1. Introduction
This manual describes the assembly, installation, operation, and troubleshooting of the SUMRY HGX 4KW 24V 110/120V Pure Sine Wave MPPT Solar Charge Hybrid Inverter. Please read this manual carefully before installation and operation. Keep this manual for future reference.
1.1. Purpose and Scope
This multi-function inverter/charger combines the functions of an inverter, MPPT solar charger, and battery charger to provide uninterruptible power support in a portable size. Its large LCD display offers user-configurable and easy-accessible touch button operation for settings such as battery charging current, AC/solar charger priority, and acceptable input voltage based on different applications.
This manual provides safety and installation guidelines, along with information on tools and wiring necessary for proper setup and use.
1.2. Key Features
- Off-grid solar inverter functionality.
- No battery function available (can operate without battery).
- Adjustable AC voltage (100VAC, 110VAC, and 120VAC) in Battery Mode.
- Utility power, battery, and PV power complement each other.
- Pure sine wave output.
- Unique glass top cover design with 6.25-inch LCD display and touchable buttons.
- Built-in 140A MPPT (Max PV 5600W) solar charger.
- High PV input range from 55V-350Vdc.
- Smart battery charger design for optimized battery performance.
- Configurable AC/Battery input priority via LCD setting.
- Auto restart while PV is recovering.
- Overload, over temperature, and output short circuit protection.
- Cold restart function.
- Built-in lithium battery automatic activation.
- Communication with RS232/RS485.
- WiFi monitoring function (optional).
- Anti-dust kit for harsh environments (optional).
- Restore default settings with one click.



1.3. Basic System Architecture
The following illustration shows a basic application for this inverter/charger. A complete running system includes:
- Generator or Utility power source.
- PV modules (optional).
Consult with your system integrator for other possible system architectures depending on your requirements. This inverter can power various appliances in home or office environments, including motor-type appliances such as tube lights, fans, refrigerators, and air conditioners.


2. Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
- CAUTION -- To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
- CAUTION – Only qualified personnel can install this device with battery.
- NEVER charge a frozen battery.
- For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
- Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
- GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
- NEVER cause AC output and DC input short-circuited. Do NOT connect to the mains when DC input short circuits.
- Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.
3. Installation
3.1. Unpacking and Inspection
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items:
- The unit x 1
- User manual x 1
3.2. Preparation
Before connecting all wirings, please remove the bottom cover by unscrewing two screws.
3.3. Mounting the Unit
Consider the following points before selecting where to install the inverter:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install this inverter at eye level to allow the LCD display to be read at all times.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
- Ensure sufficient heat dissipation and enough space for removing wires by keeping other objects and surfaces as shown in the diagram.
CAUTION: Suitable for mounting on concrete or other non-combustible surface only.

Install the unit by screwing two screws into the mounting surface.
3.4. Battery Connection
CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between the battery and inverter. While a disconnect device may not be required in some applications, over-current protection is always necessary. Refer to the table below for typical amperage and required fuse or breaker size.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.
Recommended Battery Cable and Terminal Size:
| Model | Typical Amperage | Battery Capacity | Wire Size | Cable (mm²) | Ring Terminal Dimensions (mm) | Torque Value (Nm) | ||
|---|---|---|---|---|---|---|---|---|
| D | L | M | ||||||
| 3.0KW 24V | 110A | 100AH | 1*4AWG | 22 | 8 | 44 | 18.2 | 2~3 |
| 200AH | 8 | 44 | 18.2 | |||||
| 4.0KW 24V | 150A | 200AH | 1*2AWG | 35 | 8 | 44 | 18.2 | 2~3 |
Follow these steps to connect the battery:
- Assemble battery ring terminal based on recommended battery cable and terminal size.
- Connect all battery packs as units require.
- NOTE: Please only use sealed lead-acid battery or sealed GEL/AGM lead-acid battery or lithium battery.
- Insert the ring terminal of the battery cable flatly into the battery connector of the inverter and ensure the bolts are tightened with a torque of 2-3 Nm. Verify that the polarity at both the battery and the inverter/charger is correctly connected, and ring terminals are tightly screwed to the battery terminals.

- WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.
