SUMRY MPS VIII ECO

Contents

SUMRY MPS VIII ECO Series Hybrid Solar Inverter User Manual

Models: 3.6KW/4.2KW/6.2KW

1. About This Manual

1.1 Purpose

This manual describes the assembly, installation, operation, and troubleshooting of the SUMRY MPS VIII ECO series hybrid inverter. Please read this manual carefully before installations and operations. Keep this manual for future reference.

1.2 Scope

This manual provides safety and installation guidelines as well as information on tools and wiring for the 3.6KW, 4.2KW, and 6.2KW models.

1.3 Features

  • Pure sine wave inverter
  • Configurable input voltage range for home appliances and personal computers via LCD setting
  • Configurable battery charging current based on applications via LCD setting
  • Configurable AC/Solar Charger priority via LCD setting
  • Compatible with mains voltage or generator power
  • Auto restart while AC is recovering
  • Overload/Over temperature/short circuit protection
  • Smart battery charger design for optimized battery performance
  • Cold start function
  • WIFI/GPRS (Optional)

1.4 Basic System Architecture

The hybrid inverter combines functions of an inverter, solar charger, and battery charger to provide uninterruptible power support. A typical system includes the inverter, solar panels (PV modules), a battery bank, and optionally a generator or utility grid connection. The inverter can power various home and office appliances, including motor-type loads.

Diagram showing the basic system architecture of the hybrid inverter with solar panels, battery, utility grid, generator, and home appliances.
Figure 1: Basic System Architecture

The inverter is designed to work with or without a battery, offering flexibility in power management. It supports various operational priorities such as 'Only Solar', 'Utility Priority', and 'Solar & Utility' to optimize energy usage.

Diagram illustrating solar priority, utility priority, and solar and utility priority modes.
Figure 2: Operational Priority Modes

The inverter is capable of powering a wide range of appliances, from induction cookers and refrigerators to air compressors and power tools.

Illustrations of various home and office appliances that can be powered by the inverter, including an induction cooker, rice cooker, air conditioner, refrigerator, sealing machine, air compressor, chainsaw, hammer drill, and angle grinder.
Figure 3: Appliance Compatibility

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  3. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  4. CAUTION – Only qualified personnel can install this device with battery.
  5. NEVER charge a frozen battery.
  6. For optimum operation of this inverter/charger, please follow required specifications to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  7. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  8. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to the INSTALLATION section of this manual for details.
  9. One piece of 150A fuse is provided as over-current protection for the battery supply.
  10. GROUNDING INSTRUCTIONS - This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulations to install this inverter.
  11. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  12. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

3. Setup (Installation)

3.1 Unpacking and Inspection

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the unit and a user manual.

3.2 Preparation

Before connecting any lines, remove the screws under the machine and remove the bottom cover plate.

3.3 Mounting the Unit

Consider the following points before selecting where to install:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install this inverter at eye level to allow the LCD display to be read at all times.
  • For proper air circulation to dissipate heat, allow a clearance of approximately 20 cm to the side and approximately 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.
  • Make sure that other objects and surfaces are left with enough space from the machine to ensure adequate heat dissipation and that there is enough room to remove the wires.

Install the unit by screwing two M6 screws into the wall.

Diagram showing the dimensions of the inverter (420*310*110mm) and the location of communication ports (BMS, WiFi, RS485, RS232) and battery/PV inputs.
Figure 4: Product Dimensions and Port Overview

3.4 Battery Connection

CAUTION: For safety operation and regulation compliance, it's requested to install a separate DC over-current protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in some applications, however, it's still requested to have over-current protection installed. Please refer to typical amperage in the table below as required fuse or breaker size.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable size as below.

