1. Introduction
The Megarevo MPS series hybrid inverters are designed for commercial use, offering an integrated solution for solar energy management. These units combine PV controllers, energy storage converters, and automatic on/off-grid switching capabilities into a single system. This design significantly enhances deployment efficiency and reduces installation costs. The MPS series allows for flexible PV capacity configuration, improving microgrid system availability, particularly in remote areas and islands with weaker power infrastructure. The inverter features strong load adaptability and comprehensive protection functions to ensure secure and stable power supply.

2. Setup and Installation
Installation of the Megarevo MPS Series Hybrid Solar Inverter should only be performed by qualified and certified professionals. Proper installation is crucial for safety and optimal performance. The integrated design simplifies the overall system architecture, but adherence to local electrical codes and manufacturer guidelines is paramount.
2.1 Key Considerations
- Location: Install the inverter in a well-ventilated area, protected from direct sunlight, rain, and excessive dust. Ensure the ambient temperature remains within the specified operating range (-30℃ to 55℃).
- Mounting: Securely mount the inverter according to the provided mounting instructions. Ensure adequate clearance for air circulation, as the unit uses air cooling.
- Electrical Connections: All electrical connections (PV input, battery connections, AC grid connection, and AC load output) must be made by a licensed electrician. Pay close attention to polarity and torque specifications for all terminals. The system supports a 3W+N+PE grid type.
- Grounding: Ensure the inverter is properly grounded to prevent electrical hazards.
- PV Capacity: The PV input voltage should not exceed 1,000V. The MPPT voltage range is 250V to 850V.
- Battery Compatibility: The inverter is compatible with Lithium-ion and Lead-acid batteries. Ensure the battery voltage range is within 250V to 850V (specific to MPS0500 model).

3. Operating Instructions
The Megarevo MPS Series Hybrid Solar Inverter features an intuitive LCD touch-screen display for monitoring and configuration. Once installed and powered on, the system will initiate its startup sequence.
3.1 System Modes
- On-Grid Mode: In this mode, the inverter synchronizes with the utility grid, supplying power to loads and potentially exporting excess solar energy to the grid.
- Off-Grid Mode: When the utility grid is unavailable or intentionally disconnected, the inverter operates in off-grid mode, drawing power from PV and batteries to supply connected loads. The automatic switching unit ensures seamless transition between modes.
- Battery Charging: The inverter intelligently manages battery charging from both PV and the grid (if configured) to maintain optimal battery health and ensure power availability.
3.2 Monitoring and Configuration
The LCD touch-screen display provides real-time data on PV production, battery status, load consumption, and grid interaction. Users can access various settings to customize system behavior, such as charge/discharge parameters, power factor (settable from 1 leading to 1 lagging), and operational priorities. Refer to the detailed user interface guide for specific menu navigation and parameter adjustments.
4. Maintenance
Regular maintenance ensures the longevity and efficient operation of your Megarevo MPS Series Hybrid Solar Inverter.
4.1 Routine Checks
- Visual Inspection: Periodically inspect the inverter for any signs of damage, loose connections, or unusual noises. Ensure ventilation openings are clear of obstructions.
- Cleaning: Keep the inverter's exterior clean. Use a dry, soft cloth. Do not use liquids or abrasive cleaners.
- Environmental Conditions: Verify that the operating environment remains within the specified temperature and humidity ranges (Operation temperature: -30℃ ~ 55℃; Relative humidity: 0 ~95% non-condensing). The inverter has an Ingress Protection rating of IP20, meaning it is protected against solid objects larger than 12.5mm but not against water.
- Firmware Updates: Check with Megarevo support for any available firmware updates to ensure optimal performance and access to new features.
4.2 Professional Servicing
For any internal inspections, repairs, or complex troubleshooting, contact a certified Megarevo service technician. Do not attempt to open or repair the inverter yourself, as this may void the warranty and pose safety risks.
5. Troubleshooting
This section provides general guidance for common issues. For detailed troubleshooting or persistent problems, contact technical support.