- CAUTION!! Do not place anything between the flat part of the inverter terminal and the ring terminal. Otherwise, overheating may occur.
- CAUTION!! Do not apply anti-oxidant substance on the terminals before terminals are connected tightly.
- CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).
3.5. AC Input/Output Connection
CAUTION!! Before connecting to an AC input power source, please install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and fully protected from overcurrent of AC input. The recommended AC breaker specifications are 32A for 3.0KW and 40A for 4.0KW.
CAUTION!! There are two terminal blocks with "INPUT" and "OUTPUT" markings. Please do NOT mis-connect input and output connectors.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested Cable Requirement for AC Wires:
| Model | Gauge | Torque Value (Nm) |
|---|---|---|
| 3.0KW | 10 AWG | 1.2~1.6 |
| 4.0KW | 8 AWG | 1.4~1.6 |
Follow these steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open the DC protector or disconnector first.
- Remove insulation sleeve 10mm for six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities indicated on the terminal block and tighten the terminal screws.

WARNING: Be sure that the AC power source is disconnected before attempting to hardwire it to the unit.
- Then, insert AC output wires according to polarities indicated on the terminal block and tighten terminal screws. Be sure to connect the PE protective conductor (Ground, green) first.
- Make sure the wires are securely connected.
CAUTION: Important Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
CAUTION: Appliances such as air conditioners require at least 2-3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.
3.6. PV Connection
CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between the inverter and PV modules.
WARNING! All wiring must be performed by qualified personnel.
WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested Cable Requirement for PV Wires:
| Model | Wire Size | Cable (mm²) | Torque Value (Nm) |
|---|---|---|---|
| 3.0KW/4.0KW | 1 x 12AWG | 4 | 1.2 |
PV Module Selection:
When selecting proper PV modules, please be sure to consider the below parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the min. PV Array MPPT Voltage range.
| INVERTER MODEL | 3.0KW | 4.0KW |
|---|---|---|
| Max. PV Array Open Circuit Voltage | 350Vdc | |
| PV Array MPPT Voltage Range | 55Vdc~350Vdc | |
Follow these steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors. Then, connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector. Connect the negative pole (-) of the connection cable to the negative pole (-) of the PV input connector.


- Make sure the wires are securely connected.
3.7. Final Assembly
After connecting all wirings, please put the bottom cover back by screwing two screws.
4. Operation
4.1. Power ON/OFF
Once the unit has been properly installed and the batteries are connected, simply press the On/Off switch (located on the bottom of the case) to turn on the unit.
4.2. Operation and Display Panel
The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

LED Indicator:
| LED Indicator | Messages | |
|---|---|---|
| AC/INV | Green Solid On | Output is powered by utility in Line mode. |
| Green Flashing | Output is powered by battery or PV in battery mode. | |
| CHG | Green Solid On | Battery is fully charged. |
| Green Flashing | Battery is charging. | |
| FAULT | Red Solid On | Fault occurs in the inverter. |
| Red Flashing | Warning condition occurs in the inverter. |
Function Keys:
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
4.3. LCD Display Icons
The LCD display provides various information through icons. Here's a description of the main icons:
Input Source Information:
| Icon | Function Description |
|---|---|
| AC | Indicates the AC input. |
| PV | Indicates the PV input. |
| INPUT/BATTERY/TEMP | Indicates input voltage, input frequency, PV voltage, battery voltage, and charger current. |
Configuration Program and Fault Information:
| Icon | Function Description |
|---|---|
| (Setting Programs Icon) | Indicates the setting programs. |
| (Warning/Fault Codes Icon) | Indicates the warning and fault codes. |
| ERROR (Flashing) | Warning: Flashing with warning code. |
| ERROR (Solid) | Fault: Lighting with fault code. |
Output Information:
| Icon | Function Description |
|---|---|
| OUTPUT/BATT/LOAD | Indicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current. |
Battery Information:
| Icon | Function Description |
|---|---|
| (Battery Level Bar) | Left side flashing bar and battery icon indicates battery level by 0-20%, 20-40%, 40-60%, and 80-100% in battery mode and charging status in line mode. |
Load Information:
| Icon | Function Description |
|---|---|
| OVER LOAD | Indicates overload. |
| (Load Level Bar) | Right side flashing bar and load icon indicates the load level by 0-24%, 25-50%, 50-75%, and 75-100%. |
Mode Operation Information:
| Icon | Function Description |
|---|---|
| (Utility Grid Icon) | Indicates unit connects to the mains. |
| (Solar Panel Icon) | Indicates unit connects to the PV panel. |
| BYPASS | Indicates load is supplied by utility power. |
| (Utility Charger Icon) | Indicates the utility charger circuit is working. |
| (DC/AC Inverter Icon) | Indicates the DC/AC inverter circuit is working. |
Mute Operation:
| Icon | Function Description |
|---|---|
| (Mute Icon) | Indicates unit alarm is disabled. |
4.4. LCD Settings
After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press the "UP" or "DOWN" button to select setting programs. Then, press the "ENTER" button to confirm the selection or the ESC button to exit.