Recommended Battery Cable Size
ModelWire SizeCable (mm²)Torque value (max)
3.6KW/4.2KW/6.2KW1 x 2AWG252 Nm

Follow these steps to implement battery connection:

  1. Remove insulation sleeve 18 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the chart below.
  4. Insert the battery wires flatly into battery connectors of inverter and make sure the bolts are tightened with a torque of 2 Nm in clockwise direction. Make sure polarity at both the battery and the inverter/charger is correctly connected and conductors are tightly screwed into the battery terminals. Recommended tool: #2 Pozi Screwdriver.
Diagram showing how to connect multiple 12V batteries in series to the inverter for both 3.6KW/4.2KW and 6.2KW models.
Figure 5: Battery Connection Diagram

WARNING: Shock Hazard Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing DC breaker/disconnector, be sure positive (+) must be connected to positive (+) and negative (-) must be connected to negative (-).

3.5 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 32A for 3.6KW/4.2KW and 50A for 6.2KW.

CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by a qualified personnel.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.

Suggested Cable Requirement for AC Wires
ModelGaugeCable (mm²)Torque Value
3.6KW/4.2KW12 AWG41.2 Nm
6.2KW10 AWG61.2 Nm

Please follow these steps to implement AC input/output connection:

  1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. L→LINE (brown or black), N→Neutral (blue).
Diagram showing AC input and output wiring connections with L (Line) and N (Neutral) terminals.
Figure 6: AC Input/Output Wiring

WARNING: Be sure that AC power source is disconnected before attempting to hardwire it to the unit.

  1. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. L→LINE (brown or black), N→Neutral (blue).
  2. Make sure the wires are securely connected.

CAUTION: Appliances such as air conditioners require at least 2-3 minutes to restart because it's required to have enough time to balance refrigerant gas inside of circuits. If a power shortage occurs and recovers in a short time, it will cause damage to your connected appliances. To prevent this kind of damage, please check the manufacturer of the air conditioner if it's equipped with a time-delay function before installation. Otherwise, this inverter/charger will trigger an overload fault and cut off output to protect your appliance, but sometimes it still causes internal damage to the air conditioner.

3.6 PV Connection

CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.

WARNING! It's very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.

Recommended PV Cable Size
ModelWire SizeCable (mm²)Torque value (max)
3.6KW/4.2KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection: When selecting proper PV modules, please be sure to consider below parameters:

  1. Open circuit Voltage (Voc) of PV modules not to exceed max. PV array open circuit voltage of inverter.
  2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
Inverter PV Specifications
INVERTER MODEL3.6KW/4.2KW6.2KW
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc

For example, using 250Wp PV modules (Vmp: 30.1Vdc, Imp: 8.3A, Voc: 37.7Vdc, Isc: 8.4A, Cells: 60), recommended module configurations are:

Recommended PV Module Configurations (250Wp Example)
SOLAR INPUT (Min in serial: 6 pcs, max. in serial: 13 pcs)Q'ty of panelsTotal input power
6 pcs in serial6 pcs1500W
8 pcs in serial8 pcs2000W
12 pcs in serial12 pcs3000W
13 pcs in serial13 pcs3250W
8 pieces in serial and 2 sets in parallel16 pcs4000W
10 pieces in serial and 2 sets in parallel20 pcs5000W
10 pieces in serial and 2 sets in parallel20 pcs6200W
12 pieces in serial and 2 sets in parallel24 pcs6500W
10 pieces in serial and 3 sets in parallel30 pcs7500W

PV Module Wire Connection: Follow these steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Suggest to put bootlace ferrules on the end of positive and negative wires with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Then, connect positive pole (+) of connection wire to positive pole (+) of PV input connector. Connect negative pole (-) of connection wire to negative pole (-) of PV input connector. Recommended tool: 4mm blade screwdriver.
Diagram showing PV module wire connection steps, including insulation removal and connecting positive and negative poles.
Figure 7: PV Module Wire Connection

3.7 Final Assembly

After connecting all wirings, please put the bottom cover back by screwing two screws.

3.8 Communication Connection

The inverter features dual communication ports for battery and WiFi communication (RS485, RS232).

