1. Introduction and Overview

This manual describes the assembly, installation, operation, and troubleshooting of the Sumry MPS VIII ECO Hybrid Solar Inverter. Please read this manual carefully before installation and operation, and keep it for future reference.

The Sumry MPS VIII ECO is a multi-function inverter/charger designed to provide uninterruptible power support. It combines the functions of an inverter, solar charger, and battery charger in a portable size. The comprehensive LCD display allows for user-configurable settings such as battery charging current, AC/solar charger priority, and acceptable input voltage ranges for various applications.

Key Features:

  • Pure sine wave output for reliable power.
  • Configurable input voltage range for home appliances and personal computers.
  • Adjustable battery charging current based on application needs.
  • Configurable AC/Solar Charger priority.
  • Compatible with both mains voltage and generator power.
  • Automatic restart when AC power is restored.
  • Comprehensive protection against overload, over-temperature, and short circuits.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.
  • Optional WIFI/GPRS communication for remote monitoring.
Sumry MPS VIII ECO Hybrid Solar Inverter with key features
Sumry MPS VIII ECO Hybrid Solar Inverter highlighting key specifications like 120A Max Solar Charging Current, 60-450VDC MPPT Voltage Range, 50Hz/60Hz Frequency Range, 1 Year Warranty, CE/ROHS/FC certifications, ability to work without battery, support for WIFI, and dual output for On/Off Grid Solar Inverter functionality.
Pure Sine Wave Inverter features
Features of the Pure Sine Wave Inverter, including running without battery, high PV input voltage range (60-500VDC), built-in 120A MPPT Solar charge (max 6200W for 3.6KW/4.2KW, max 6500W for 6.2KW), built-in 80A MPPT Solar charge (max 6500W for 3.6KW/48V), dual communication ports for Battery and Wifi, and dual output.

Basic System Architecture:

The inverter supports various power flow priorities, including 'Only Solar', 'Utility Priority', and 'Solar & Utility', allowing flexible energy management. It can operate with or without a battery, and supports dual communication ports for enhanced monitoring and control.

Basic System Architecture Diagram
Basic System Architecture diagram showing solar panels (PV Input), utility grid, generator, and lithium battery connected to the On/Off Grid Solar Inverter. The inverter provides 230VAC output to home appliances and can be monitored via an APP or computer. It illustrates day-time charging and night-time discharging.
Solar and Utility Priority Options
Diagram illustrating different power priority settings: 'Only Solar', 'Utility Priority', and 'Solar & Utility', along with selectable 'Solar Priority' and 'Utility Priority' modes.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  1. Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  2. CAUTION --To reduce risk of injury, charge only deep-cycle lead acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  3. Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  4. To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  5. CAUTION – Only qualified personnel can install this device with battery.
  6. NEVER charge a frozen battery.
  7. For optimum operation of this inverter/charger, please follow required spec to select appropriate cable size. It's very important to correctly operate this inverter/charger.
  8. Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  9. Please strictly follow installation procedure when you want to disconnect AC or DC terminals. Please refer to INSTALLATION section of this manual for the details.
  10. One piece of 150A fuse is provided as over-current protection for the battery supply.
  11. GROUNDING INSTRUCTIONS -This inverter/charger should be connected to a permanent grounded wiring system. Be sure to comply with local requirements and regulation to install this inverter.
  12. NEVER cause AC output and DC input short circuited. Do NOT connect to the mains when DC input short circuits.
  13. Warning!! Only qualified service persons are able to service this device. If errors still persist after following troubleshooting table, please send this inverter/charger back to local dealer or service center for maintenance.

3. Setup and Installation

3.1 Unpacking and Inspection

Before installation, carefully inspect the unit. Ensure that nothing inside the package is damaged. The package should contain the inverter unit and a user manual.

3.2 Preparation

Before connecting any wirings, remove the bottom cover by unscrewing the two screws.

3.3 Mounting the Unit

Consider the following points when selecting a mounting location:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display readability.
  • Allow a clearance of approximately 20 cm to the sides and 50 cm above and below for proper air circulation and heat dissipation.
  • Maintain an ambient temperature between 0°C and 55°C for optimal operation.
  • Mount vertically on the wall.
  • Ensure enough space for removing wires.

SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two M6 screws.

Inverter dimensions and communication ports
Inverter dimensions (420mm D x 310mm W x 110mm H) and rear panel showing communication ports (BMS RS485, WiFi RS232).

3.4 Battery Connection

CAUTION: For safety and compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Over-current protection is always required.

WARNING! All wiring must be performed by qualified personnel.

WARNING! Use appropriate cable for battery connection to reduce risk of injury.

ModelWire SizeCable (mm²)Torque value (max)
3.6KW/6.2KW1 x 2AWG252 Nm

Battery Connection Steps:

  1. Remove 18 mm of insulation sleeve from positive and negative conductors.
  2. Suggest using bootlace ferrules on the wire ends with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
  4. Insert battery wires into the inverter's battery connectors and tighten bolts to 2 Nm in a clockwise direction. Ensure correct polarity (+ to + and - to -). Recommended tool: #2 Pozi Screwdriver.
Battery Connection Diagram
Diagram illustrating how to connect multiple 12V battery packs in series to the Inverter (e.g., 6.2KW and 4.2KW models).

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION!! Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

3.5 AC Input/Output Connection

CAUTION!! Before connecting to AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures the inverter can be securely disconnected during maintenance and is fully protected from over-current.

  • Recommended AC breaker spec: 32A for 3.6KW and 50A for 6.2KW.
  • There are two terminal blocks marked “IN” and “OUT”. Do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel.

WARNING! Use appropriate cable for AC input connection for system safety and efficient operation.

Suggested Cable Requirement for AC Wires:

ModelGaugeCable (mm²)Torque Value
3.6KW12 AWG41.2 Nm
6.2KW10 AWG61.2 Nm

AC Input/Output Connection Steps:

  1. Before making AC input/output connection, open the DC protector or disconnector.
  2. Remove 10mm of insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities (L→LINE (brown or black), N→Neutral (blue)) indicated on the terminal block and tighten the terminal screws.

WARNING: Ensure the AC power source is disconnected before attempting to hardwire it to the unit.

  1. Insert AC output wires according to polarities (L→LINE (brown or black), N→Neutral (blue)) indicated on the terminal block and tighten the terminal screws.
  2. Ensure all wires are securely connected.
AC Input/Output Connection Diagram
Diagram showing the steps for AC input and output wiring, including stripping insulation, inserting wires into terminal blocks, and tightening screws.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart. If power shortages occur and recover quickly, it can damage connected appliances. Check if your air conditioner has a time-delay function. Otherwise, the inverter may trigger an overload fault to protect the appliance, but internal damage to the air conditioner may still occur.

3.6 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING! Use appropriate cable for PV module connection for system safety and efficient operation.

ModelWire SizeCable (mm²)Torque Value (max)
3.6KW/6.2KW1 x 12AWG41.2 Nm

PV Module Selection:

When selecting PV modules, consider the following:

  • Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
  • Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
INVERTER MODEL3.6KW6.2KW
Max. PV Array Open Circuit Voltage500Vdc
PV Array MPPT Voltage Range60Vdc~450Vdc

PV Module Connection Steps:

  1. Remove 10 mm of insulation sleeve from positive and negative conductors.
  2. Suggest using bootlace ferrules on the wire ends with a proper crimping tool.
  3. Check correct polarity of wire connection from PV modules and PV input connectors. Connect positive pole (+) to positive pole (+) and negative pole (-) to negative pole (-). Recommended tool: 4mm blade screwdriver.
PV Module Connection Diagram
Diagram showing the steps for PV module wiring, including stripping insulation, inserting wires into terminal blocks, and tightening screws.

3.7 Final Assembly

After connecting all wirings, replace the bottom cover by screwing the two screws back in.

3.8 Communication Connection

The inverter supports optional Wi-Fi and GPRS cloud communication for monitoring.

Wi-Fi Cloud Communication (Optional):

Use the supplied communication cable to connect the inverter to the Wi-Fi module. Download the APP from the APP store and refer to the "Wi-Fi Plug Quick Installation Guideline" for network setup and registration. The inverter status can then be viewed via the mobile phone APP or a computer webpage.