Setting Programs:
| Program | Description | Selectable Option |
|---|---|---|
| 00 | Exit setting mode | ESC |
| 01 | Output source priority: To configure load power source priority |
|
| 02 | Maximum charging current: To configure total charging current for solar and utility chargers. (Max. charging current = utility charging current + solar charging current) |
|
| 03 | AC input voltage range |
|
| 04 | Power saving mode enable/disable |
|
| 05 | Battery type (Notice: in battery-free working mode, the value cannot be set to LIB or lib-485) |
|
| 06 | Auto restart when overload occurs |
|
| 07 | Auto restart when over temperature occurs |
|
| 08 | Output voltage |
|
| 09 | Output frequency |
|
| 11 | Maximum utility charging current |
|
| 12 | Setting voltage point back to utility source when selecting "SBU priority" |
|
| 13 | Setting voltage point back to battery mode when selecting "SBU priority" |
|
| 16 | Charger source priority: To configure charger source priority |
|
| 18 | Alarm control |
|
| 19 | Auto return to default display screen |
|
| 20 | Backlight control |
|
| 22 | Beeps while primary source is interrupted |
|
| 25 | Record Fault code |
|
| 26 | Bulk charging voltage (C.V voltage) |
|
| 27 | Floating charging voltage |
|
| 29 | Low DC cut-off voltage |
|
| 30 | Restore default settings |
|
| 33 | Battery equalization |
|
| 34 | Battery equalization voltage |
|
| 35 | Battery equalized time |
|
| 36 | Battery equalized timeout |
|
| 37 | Equalization interval |
|
| 39 | Equalization activated immediately |
|
4.5. Lithium Battery Connection and Settings
If the inverter is matched with lithium batteries, only lithium batteries that have been matched with the BMS communication protocol are allowed to be used.
Follow these steps to implement lithium battery connection:
- Assemble battery ring terminal based on recommended battery cable and terminal specifications.
- Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2-3Nm. Make sure polarity at both the battery and the inverter/charge is correctly connected and ring terminals are tightly screwed to the battery terminals.
- Connect the RJ45 connector to the COMM port on the inverter.
- Connect the other end of the RJ45 plug to the battery communication port (RS485). Ensure that the battery signal cable RS485-A is connected to the RS485-A of the COMM port, and the battery signal cable RS485-B is connected to the RS485-B of the COMM port.
Note: If choosing a lithium battery, make sure to connect the BMS communication cable between the battery and the inverter. You need to choose battery type as "Lib-485" mode.
Lithium Battery Communication Port Pin Definition:

| Pin Number | Definition |
|---|---|
| 1 | RX |
| 2 | TX |
| 3 | VCC |
| 4 | VCC |
| 5 | RS485-A |
| 6 | RS485-B |
| 7 | GND |
| 8 | GND |
Lithium Battery Communication and Setting:
To communicate with the battery BMS, set the battery type to "Lib-485" in Program 5. The default charging current is 0.5C. When the battery type is set to "Lib-485", the settings for programs 12, 13, and 29 are adjusted as follows:
- Program 12 (Setting SOC point back to utility source when selecting SBU): 10%-50% can be set.
- Program 13 (Setting SOC point back to battery mode when selecting SBU): 30%-100% can be set.