Detailed view of the inverter's rear panel showing AC input, Main output, Second output, Battery communication RS-485 port, WIFI communication RS-232 port, PV input, and Battery input.
Figure 8: Inverter Communication Ports and Inputs
  1. Wi-Fi Cloud Communication (Option): Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" to set up the network and register. The inverter status will be shown by mobile phone APP or a computer webpage.
  2. GPRS Cloud Communication (Option): Use the supplied communication cable to connect to the inverter and GPRS module, and then apply external power to the GPRS module. Download the APP from the APP store and refer to the "GPRS RTU Quick Installation Guideline" to set up the network and register. The inverter status will be shown by mobile phone APP or a computer webpage.
  3. Battery Communication: The communication between the battery and the inverter can be realized through the battery communication interface, so that the inverter and the lithium battery can exchange information (Baud rate: 9600).

3.9 Lithium Battery and Inverter Connection

If choosing a lithium battery for the inverter, only lithium batteries that have been matched with BMS communication protocol are allowed.

  1. Connect the battery according to the recommended battery cable specifications.
  2. Insert the ring terminal of the battery cable into the battery connector of the inverter flatly, and ensure that the bolts are tightened with a torque of 2-3 Nm. Make sure that the polarities of the battery and inverter are connected correctly, and that the ring terminal is tightened with the battery terminal.
  3. Connect one side of the RJ45 cable to the BMS communication port of the inverter.
  4. Insert the other side of the RJ45 cable into the RS485 communication port on the lithium battery.

NOTE: If you choose a lithium battery, please make sure to connect the battery and inverter with BMS communication cable, and select the battery type as "LIB-485" mode.

Communication And Setting Of Lithium Battery:

  1. Connect the RJ45 communication cable between the inverter and battery. Please confirm that the lithium battery BMS port's PIN is correspond with the inverter BMS communication port. The inverter BMS port's PIN definition is as below:
Inverter BMS Port PIN Definition
Pin numberPort definitions
1RS485B
2RS485A
3NG
4NG
5NG
6NG
7RS485A
8RS485B

In order to communicate with the lithium battery BMS, you should press the "ENTER" button for a long time, and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.

CAUTION: When the battery type is set to "LIB-485", the setting items 12, 13 and 29 are displayed in percentage.

CAUTION: When the battery type is set to "LIB-485", the user cannot modify the maximum charging current. When communication fails, the inverter will cut off the output.

Diagram showing compatibility with various battery types: Flooded, Gel, Lithium-iron phosphate, Lithium-ion, AGM/Sealed, and User custom Battery.
Figure 9: Compatible Battery Types

4. Operation

4.1 Power ON/OFF

Once the unit has been properly installed and the batteries are connected well, simply press the On/Off switch (located on the button of the case) to turn on the unit.

4.2 Operation and Display Panel

The operation and display panel, shown below, is on the front panel of the inverter. It includes three indicators, four function keys, and an LCD display, indicating the operating status and input/output power information.

Image of the inverter's front panel showing the LCD display, LED indicators (INV/AC, CHG, FAULT), and function buttons (ESC, UP, DOWN, ENTER).
Figure 10: LCD Display and Function Buttons
LED Indicator Messages
LED IndicatorDescriptionMessages
INV/AC (Green)Solid On
Flashing
Output is powered by utility in Line mode.
Output is powered by battery or PV in battery mode.
CHG (Green)Solid On
Flashing
Battery is fully charged.
Battery is charging.
FAULT (Red)Solid On
Flashing
Fault occurs in the inverter.
Warning condition occurs in the inverter.
Function Keys
Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3 LCD Display Icons

The LCD display provides various icons to indicate the inverter's status and operational information.

LCD Display Icons and Their Meanings
IconFunction description
Indicates the AC input.
Indicates the PV input.
Indicates input voltage, input frequency, PV voltage, charger current (if PV in charging for 3.6KW models), charger power, battery voltage.
Indicates the setting programs.
Indicates the warning and fault codes.
Warning: flashing with warning code.
Fault: lighting with fault code.
Indicates output voltage, output frequency, load percent, load in VA, load in Watt and discharging current.
Indicates overload.
Indicates unit connects to the mains.
Indicates unit connects to the PV panel.
Indicates load is supplied by utility power.
Indicates the utility charger circuit is working.
Indicates the DC/AC inverter circuit is working.
Indicates unit alarm is disabled.

4.4 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN" button to select setting programs. And then, press "ENTER" button to confirm the selection or ESC button to exit.