GPRS Cloud Communication (Optional):

Use the supplied communication cable to connect the inverter to the GPRS module, and then apply external power to the GPRS module. Download the APP from the APP store and refer to the "GPRS RTU Quick Installation Guideline" for network setup and registration. The inverter status can then be viewed via the mobile phone APP or a computer webpage.

Communication Ports on Inverter
Close-up view of the inverter's communication ports, including BMS RS485 and WiFi RS232 ports.
Monitoring via SmartESS App
Image showing the inverter connected to an optional monitoring device, allowing control and monitoring via the SmartESS App on a smartphone.

4. Operation

4.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, simply press the On/Off switch (located on the side of the case) to turn on the unit.

4.2 Operation and Display Panel

The operation and display panel is on the front of the inverter. It includes three indicators, four function keys, and an LCD display to show operating status and input/output power information.

LCD Display and Function Buttons
Detailed view of the inverter's LCD display and function buttons. It also shows LED indicators for INV/AC, CHG, and FAULT, along with their messages (Solid On, Flashing, Red).

LED Indicator Messages:

LED IndicatorColorMessages
INV/ACGreenSolid On: Output is powered by utility in Line mode.
Flashing: Output is powered by battery or PV in battery mode.
CHGGreenSolid On: Battery is fully charged.
Flashing: Battery is charging.
FAULTRedSolid On: Fault occurs in the inverter.
Flashing: Warning condition occurs in the inverter.

Function Keys:

Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4.3 LCD Setting

After pressing and holding the ENTER button for 3 seconds, the unit will enter setting mode. Use the UP or DOWN buttons to select setting programs, and ENTER to confirm or ESC to exit.

The manual provides detailed tables for various settings, including output source priority, maximum charging current, AC input voltage range, battery type, auto restart functions, output frequency, output voltage, and more. Refer to the full PDF manual for detailed LCD setting options (pages 14-20).

4.4 Display Setting

The LCD display information can be switched by pressing the UP or DOWN keys. Selectable information includes input voltage, input frequency, PV voltage, charging current, charging power, battery voltage, output voltage, output frequency, load percentage, load in Watt, load in VA, DC discharging current, and main CPU Version. Refer to the full PDF manual for detailed display information (pages 21-24).

4.5 Operating Mode Description

The inverter operates in various modes, including Standby, Line mode, and Grid-Tie Operation. The LCD display provides specific information for each mode, indicating power flow and system status. Refer to the full PDF manual for detailed operating mode descriptions (pages 25-26).

4.6 Battery Equalization Description

The charge controller includes a battery equalization function to reverse negative chemical effects like stratification and remove sulfate crystals, which can reduce battery capacity. It is recommended to equalize batteries periodically.

How to Apply Equalization Function:

  1. Enable the battery equalization function in LCD setting program 30.
  2. Apply by setting the equalization interval in program 35 or activating equalization immediately in program 36.

When to Equalize:

In float stage, when the set equalization interval is reached or equalization is actively initiated, the controller will enter the Equalize stage. The controller will charge the battery until it reaches the equalization voltage and maintains it. If the battery voltage is still lower than the equalization voltage when the timeout is over, the equalization will stop, and the system will return to float stage.

4.7 Fault Reference Code and Warning Indicator

The inverter provides fault codes and warning indicators on the LCD display to help diagnose issues. Refer to the Troubleshooting section for a detailed table of codes and their meanings.

Comprehensive Protections
Icons representing comprehensive protections: Overload Protection, Overheating Protection, High Low Voltage Protection, Battery Protection, Short Circuit Protection, Overcurrent Protection, Anti Reverse Protection, and Power Failure Protection.

5. Maintenance

5.1 Anti-Dust Kit Clearance and Maintenance

Every inverter comes with a factory-installed anti-dust kit. This kit helps keep dust out of the inverter and enhances product reliability in harsh environments. The inverter automatically detects this kit and adjusts its internal thermal sensor to regulate temperature.

Maintenance Steps:

  1. Loosen the screws on the top of the inverter in a counterclockwise direction.
  2. Remove the dustproof case and take out the air filter foam.
  3. Clean the air filter foam and dustproof case. After cleaning, re-assemble the dust-kit back into the inverter.