- Program 29 (SOC shutdown point): 5%-30% can be set.
Note: When the battery type is set to "Lib-485", the charge current cannot be modified by the user. If communication fails, the inverter will cut off output.
After pressing and holding the "ESC" button for 3 seconds, enter the lithium battery page. The lithium battery information display content includes:
| LCD Data on the Left | LCD Data on the Right | Instruction |
|---|---|---|
| Total battery voltage | Remaining battery capacity | |
| Battery charging current | Battery discharge current | |
| Battery capacity | Battery charge/discharge times | Warning in the middle |
| BMS board temperature | Mosfet temperature of BMS board | |
| Maximum voltage of a single battery cell | Minimum voltage of a single battery cell | |
| Maximum temperature of a single battery cell | Minimum temperature of a single battery cell |
Long press the ENTER key to enter the setting item and set program 05 to Lib-485 mode. If communication fails (LCD display shows code 51), the inverter will cut off output. If the communication protocol does not match, you can select "LIB" mode.
Long press the ESC key to enter the lithium battery display interface. The initial display interface indicates the total battery voltage and remaining battery capacity.
4.6. Display Setting
The LCD display information will be switched in turns by pressing the "UP" or "DOWN" key. The selectable information is switched in the following order: input voltage, input frequency, PV voltage, MPPT charging current, MPPT charging power, battery voltage, output voltage, output frequency, load percentage, load in VA, load in Watt, DC discharging current, main CPU Version.
4.7. Operating Mode Description
The inverter operates in various modes depending on the power sources available and configured priorities.
| Operation Mode | Description | LCD Display |
|---|---|---|
| Standby mode / Power saving mode | Standby mode: The inverter is not turned on yet, but can charge the battery without AC output. Power saving mode: If enabled, the output of the inverter will be off when the connected load is very low or not detected. No output is supplied by the unit but it still can charge batteries. | Charging by utility and PV energy. Charging by utility. Charging by PV energy. No charging. |
| Fault mode | Errors caused by internal circuit errors or external reasons (e.g., over temperature, output short circuit). The inverter will disconnect all inputs and outputs (PV, load, grid, battery). Red fault indicator will be steady on, and buzzer alarm will sound. | Over-temperature Output low voltage Output overcurrent Battery low |
| Line Mode | The unit will provide output power from the mains. It will also charge the battery at line mode. | Charging by utility and PV energy. Charging by utility. If "SUE" is selected as output source priority and solar energy is not sufficient to provide the load, solar energy and the utility will provide the loads and charge the battery at the same time. If "SUE" is selected as output source priority and battery is not connected, solar energy and the utility will provide the loads. Power from utility. |
| Battery Mode | The unit will provide output power from battery and PV power. | Power from battery and PV energy. PV energy will supply power to the loads and charge battery at the same time. Power from battery only. Power from PV energy only. |
5. Maintenance
5.1. Battery Equalization Description
Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalization also helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery. Therefore, it's recommended to equalize the battery periodically.
How to Apply Equalization Function:
You must enable the battery equalization function in monitoring LCD setting program 33 first. Then, you may apply this function in the device by either one of the following methods:
- Setting equalization interval in program 37.
- Active equalization immediately in program 39.
When to Equalize:
In the float stage, when the setting equalization interval (battery equalization cycle) is reached, or equalization is active immediately, the controller will start to enter the Equalize stage.
In the Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain the battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is reached.
However, in the Equalize stage, if the battery equalized time expires and the battery voltage doesn't rise to the battery equalization voltage point, the charge controller will extend the battery equalized time until the battery voltage achieves the battery equalization voltage. If the battery voltage is still lower than the battery equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.