The manual provides detailed tables for various settings, including Output source priority, Maximum charging current, AC input voltage range, Battery type, Auto restart conditions, Output frequency, Output voltage, Maximum utility charging current, Setting voltage point back to utility source, and Lithium battery protocol settings. Refer to pages 19-28 of the User Manual (PDF) for full details on these settings.

4.5 Display Setting

The LCD display information will be switched in turns by pressing the “UP” or “DOWN" key. The selectable information includes input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, load in Watt, DC discharging current, and main CPU Version. Refer to page 29 of the User Manual (PDF) for full details on display settings.

4.6 Operating Mode Description

The inverter supports various operating modes, including Standby mode, Line mode, and Grid-Tie operation. Each mode has specific behaviors regarding power output, battery charging, and grid interaction. Refer to pages 30-31 of the User Manual (PDF) for full details on operating modes.

4.7 Battery Equalization

Equalization function is added into the charge controller. It reverses the buildup of negative chemical effects like stratification and helps remove sulfate crystals that might have built up on the plates. It's recommended to equalize the battery periodically.

How to Apply Equalization Function:

  1. Enable battery equalization function in monitoring LCD setting program 30 first.
  2. Then, you may apply this function by either: setting equalization interval in program 35, or activating equalization immediately in program 36.

When to Equalize: In float stage, when the setting equalization interval (battery equalization cycle) is arrived, or equalization is active immediately, the controller will start to enter the Equalize stage.

Equalize charging time and timeout: In Equalize stage, the controller will supply power to charge the battery as much as possible until the battery voltage raises to the battery equalization voltage. Then, constant-voltage regulation is applied to maintain battery voltage at the battery equalization voltage. The battery will remain in the Equalize stage until the setting battery equalized time is arrived. If the battery equalized time expires and the battery voltage doesn't rise to the equalization point, the charge controller will extend the battery equalized time until the battery voltage achieves the equalization voltage. If the battery voltage is still lower than the equalization voltage when the battery equalized timeout setting is over, the charge controller will stop equalization and return to the float stage.

4.8 Mains and Lithium Battery Activation Function

  1. After 90s of mains power connection to the inverter, the machine is connected to the mains and starts to work.
  2. If the inverter is in lithium battery mode (item 05 is Llb or Llb-485), and the mains is connected but the battery is not connected, the mains activation function is automatically enabled.

5. Maintenance (Clearance and Maintenance for Anti-Dust Kit)

5.1 Overview

Every inverter is already installed with an anti-dust kit from the factory. The inverter will automatically detect this kit and activate an internal thermal sensor to adjust the internal temperature. This kit also keeps dust out of your inverter and increases product reliability in harsh environments.

5.2 Clearance and Maintenance

  1. Step 1: Loosen the screw in a counterclockwise direction on the top of the inverter.
  2. Step 2: Then, the dustproof case can be removed, and the air filter foam can be taken out.
  3. Step 3: Clean the air filter foam and dustproof case. After clearance, re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

6. Troubleshooting

6.1 Fault Reference Code

The inverter provides various fault codes and warning indicators to help diagnose issues. Refer to the tables below for common problems, their explanations, and recommended actions.

Fault Reference Code
Fault CodeFault EventWhat to do
01Fan is locked when inverter is off.Replace the fan.
02Over temperatureCheck whether the air flow of the unit is blocked or whether the ambient temperature is too high.
03Battery voltage is too highCheck if spec and quantity of batteries are meet requirements.
04Battery voltage is too low1. Re-charge battery.
2. Replace battery.
05Output short circuited or over temperature is detected by internal converter components.Check if wiring is connected well and remove abnormal load.
06/58Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)1. Reduce the connected load.
2. Return to repair center.
07Overload time outReduce the connected load by switching off some equipment.
08/09/53/57Internal components failed.Return to repair center.
51Over current or surge.Restart the unit, if the error happens again, please return to repair center.
52Bus voltage is too low.Restart the unit, if the error happens again, please return to repair center.
55Output voltage is unbalanced.Restart the unit, if the error happens again, please return to repair center.
59PV voltage is over limitationAdjust PV input to be within limits.

