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 50Hz | |
| Peak Efficiency | 93% | |
| Overload Protection | 3s@≥150% load; 5s@101%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 48Vdc | |
| Cold Start Voltage | 46.0Vdc | |
| Low DC Warning Voltage @load < 50% | 44.0Vdc | |
| Low DC Warning Voltage @load ≥ 50% | 42.0Vdc | |
| Low DC Warning Return Voltage @load < 50% | 45.0Vdc | |
| Low DC Warning Return Voltage @load ≥ 50% | 44.0Vdc | |
| Low DC Cut-off Voltage @load < 50% | 41.0Vdc | |
| Low DC Cut-off Voltage @load ≥ 50% | 40.0Vdc | |
| High DC Recovery Voltage | 62Vdc | |
| High DC Cut-off Voltage | 63Vdc | |
| No Load Power Consumption | 70W | 75W |
8.3. Two Load Output Power
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Full Load | 8200W | 10200W |
| Maximum Main Load | 8200W | 10200W |
| Second Load Range | 1640W~5740W | 2040W~7140W |
| Main Load Cut Off Voltage | 52VDC | |
| Main Load Return Voltage | 54VDC | |
8.4. Charge Mode Specifications
| Utility Charging Mode | 8.2KW | 10.2KW |
|---|---|---|
| Charging Algorithm | 3-Step | |
| AC Charging Current (Max) | 140Amp | 140Amp |
| Bulk Charging - Flooded Battery | 58.4 | |
| Bulk Charging - AGM / Gel Battery | 56.4 | |
| Floating Charging Voltage | 54Vdc | |
8.5. MPPT Solar Charging Mode
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Max. PV Array Power | PV1 Channel: 5400W | PV1 Channel: 5400W |
| PV2 Channel: 5400W | PV2 Channel: 5400W | |
| Imax.PV | PV1 Channel:18A | PV1 Channel:18A |
| PV2 Channel:18A | PV2 Channel:18A | |
| Nominal PV Voltage | 360Vdc | |
| PV Array MPPT Voltage Range | 90Vdc~450Vdc | |
| Max. PV Array Open Circuit Voltage | 500Vdc | |
| Max Charging Current (AC charger plus solar charger) | 160Amp | |
8.6. Grid-Tie Operation
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Nominal Output Voltage | 220/230/240VAC | |
| Feed in Grid Voltage Range | 190~253VAC | |
| Feed in Grid Frequency Range | 50~1Hz/60~1Hz | |
| Nominal Output Current | 35.8A | 44.3A |
| Power Factor Range | >0.99 | |
| Maximum Conversion Efficiency | 98% | |
8.7. General Specifications
| INVERTER MODEL | 8.2KW | 10.2KW |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | -10°C to 50°C | |
| Storage Temperature | -15°C to 60°C | |
| Humidity | 5% to 95% Relative Humidity (non-condensing) | |
| Dimension (D*W*H), mm | 550*390*130mm | |
| Net Weight, kg | 14.5 | 14.7 |
8.8. Approximate Back-up Time Table
The table below provides approximate backup times for different loads and battery capacities. Note that actual backup time depends on battery quality, age, and type.
| Model | Load (W) | Backup Time @ 48Vdc 100Ah (min) | Backup Time @ 48Vdc 200Ah (min) |
|---|---|---|---|
| 8.2KW/10.2KW | 500 | 613 | 1288 |
| 1000 | 268 | 613 | |
| 1500 | 158 | 402 | |
| 2000 | 111 | 271 | |
| 2500 | 90 | 215 | |
| 3200 | 76 | 182 | |
| 3500 | 65 | 141 | |
| 4000 | 50 | 112 | |
| 4500 | 44 | 100 | |
| 5000 | 40 | 90 | |
| 6200 | 36 | 80 | |
| 7200 | 32 | 70 | |
| 8200 | 28 | 60 | |
| 9200 | 24 | 50 | |
| 10200 | 20 | 40 |
9. User Tips
- This inverter supports dual output voltages, typically 110V and 220V, making it versatile for various household and office appliances.
- When connecting to a two-phase system, ensure proper wiring for phase, phase, and neutral connections as per local electrical codes.
- While the inverter can operate in certain modes without a battery, for full hybrid functionality and backup power, a compatible battery system is required.
10. Support and Further Information
For detailed diagrams, advanced settings, and comprehensive troubleshooting, please refer to the complete user manual PDF available at: SUMRY 8.2KW/10.2KW Hybrid Solar Inverter User Manual (PDF).
If you encounter issues not covered in this manual or require further assistance, please contact your local dealer or the SUMRY Global Store customer support.