6. Troubleshooting
6.1. Fault Reference Code
| Fault Code | Fault Event | Icon on |
|---|---|---|
| 01 | Fan is locked when inverter is off. | (Fan icon) |
| 02 | Over temperature | (Temperature icon) |
| 03 | Battery voltage is too high | (Battery icon) |
| 04 | Battery voltage is too low | (Battery icon) |
| 05 | Output short circuited or over temperature is detected by internal converter components. | (Error icon) |
| 06 | Output voltage is too high. | (Voltage icon) |
| 07 | Overload time out | (Overload icon) |
| 08 | Bus voltage is too high | (Voltage icon) |
| 09 | Bus soft start failed | (Error icon) |
| 11 | Main relay failed | (Error icon) |
| 51 | Over current or surge | (Overcurrent icon) |
| 52 | Bus voltage is too low | (Voltage icon) |
| 53 | Inverter soft start failed | (Error icon) |
| 55 | Over DC voltage in AC output | (Voltage icon) |
| 56 | Battery connection is open | (Battery icon) |
| 57 | Current sensor failed | (Error icon) |
| 58 | Output voltage is too low | (Voltage icon) |
6.2. Warning Indicator
| Warning Code | Warning Event | Audible Alarm | Icon flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep twice every second | (Fan icon) |
| 03 | Battery is over-charged | Beep twice every second | (Battery icon) |
| 04 | Low battery | Beep twice every second | (Battery icon) |
| 07 | Overload | Beep twice every second | (Overload icon) |
| 10 | Output power derating | Beep twice every second | (Power icon) |
| 12 | Solar charger stops due to low battery. | (Solar icon) | |
| 13 | Solar charger stops due to high PV voltage. | (Solar icon) | |
| 14 | Solar charger stops due to overload. | (Solar icon) | |
| 15 | PV is weak | (Solar icon) | |
| 61 | When the battery communication is abnormal, stop charging and discharging. | (Battery icon) |
6.3. Common Problems and Solutions
| Problem | LCD/LED/Buzzer | Explanation / Possible Cause | What to Do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD/LEDs and buzzer will be active for 3 seconds and then complete off. | The battery voltage is too low (<1.91V/Cell) | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. The battery voltage is far too low. (<1.4V/Cell) 2. Battery polarity is connected reversed. | 1. Check if batteries and the wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
| Input voltage is displayed as 0 on the LCD and green LED is flashing. | Input protector is tripped | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but the unit works in battery mode. | Green LED is flashing. | Insufficient quality of AC power. (Shore or Generator) | 1. Check if AC wires are too thin and/or too long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance) |
| Green LED is flashing. | Set "Solar First" as the priority of output source. | Change output source priority to Utility first. | |
| When the unit is turned on, internal relay is switched on and off repeatedly. | LCD display and LEDs are flashing | Battery is disconnected. | Check if battery wires are connected well. |
| Buzzer beeps continuously and red LED is on. | Fault code 07 | Overload error. The inverter is overload 110% and time is up. | Reduce the connected load by switching off some equipment. |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Temperature of internal converter component is over 120°C. | Check whether the air flow of the unit is blocked or whether the ambient temperature is too high. | ||
| Fault code 02 | Internal temperature of inverter component is over 100°C. | Return to repair center. | |
| Fault code 03 | Battery is over-charged. | Check if spec and quantity of batteries are meet requirements. | |
| The battery voltage is too high. | Replace the fan. | ||
| Fault code 01 | Fan fault. | 1. Reduce the connected load. 2. Return to repair center. | |
| Fault code 06/58 | Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac) | Return to repair center. | |
| Fault code 08/09/53/57 | Internal components failed. | Restart the unit, if the error happens again, please return to repair center. | |
| Fault code 51 | Over current or surge. | If the battery is connected well, please return to repair center. | |
| Fault code 52 | Bus voltage is too low. | ||
| Fault code 55 | Output voltage is unbalanced. | ||
| Fault code 56 | Battery is not connected well or fuse is burnt. |
7. Specifications
7.1. Table 1 Line Mode Specifications
