1. Introduction
The ZL-7835A is an intelligent automatic temperature and humidity controller designed for incubators and similar applications. It features PID control for precise temperature management, high-temperature power-off protection, and comprehensive humidity control. Its multi-functional design includes timed output and over-limit protection, making it suitable for various types of incubators, including pet incubators.
Video: Overview of the ZL-7835A Incubator Controller and its components.
2. Product Components
The ZL-7835A controller package typically includes the main control unit, a temperature sensor, a humidity sensor, and necessary wiring. Ensure all components are present and undamaged upon unboxing.

Image: ZL-7835A controller and included accessories.
3. Setup and Installation
3.1 Mounting the Controller
- Cut an opening in your control panel with dimensions of 71mm x 29mm.
- Insert the ZL-7835A controller into the prepared opening.
- Secure the controller using the provided mounting clips on the sides. Push the clips firmly until the controller is snug in place.

Image: ZL-7835A controller side view, illustrating the mounting clips.
3.2 Electrical Wiring
Safety Warning: Electrical wiring should only be performed by qualified personnel. Ensure power is disconnected before making any connections to prevent electric shock or damage to the device.
- Use appropriate wire gauges for all connections.
- Ensure all connections are secure and properly insulated.
- Avoid routing sensor wires alongside power lines to prevent interference.
- Place temperature and humidity sensors in locations that accurately represent the environment to be controlled.

