TONGOU TOSAR1-XWTNA-1N+BD6

TONGOU Type A RCBO Tuya Smart Auto Recloser Circuit Breaker

Model: TOSAR1-XWTNA-1N+BD6

1. Introduction and Safety Information

The TONGOU Type A RCBO (Residual Current Circuit Breaker with Overcurrent Protection) with Tuya Smart Auto Recloser functionality is designed to provide earth leakage and overload protection for electrical circuits. It integrates smart features for remote control, real-time monitoring, and automatic reclosing after faults, enhancing electrical safety and convenience.

Important Safety Instructions:

  • Installation and maintenance should only be performed by qualified electricians.
  • Always disconnect power before installing or servicing the device.
  • Ensure proper wiring according to local electrical codes and the provided diagrams.
  • Do not operate the device if it appears damaged.
  • This device is designed for indoor use in dry environments unless otherwise specified.
TONGOU WiFi RCBO Auto Recloser with smartphone app showing real-time voltage
Figure 1: TONGOU WiFi RCBO Auto Recloser with smartphone app display.

2. Product Features

This smart RCBO offers continuous protection and advanced control for your electronic devices:

  • Dual Protection: Provides both earth leakage (Type A) and overcurrent protection.
  • Smart Connectivity: Works with Tuya and Smart Life applications for remote control and monitoring via WiFi.
  • Real-time Voltage Monitoring: Digital display and app integration show live voltage (100-280V) and historical trend data (hourly, daily, monthly, yearly).
  • Voltage Protection: Automatic shutdown if voltage exceeds 250V and alarms if it drops below 180V.
  • Auto Reclosing: Automatically attempts to reclose the circuit after a fault, with a configurable reclosing interval (30s) and cycles (3).
  • Smart Scheduling: Supports sunrise/sunset automation and custom timing cycles (15 minutes to 24 hours).
  • Memory Function: Retains settings even after power outages.
  • Multiple Safety Protections: Certified compliance (CE, CCC), dual-color status indicator (Red/Green), reinforced buckle mechanism, flame-retardant protection, and touch protection design.
  • Flexible Wiring: Compatible with terminal, pin, and DPN busbar connections (top/bottom).
Product Function settings including overvoltage/undervoltage protection and timing functions
Figure 2: Overview of product function settings and timing features.
Diagram showing multiple safety protections: Certified Compliance, Dual-Color Status Indicator, Reinforced Buckle Mechanism, Flame-Retardant Protection, Touch Protection Design
Figure 3: Multiple Safety Protections integrated into the device.

3. Specifications

AttributeValue
Model NumberTOSAR1-XWTNA-1N+BD6
TypeResidual Current (RCBO)
Poles Number1P+N
Rated Voltage220V/230V/240V
Rated Current16A, 25A, 32A, 40A
Rated Operating Current (In)10mA, 30mA
Breaking Capacity6kA
Tripping CharacteristicsType A
CurveB, C
Rated Impulse Withstand Voltage (Uimp)4 kV
Static Power1 VA
Rated Frequency50/60 Hz
Operating Temperature-25°C to +60°C (-13°F to 140°F)
Reclosing Interval30s → 30s → 30s
Reclosing Cycles3
Electrical Life10,000 operations
Mounting35mm DIN Rail
CertificationCE, CCC
Is Smart DeviceYes

Dimensions:

Product dimensions showing height 105mm, width 36mm, depth 80mm, and terminal height 45mm, terminal depth 35mm
Figure 4: Product dimensions (Height: 105mm, Width: 36mm, Depth: 80mm).

4. Setup and Installation

This device is designed for 35mm DIN rail mounting. Ensure all connections are secure and comply with local electrical standards. Refer to the detailed wiring diagrams below for proper installation.

4.1 Wiring Diagrams

Basic wiring diagram for 1P+N RCBO, showing Live (L) and Neutral (N) connections
Figure 5: Basic 1P+N RCBO Wiring Diagram. Connect the incoming Live (L) and Neutral (N) to the top terminals and outgoing Live (L) and Neutral (N) to the bottom terminals.
Wiring diagram for 1P+N RCBO with external control terminals
Figure 6: 1P+N RCBO Wiring Diagram with External Control. This diagram illustrates how to connect external control signals to the device's dedicated terminals.
Wiring diagram for 1P+N RCBO with external control and manual switch integration
Figure 7: 1P+N RCBO Wiring Diagram with External Control and Manual Switch. Shows integration of a manual switch for additional control.
Detailed connection points for 1P+N RCBO, highlighting various terminal functions
Figure 8: Detailed Connection Points for 1P+N RCBO. This diagram provides a closer look at the specific terminals for Live, Neutral, and control signals.

4.2 App Integration

  1. Download the Tuya Smart or Smart Life app from your smartphone's app store.
  2. Register or log in to your account.
  3. Add the device by following the in-app instructions. Ensure the RCBO is in Wi-Fi mode (slide the switch to the right).
  4. Once connected, you can access all smart features, including remote ON/OFF, voltage monitoring, and scheduling.

5. Operating Instructions

5.1 Manual Operation

The RCBO features a physical switch for manual control:

  • ON: Turns the circuit breaker on.
  • OFF: Turns the circuit breaker off.
  • AUTO: Enables automatic reclosing and smart functions via the app.
  • LOCK: Locks the switch in its current position, preventing accidental changes.
Auto-reset smart switch with Over-voltage/Under-voltage Reclosed settings and AUTO/ON/OFF/LOCK switch diagram
Figure 9: Auto-reset smart switch with manual control options.