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) | |
| Nominal Input Voltage | 120Vac | |
| Low Loss Voltage | 95Vac±5V(UPS); 65Vac±7V(Appliances) | |
| Low Loss Return Voltage | 100Vac±5V(UPS); 70Vac±5V(Appliances) | |
| High Loss Voltage | 140Vac±5V | |
| High Loss Return Voltage | 135Vac±5V | |
| Max AC Input Voltage | 150Vac | |
| Nominal Input Frequency | 50Hz / 60Hz (It can be set in program 09) | |
| Low Loss Frequency | 45±1Hz/55±1Hz | |
| Low Loss Return Frequency | 47±1Hz/57±1Hz | |
| High Loss Frequency | 55±1Hz/65±1Hz | |
| High Loss Return Frequency | 53±1Hz/63±1Hz | |
| Output Short Circuit Protection | Line mode: Circuit Breaker Battery mode: Electronic Circuits | |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) | |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) | |
7.2. Table 2 Inverter Mode Specifications
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Rated Output Power | 3.0KW | 4.0KW |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 120Vac±5% | |
| Output Frequency | 60Hz or 50Hz | |
| Peak Efficiency | 94% | |
| Overload Protection | 5s@≥150% load; 10s@110%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 24Vdc | |
| Cold Start Voltage | 23.0Vdc | |
| Low DC Warning Voltage | 22.0Vdc | |
| Low DC Warning Return Voltage | 23.0Vdc | |
| Low DC Cut-off Voltage | 21.0Vdc | |
| High DC Recovery Voltage | 29Vdc | |
| High DC Cut-off Voltage | 31Vdc | |
| No Load Power Consumption | <35W | |
7.3. Table 3 Charge Mode Specifications
Utility Charging Mode:
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Charging Current (UPS) @ Nominal Input Voltage | 80A | 110A |
| Bulk Charging Voltage (Flooded Battery) | 29.2Vdc | |
| Bulk Charging Voltage (AGM / Gel Battery) | 28.2Vdc | |
| Floating Charging Voltage | 27Vdc | |
| Charging Algorithm | 3-Step | |
Solar Charging Mode:
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Rated Power | 5600W | |
| PV Charge Current | 100A | 140A |
| Efficiency | 98.0% max. | |
| Max. PV Array Open Circuit Voltage | 350Vdc | |
| PV Array MPPT Voltage Range | 55-350Vdc | |
| Standby Power Consumption | 2W | |
| Battery Voltage Accuracy | +/-0.3% | |
| PV Voltage Accuracy | +/-2V | |
| Charging Algorithm | 3-Step | |
7.4. Table 4 General Specifications
| INVERTER MODEL | 3.0KW/24V | 4.0KW/24V |
|---|---|---|
| Safety Certification | CE | |
| Operating Temperature Range | 0°C to 55°C | |
| Storage temperature | -15°C~60°C | |
| Dimension (D*W*H), mm | 400*250*89mm | |
| Net Weight, kg | 7.5kg | 8.5kg |
7.5. Appendix: Approximate Back-up Time Table
| Model | Load (W) | Backup Time @ 24Vdc 100Ah (min) | Backup Time @ 24Vdc 200Ah (min) |
|---|---|---|---|
| 4.0KW | 300 | 449 | 1100 |
| 600 | 222 | 525 | |
| 900 | 124 | 303 | |
| 1200 | 95 | 227 | |
| 1500 | 68 | 164 | |
| 1800 | 56 | 126 | |
| 2100 | 48 | 108 | |
| 2400 | 35 | 94 | |
| 2700 | 31 | 74 | |
| 3200 | 28 | 67 |
Note: Backup time depends on the quality of the battery, age of battery, and type of battery. Specifications of batteries may vary depending on different manufacturers.
* Product technical specifications are subject to change without notice.
8. User Tips
- Battery-less Operation: This inverter is capable of operating without a battery, directly utilizing solar or utility power to supply loads. This can be a useful feature for systems where battery storage is not required or desired.
- Optimal Cable Sizing: Always use the recommended cable sizes for battery, AC, and PV connections to ensure optimal performance and safety, as specified in the installation section.
- Regular Equalization: If using compatible battery types, consider enabling the battery equalization function periodically to prolong battery life and maintain performance by preventing stratification and sulfation.
9. Warranty and Support
This SUMRY inverter comes with a 1-year warranty, ensuring reliability and performance. For detailed warranty terms and conditions, please refer to the official documentation provided with your purchase.
For technical support, service, or maintenance inquiries, please contact your local dealer or an authorized service center. Do not attempt to service the device yourself unless explicitly instructed by qualified personnel.
A comprehensive user manual in PDF format is available for download and further reference: Download User Manual (PDF).