5.1 Common Issues and Solutions
- No Power Output: Check all AC and DC connections. Verify that the PV array is producing power and batteries are charged. Check circuit breakers and fuses.
- Inverter Not Starting: Ensure sufficient PV input voltage and battery charge. Check for any error messages on the LCD display.
- Error Codes on Display: Refer to the specific error code definitions in the comprehensive user manual (if provided separately) or contact technical support with the exact code.
- Reduced Performance: Check for shading on PV panels, dirty panels, or high ambient temperatures. Ensure all system components are operating within their specified parameters.
Always prioritize safety. If you are unsure about any troubleshooting step, contact a qualified technician.
6. Specifications
The following table details the technical specifications for the Megarevo MPS Series Hybrid Inverters, including the MPS0500 model.
| Model | MPS0030 | MPS0050 | MPS0100 | MPS0150 | MPS0250 | MPS0500 |
|---|---|---|---|---|---|---|
| AC (on-grid) | ||||||
| Max. output power (kW) | 33 | 55 | 110 | 165 | 275 | 550 |
| Rated output power (kW) | 30 | 50 | 100 | 150 | 250 | 500 |
| Rated voltage (V) | 400 | |||||
| Voltage range (V) | 320~460 | |||||
| Rated current (A) | 43 | 72 | 144 | 216 | 361 | 722 |
| Rated frequency (Hz) | 50/60 | |||||
| Frequency range (Hz) | 45~55 / 55~65 | |||||
| THDi | <3% | |||||
| Power factor | 1leading-1lagging (settable) | |||||
| Grid type | 3W+N+PE | |||||
| AC (off-grid) | ||||||
| Max. output power (kW) | 33 | 55 | 110 | 165 | 275 | 550 |
| Rated power (kW) | 30 | 50 | 100 | 150 | 250 | 500 |
| Rated voltage (V) | 400 | |||||
| Rated current (A) | 43 | 72 | 144 | 216 | 361 | 722 |
| THDu | ≤1% linear; or≤5% nonlinear | |||||
| Rated frequency (Hz) | 50/60 | |||||
| Overload capacity | 110% long-term, 120% 1min | |||||
| PV input | ||||||
| Max. PV input voltage (V) | 1,000 | |||||
| Max. PV power (kW) | 36/72 | 60/120 | 120/180/240 | 300/360 | 600/660/720 | |
| MPPT module quantity | 1/2 | 1/2 | 2/3/4 | 5/6 | 10/11/12 | |
| MPPT voltage range (V) | 250~850 | |||||
| Battery | ||||||
| Battery voltage range (V) | 250~850 | 320~850 | 420~850 | 420~850 | 500~850 | |
| Max. charging power (kW) | 36/72 | 60/120 | 120/180/240 | 300/360 | 600/660/720 | |
| General | ||||||
| Size | 800*800*1,900mm (for MPS0500) | |||||
| Weight | 3325kg (for MPS0500) | |||||
| Operation temperature | -30℃ ~ 55℃ | |||||
| Relative humidity | 0 ~95% non-condensing | |||||
| Ingress protection | IP20 | |||||
| Cooling | Air Cooling | |||||
| Display | LCD touch-screen | |||||
7. User Tips
- System Monitoring: Regularly check the inverter's LCD display or connected monitoring platform to track energy production, consumption, and battery status. This helps in optimizing energy usage and identifying potential issues early.
- Battery Management: For optimal battery life, avoid consistently deep discharging the batteries. Configure charging parameters to suit your battery type and usage patterns.
- Load Management: Be mindful of the inverter's overload capacity. While it can handle 110% long-term and 120% for 1 minute, continuous overloading can reduce efficiency and lifespan.
8. Warranty and Support
For warranty information, technical support, or service requests, please contact your Megarevo dealer or the manufacturer directly. Ensure you have your product model (MPS0500) and serial number available when contacting support.
9. Visual Aids
9.1 Product Features Overview