5.2 Smart App Operation

Once connected to the Tuya Smart or Smart Life app:

  • Remote ON/OFF: Control the circuit breaker from anywhere.
  • Real-time Voltage Monitoring: View the current voltage (e.g., 224.6V) and track power running time, device operation duration, power failure number, and switch times.
  • Voltage Statistics Table: Access hourly, daily, monthly, and annual voltage trend data.
  • Auto Reclose Function: Enable or disable the automatic reclosing feature in the app settings.
  • Timing Function: Set schedules for automatic operation, including specific times, sunrise/sunset, or custom cycle timings.
  • Overvoltage/Undervoltage Protection: Configure voltage thresholds for automatic reclosing (100-280V).
Smartphone app displaying real-time voltage monitoring at 224.6V
Figure 10: Real-time voltage monitoring via the smartphone app.
Voltage trend data graph showing hourly, daily, monthly, and annual views
Figure 11: Voltage trend data graph for historical analysis.

6. Maintenance

The TONGOU RCBO is designed for minimal maintenance. However, regular checks are recommended:

  • Visual Inspection: Periodically check the device for any signs of physical damage, discoloration, or loose connections.
  • Functionality Test: Test the manual ON/OFF function and verify app control periodically.
  • Firmware Updates: Ensure the device firmware is up-to-date through the Tuya Smart or Smart Life app for optimal performance and security.
  • Cleaning: Keep the device free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquids or abrasive cleaners.

7. Troubleshooting

If you encounter issues with your TONGOU RCBO, refer to the following troubleshooting steps:

  • Failure to Reclose Automatically:
    1. Ensure the device is in Wi-Fi mode (slide the physical switch to the right). The auto-reclose function is only available in Wi-Fi mode.
    2. Verify that the "Auto Reclose" function is enabled within the Tuya Smart or Smart Life app settings.
  • Product Cannot Be Manually Tripped (Handle Stuck):
    1. Attempt a remote open/close operation via the Tuya Smart or Smart Life app. This often resolves the issue.
  • Product Fails to Reclose Automatically, Display Shows Error Codes C01, H01, or H02:
    1. These error codes indicate specific faults. First, go to "Setting → Advanced → Fault Reset" in the app to clear any fault codes.
    2. Then, power cycle the device (turn the power off and on again). This should resolve the fault.
    3. If the issue persists, consult the full user manual PDF for detailed explanations of error codes and further troubleshooting steps.
  • No App Connectivity:
    1. Ensure your Wi-Fi network is active and the signal strength is adequate where the device is installed.
    2. Check that the device is in pairing mode or Wi-Fi mode.
    3. Restart your router and the RCBO, then attempt to reconnect via the app.

8. User Tips

  • Storm Protection: During severe weather, configure the app to send alerts if voltage exceeds 250V and enable remote power cut-off to protect sensitive electronics.
  • Vacation Automation: Use the smart scheduling feature to set custom cycles for appliances like aquarium pumps (e.g., 15 minutes every 2 hours) while you are away.
  • Appliance Protection: Leverage the voltage monitoring and protection features to safeguard appliances like refrigerators from damage due to voltage fluctuations. The historical voltage graph can provide evidence for insurance claims if needed.
  • Power Stability Monitoring: Regularly review the daily, monthly, and yearly voltage graphs to identify recurring power issues (e.g., frequent voltage drops) and gather data to request improvements from your power provider.
  • Post-Outage Recovery: After a power outage (e.g., due to a typhoon), the auto-reclose function ensures that connected lights and appliances reboot automatically once power stabilizes, minimizing disruption.

9. Warranty and Support

For detailed warranty information, technical support, and a comprehensive guide to all features and troubleshooting, please refer to the official user manual PDF. The PDF manual contains in-depth diagrams and explanations not fully covered in this summary.

You can access the user manual PDF here: TONGOU RCBO User Manual (PDF)

For further assistance, please contact TONGOU customer support.

Related Documents - TOSAR1-XWTNA-1N+BD6

Preview TONGOU TOSAR-1 Manual Instruction and Technical Specifications
User manual and technical specifications for the TONGOU TOSAR-1 automatic recloser, detailing its features, dimensions, wiring diagrams, and electrical characteristics for circuit protection.
Preview TONGOU Mini WiFi Smart Circuit Breaker with Energy Monitoring - User Manual & Technical Specifications
Detailed user manual and technical specifications for the TONGOU Mini WiFi Smart Circuit Breaker (1P, 1-63A adjustable). Covers installation, electrical parameters, Wi-Fi connectivity, app control via Tuya/Smart Life, and safety features for smart home automation.
Preview Tongou TOQCB1-TJ-100 WiFi Metering Circuit Breaker: Operating Manual & Features
Detailed operating manual for the Tongou TOQCB1-TJ-100 WiFi Metering Circuit Breaker. Covers main functions, parameter settings, live view, LED indicators, configuration steps, and remote protection mode for the Smart Life APP.
Preview Tongou TOQCB2 Smart Metering Circuit Breaker User Manual & Specifications
Comprehensive user manual and technical specifications for the Tongou TOQCB2 Smart Metering Circuit Breaker, covering installation, functions, features, and safety guidelines.
Preview Tongou Circuit Breakers: Installation Guide & EU Compliance
Official assembly instructions and EU Declaration of Conformity for Tongou circuit breakers (TORD4B-63, TOMD6-63(DC), TOND6-40, etc.). Details on installation, specifications, and safety for qualified electricians.
Preview Tongou DIN Rail Smart Switch Operating Manual
Comprehensive operating manual for Tongou DIN Rail Smart Switches (TO-Q-SY1, TO-Q-SY2 series), covering product appearance, specifications, LED indicators, configuration steps, wiring diagrams, parameter settings, event logs, time settings, and safety guidelines.