6.2 Warning Indicator

Warning Indicator Messages
Warning CodeWarning EventAudible Alarm
01Fan is locked when inverter is on.Beep three times every second
03Battery is over-chargedBeep once every second
04Low batteryBeep once every second
07OverloadBeep once every 0.5 second
10Output power deratingBeep twice every 3 seconds
15PV energy is low.Beep twice every 3 seconds
E9Battery equalizationNone
bPBattery is not connectedNone

7. Specifications

The SUMRY MPS VIII ECO series inverter comes in 3.6KW, 4.2KW, and 6.2KW models, offering robust performance for various solar power applications.

Product Data Sheet table showing detailed specifications for MPS VIII ECO 3.6KW, 4.2KW, and 6.2KW models, including PV input, Grid-Tie output, efficiency, two load output power, off-grid operation, AC input, battery charger, and hybrid operation.
Figure 11: Product Data Sheet

7.1 Line Mode Specifications

Table 1: Line Mode Specifications
INVERTER MODEL3.6KW4.2KW6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

7.2 Inverter Mode Specifications

Table 2: Inverter Mode Specifications
INVERTER MODEL3.6KW4.2KW6.2KW
Rated Output Power3.6KW4.2KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @load < 50%22.0Vdc44.0Vdc
Low DC Warning Voltage @load ≥ 50%21.0Vdc42.0Vdc
Low DC Warning Return Voltage @load < 50%22.5Vdc45.0Vdc
Low DC Warning Return Voltage @load ≥ 50%22.0Vdc44.0Vdc
Low DC Cut-off Voltage @load < 50%20.5Vdc41.0Vdc
Low DC Cut-off Voltage @load ≥ 50%20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption30W35W50W

7.3 Two Load Output Power

Table 3: Two Load Output Power
INVERTER MODEL3.6KW4.2KW6.2KW
Full Load3600W4200W6200W
Maximum Main Load3600W4200W6200W
Second Load Range720W~2520W840W~2940W1240W~4340W
Main Load Cut Off Voltage22VDC44VDC
Main Load Return Voltage26VDC52VDC

7.4 Charge Mode Specifications

Table 4: Charge Mode Specifications
INVERTER MODEL3.6KW4.2KW6.2KW
Utility Charging Mode
Charging Algorithm3-Step
AC Charging Current (Max)100Amp (@VI/P=230Vac)
Bulk Charging Voltage (Flooded Battery)29.258.4
Bulk Charging Voltage (AGM / Gel Battery)28.256.4
Floating Charging Voltage27Vdc54Vdc
MPPT Solar Charging Mode
Max. PV Array Power6200W6500W
Nominal PV Voltage240Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp120Amp120Amp

7.5 Grid-Tie Operation

Table 5: Grid-Tie Operation
INVERTER MODEL3.6KW4.2KW6.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current15.7A18.2A26.9A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)97%

7.6 General Specifications

Table 6: General Specifications
INVERTER MODEL3.6KW4.2KW6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm358×442×116
Net Weight, kg8.08.08.9

7.7 Approximate Back-up Time Table

The backup time depends on the quality, age, and type of battery. Specifications of batteries may vary depending on different manufacturers.

Table 7: Approximate Back-up Time (3.6KW/4.2KW Models)
Load (W)Backup Time @ 24Vdc 100Ah (min)Backup Time @ 24Vdc 200Ah (min)
3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
32002867
36002560
42002253
Table 8: Approximate Back-up Time (6.2KW Model)
Load (W)Backup Time @ 48Vdc 100Ah (min)Backup Time @ 48Vdc 200Ah (min)
5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680

8. Warranty and Support

All SUMRY products come with a 1-year warranty from the store. For any issues or support, please contact the seller or a qualified service center.

Image showing EU local warehouses, 1-year warranty, and 24-hour response time for support.
Figure 12: Warranty and Service Information

For detailed instructions and specifications, you can also refer to the official User Manual (PDF).

9. User Tips

No specific user tips were available from provided reviews or Q&A content. Always ensure proper ventilation around the inverter to prevent overheating and maintain optimal performance.