NOTICE: The anti-dust kit should be cleaned from dust every one month.

Anti-Dust Kit Removal Steps
Diagram illustrating the steps to remove the anti-dust kit: unscrewing the top screws, lifting the dustproof case, and accessing the air filter foam.

6. Troubleshooting

This section provides a guide to common problems and their solutions. If errors persist after following these steps, contact your local dealer or service center.

ProblemLCD/LED/BuzzerExplanation / Possible causeWhat to do
Unit shuts down automatically during startup process.LCD/LEDs and buzzer active for 3 seconds then off.The battery voltage is too low (<1.91V/Cell)1. Re-charge battery.
2. Replace battery.
No response after power on.No indication.1. The battery voltage is far too low. (<1.4V/Cell)
2. Internal fuse tripped.
1. Contact repair center for replacing the fuse.
2. Re-charge battery.
3. Replace battery.
Input voltage is displayed as 0 on the LCD and green LED is flashing.Input protector is trippedCheck if AC breaker is tripped and AC wiring is connected well.
Mains exist but the unit works in battery mode.Green LED is flashing.Insufficient quality of AC power. (Shore or Generator)1. Check if AC wires are too thin and/or too long.
2. Check if generator (if applied) is working well or if input voltage range setting is correct. (UPS Appliance)
Green LED is flashing.Set "Solar First" as the priority of output source.Change output source priority to Utility first.
When the unit is turned on, internal relay is switched on and off repeatedly.LCD display and LEDs are flashingBattery is disconnected.Check if battery wires are connected well.
Fault code 07Overload error. The inverter is overload 110% and time is up.Reduce the connected load by switching off some equipment.
Fault code 05Output short circuited.Check if wiring is connected well and remove abnormal load.
Temperature of internal converter component is over 120°C.Check whether the air flow of the unit is blocked or whether the ambient temperature is too high.
Fault code 02Internal temperature of inverter component is over 100°C.Return to repair center.
Buzzer beeps continuously and red LED is on.Fault code 03Battery is over-charged.
The battery voltage is too high.
Check if spec and quantity of batteries are meet requirements.
Fault code 01Fan faultReplace the fan.
Fault code 06/58Output abnormal (Inverter voltage below than 190Vac or is higher than 260Vac)1. Reduce the connected load.
2. Return to repair center.
Fault code 08/09/53/57Internal components failed.Return to repair center.
Fault code 51Over current or surge.Restart the unit, if the error happens again, please return to repair center.
Fault code 52Bus voltage is too low.
Fault code 55Output voltage is unbalanced.

Warning Indicator:

Warning CodeWarning EventAudible AlarmIcon flashing
01Fan is locked when inverter is on.Beep three times every second01
03Battery is over-chargedBeep once every second03
04Low batteryBeep once every second04
07OverloadBeep once every 0.5 second07
10Output power deratingBeep twice every 3 seconds10
15PV energy is low.Beep twice every 3 seconds15
E9Battery equalizationNoneE9
6PBattery is not connectedNone6P

7. Specifications

The following tables provide detailed specifications for the Sumry MPS VIII ECO Hybrid Solar Inverter.

Product Data Sheet
Comprehensive Product Data Sheet for MPS VIII ECO 3.6KW and 6.2KW models, detailing PV input, Grid Output (AC), AC Input, General, and Interface specifications.

7.1 Line Mode Specifications

INVERTER MODEL3.6KW6.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage100Vac
Low Loss Voltage90Vac±5V (UPS); 90Vac±5V (Appliances)
Low Loss Return Voltage95Vac±5V (UPS); 95Vac±5V (Appliances)
High Loss Voltage145Vac±5V
High Loss Return Voltage140Vac±5V
Max AC Input Voltage150Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time10ms typical (UPS); 20ms typical (Appliances)