Image: Electrical wiring diagram for the ZL-7835A controller. Connect power to terminals 6 (N) and 7 (L). Connect the temperature sensor to terminals 1 and 2. Connect the humidity sensor to terminals 4 and 5. R1 (Heating) connects to terminals 1 and 3. R2 (Fan) connects to terminals 4 and 5. R3 (Heater) connects to terminals 8 and 9.
Refer to the wiring diagram above for specific connections:
- Power Supply (100-240Vac): Connect to terminals 6 (Neutral, N) and 7 (Live, L).
- Temperature Sensor: Connect to terminals 1 and 2.
- Humidity Sensor: Connect to terminals 4 and 5.
- R1 Output (Heating, 2A 250Vac): Connect to terminals 1 and 3.
- R2 Output (Fan, 3A 250Vac): Connect to terminals 4 and 5.
- R3 Output (Heater, 5A 250Vac): Connect to terminals 8 and 9.
4. Operating Instructions
4.1 Display Indicators
The controller's display provides real-time information and status indicators:
| Icon/Indicator | Description |
|---|---|
| Heating Mode | Indicates active heating mode. |
| Heating Output | Indicates heating output is active. |
| Alarm Indication | Flashes when an alarm condition is met. |
| AT | PID auto-tuning in progress. |
| Parameter Setting | Indicates parameter setting mode. |
| Timed Output R2 | Indicates timed output R2 is active. |
| Et | NTC temperature sensor error. |
| Eh | Humidity sensor error. |
| tHi | High temperature alarm. |
| tLo | Low temperature alarm. |
| HHi | High humidity alarm. |
| HLo | Low humidity alarm. |
| At1-At4 | PID auto-tuning failure reasons. |
| Suc | PID auto-tuning successful. |
4.2 Key Operations
The controller has several buttons for navigation and setting adjustments:
- Setting Temperature/Humidity: Press the S key for 3 seconds. The display will flash. Use the Up and Down arrow keys to adjust the desired temperature or humidity. Press S again to confirm and save the setting.
- Accessing System Parameters: Press the S key for 3 seconds, then press the P key. Use the Up and Down arrow keys to navigate through parameters (U10-U99). Press S to select a parameter, adjust its value with Up/Down, and press S again to confirm.
4.3 Parameter Settings (U10-U99)
The ZL-7835A offers a wide range of configurable parameters to fine-tune its operation. Below is a summary of key parameters:
| Code | Function | Range | Description |
|---|---|---|---|
| U10 | Upper temperature limit | U11 ~ 99.9°C | Maximum settable temperature. |
| U11 | Lower temperature limit | -40.0 ~ U10°C | Minimum settable temperature. |
| U12 | Control mode | 0-1 | 0: PID control; 1: Hysteresis control. |
| U13 | Temperature hysteresis | 0.0 ~ 20.0°C | Temperature difference for switching outputs in hysteresis mode. |
| U14 | Temperature correction | -20.0 ~ 20.0°C | Adjusts the displayed temperature to match a reference. |
| U15 | Over-temperature protection upper limit | U15 ~ 0.1°C | Offset for upper temperature protection. |
| U20 | Humidity hysteresis | 0.1 ~ 20% | Humidity difference for switching outputs. |
| U22 | Humidity correction | -20.0 ~ 20.0% | Adjusts the displayed humidity to match a reference. |
| U40 | Timed R2 off time unit | 0-2 | 0: seconds; 1: minutes; 2: hours. |
| U41 | Timed R2 on time | 1-998 | Duration R2 output is ON. |
| U42 | Timed R2 off time | 1-998 | Duration R2 output is OFF. |
Note: This table is a partial list. Refer to the full manual for all parameter descriptions.
4.4 PID Auto-tuning (AT)
PID auto-tuning helps the controller achieve optimal temperature stability. It is recommended to perform auto-tuning in the actual operating environment with the load connected.
- Ensure the control mode (U12) is set to 0 (PID control).
- Set the desired temperature (SP).
- Press and hold the S key for 3 seconds, then press and hold the Up or Down arrow key for 5 seconds. The 'AT' indicator will appear, signifying that auto-tuning has started.
- The controller will cycle through heating and cooling to determine optimal PID parameters. This process can take some time (e.g., 180 minutes).
- Once auto-tuning is complete, the 'AT' indicator will disappear, and 'Suc' will be displayed, indicating successful tuning. The controller will then operate with the newly optimized parameters.
Important: Do not interrupt the auto-tuning process. If auto-tuning fails, an error code (At1-At4) will be displayed. In such cases, check the setup and retry.
5. Control Functions
5.1 Temperature Control
- PID Control (U12=0): Utilizes a PID algorithm for precise temperature regulation, with R3 acting as the primary heating output.
- Temperature Over-limit Protection (U46=2, 4, 6, 7): If the measured temperature exceeds the set temperature plus parameter U15, output R2 (fan) will activate. If the temperature drops below the set temperature plus parameter U16, R2 will deactivate after a 3-second delay.
- High Temperature Alarm (Secondary Protection): If the measured temperature exceeds the set temperature plus parameter U17, the power to the heater will be cut, the display will flash 'HH', and the buzzer will sound.
- Low Temperature Alarm: If the measured temperature falls below the set temperature minus parameter U18, the buzzer will sound.
5.2 Humidity Control
- Humidity Control: If the measured humidity exceeds the set humidity minus parameter U20, output R1 will activate. If the humidity drops below the set humidity minus parameter U20, R1 will deactivate.
- Humidity Over-limit Protection (U46=3, 5, 6, 7): If the measured humidity exceeds the set humidity plus parameter U23, output R2 will activate. If the humidity drops below the set humidity plus parameter U24, R2 will deactivate after a 3-second delay.
- High Humidity Alarm (Secondary Protection): If the measured humidity exceeds the set humidity plus parameter U25, the power to the humidifier will be cut, the display will flash 'HH', and the buzzer will sound.
- Low Humidity Alarm: If the measured humidity falls below the set humidity minus parameter U26, the buzzer will sound.
5.3 Timed Output R2
The R2 output can be configured for timed operation using parameters U41 (ON time) and U43 (OFF time), with the time unit set by U40.
6. Maintenance
- Cleaning: Regularly clean the controller's display and buttons with a soft, dry cloth. Do not use abrasive cleaners or solvents.
- Sensor Care: Keep the temperature and humidity sensors clean and free from debris. Avoid exposing them to direct water or extreme physical stress.
- Connection Check: Periodically inspect all wiring connections to ensure they are secure and free from corrosion.
- Calibration: If you suspect sensor inaccuracy, use the temperature (U14) and humidity (U22) correction parameters to adjust readings against a known accurate reference.
- Factory Reset: To restore all system parameters to their factory default values, press the S key for 3 seconds, then press the Down arrow key for 5 seconds. The display will show 'Suc' upon successful reset.
7. Troubleshooting
This section addresses common issues and alarm conditions you might encounter.
7.1 Alarm Indications
The controller will sound a buzzer and display specific codes for alarm conditions:
- Buzzer Alarm: The buzzer will sound for high/low temperature, high/low humidity, and sensor errors.
- System Recovery: If the system recovers from an alarm condition, the buzzer will stop.
- Manual Mute: Press any key to mute the buzzer during an alarm.
7.2 Common Issues and Solutions
| Problem/Error Code | Possible Cause | Solution |
|---|---|---|
| Et (NTC Sensor Error) | Temperature sensor open circuit, short circuit, or damage. | Check sensor connection. Replace sensor if damaged. |
| Eh (Humidity Sensor Error) | Humidity sensor open circuit, short circuit, or damage. | Check sensor connection. Replace sensor if damaged. |
| tHi / HHi | Temperature/Humidity exceeds high alarm limit. | Check heating/humidifying elements. Verify set points and alarm parameters (U17, U25). Ensure proper ventilation. |
| tLo / HLo | Temperature/Humidity falls below low alarm limit. | Check heating/humidifying elements. Verify set points and alarm parameters (U18, U26). |
| At1-At4 (PID Auto-tuning Failure) | PID auto-tuning failed due to unstable environment, incorrect wiring, or improper settings. | Ensure stable environment, correct wiring, and appropriate set points. Retry auto-tuning. |
| Controller not responding | No power, loose connections, or internal fault. | Check power supply. Verify all wiring. Contact support if issue persists. |
8. Specifications
| Feature | Specification |
|---|---|
| Power Supply | 100-240Vac, 50/60Hz |
| Temperature Sensor | NTC, R25=10K, B25/50=3470K |
| Humidity Sensor | 0-100%RH (no condensation) |
| Output R1 (Heating) | 5A, 250Vac (resistive load) |
| Output R2 (Fan) | 3A, 250Vac (resistive load) |
| Output R3 (Heater) | 5A, 250Vac (resistive load) |
| Working Environment | -10°C to 45°C, 5% to 85%RH |
| Protection Level | IP65 (front panel) |
| Panel Size | 78mm (L) x 34.5mm (W) |
| Opening Size | 71mm (L) x 29mm (W) |
9. User Tips
- Stable Environment: For best performance, ensure the controller is installed in a stable environment, away from direct sunlight, excessive vibrations, or extreme temperature fluctuations.
- Sensor Placement: Position the temperature and humidity sensors centrally within the incubator or controlled space to get the most accurate readings. Avoid placing them too close to heating elements or water sources.
- Regular Monitoring: Even with automatic control, it's good practice to periodically monitor the incubator's conditions and the controller's readings to ensure everything is operating as expected.
- Power Stability: Use a stable power source. Fluctuations can affect the controller's performance and the accuracy of its readings.
- Test Before Use: Before placing valuable contents in the incubator, run the controller for a full cycle to verify that it maintains the desired temperature and humidity accurately.
10. Warranty and Support
This product is manufactured to high-quality standards. For any technical assistance, warranty claims, or support inquiries, please contact your seller or the manufacturer directly. Keep your purchase receipt as proof of purchase.
For general inquiries, you may reach out via:
- Email: qh13332502386@163.com
- WhatsApp: +8613667399620