7.2 Inverter Mode Specifications

INVERTER MODEL3.6KW6.2KW
Rated Output Power3.6KW6.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation100/105/110/115/120Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150%; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage24Vdc48Vdc
Cold Start Voltage23.0Vdc46.0Vdc
Low DC Warning Voltage @load < 50%22.0Vdc44.0Vdc
Low DC Warning Voltage @load ≥ 50%21.0Vdc42.0Vdc
Low DC Warning Return Voltage @load < 50%22.5Vdc45.0Vdc
Low DC Warning Return Voltage @load ≥ 50%22.0Vdc44.0Vdc
Low DC Cut-off Voltage @load < 50%20.5Vdc41.0Vdc
Low DC Cut-off Voltage @load ≥ 50%20.0Vdc40.0Vdc
High DC Recovery Voltage32Vdc62Vdc
High DC Cut-off Voltage33Vdc63Vdc
No Load Power Consumption45W50W

7.3 Two Load Output Power

INVERTER MODEL3.6KW6.2KW
Full Load3600W6200W
Maximum Main Load3600W6200W
Maximum Second Load (battery model)1200W2066W
Main Load Cut Off Voltage26VDC52VDC
Main Load Return Voltage27VDC54VDC

7.4 Charge Mode Specifications

INVERTER MODEL3.6KW6.2KW
Charging Algorithm3-Step
AC Charging Current (Max)80Amp (@VI/P=100 Vac)
Bulk Charging Flooded Battery Voltage29.258.4
AGM / Gel Battery28.256.4
Floating Charging Voltage27Vdc / 54Vdc

7.5 MPPT Solar Charging Mode

INVERTER MODEL3.6KW6.2KW
Max. PV Array Power4200W6500W
Nominal PV Voltage240Vdc360Vdc
PV Array MPPT Voltage Range60Vdc~500Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)120Amp120Amp

7.6 Grid-Tie Operation

INVERTER MODEL3.6KW6.2KW
Nominal Output Voltage100/105/110/115/120VAC
Feed-in Grid Voltage Range90~150VAC
Feed-in Grid Frequency Range49~51±1Hz/59~61±1Hz
Nominal Output Current30A51.7A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)97%

7.7 General Specifications

INVERTER MODEL3.6KW6.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage temperature-15°C~ 60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm420*310*110420*310*110
Net Weight, kg910

7.8 Approximate Back-up Time Table

The following tables provide approximate backup times for different loads and battery configurations.

3.6KW Model:

Load (W)Backup Time @ 24Vdc 100Ah (min)Backup Time @ 24Vdc 200Ah (min)
3004491100
600222525
900124303
120095227
150068164
180056126
210048108
24003594
27003174
32002867
36002560
42002253

6.2KW Model:

Load (W)Backup Time @ 48Vdc 100Ah (min)Backup Time @ 48Vdc 200Ah (min)
5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680

Note: Backup time depends on the quality, age, and type of battery. Battery specifications may vary.

8. User Tips

  • Optimal Placement: Ensure the inverter is installed in a well-ventilated area, away from direct sunlight and moisture, to prevent overheating and ensure longevity.
  • Battery Compatibility: Always use compatible deep-cycle rechargeable batteries (Flooded, Gel, Lithium-iron phosphate, Lithium-ion, AGM/Sealed, or user-customized) as specified in the manual to avoid damage and ensure safe operation.
  • Regular Checks: Periodically check all wiring connections for tightness and signs of wear. Loose connections can lead to power loss or safety hazards.
  • Monitor Performance: Utilize the optional Wi-Fi or GPRS module to remotely monitor your inverter's performance and battery status via the SmartESS App or a web interface. This allows for proactive management and early detection of potential issues.
  • Load Management: Be mindful of the total load connected to the inverter. Avoid exceeding the rated output power to prevent overload faults and ensure stable operation.
  • Anti-Dust Kit Cleaning: Clean the anti-dust kit monthly to maintain optimal airflow and prevent dust buildup, which can affect the inverter's efficiency and lifespan.
Compatible Battery Types
Diagram showing the inverter's compatibility with multiple battery types: Flooded, Gel, Lithium-iron phosphate, Lithium-ion, AGM/Sealed, and User custom Battery.

9. Warranty and Support

The Sumry MPS VIII ECO Hybrid Solar Inverter comes with a 1-year warranty from the seller. For any service or repair needs, please contact your local dealer or service center.