1. Introduction
The UT271 series of Clamp Earth Resistance Tester represents a major breakthrough in traditional grounding resistance measurement. It is widely used in the grounding resistance measurement of power, telecommunications, meteorology, oilfield, construction, and industrial and electrical equipment.
When measuring a grounding system with a loop, the UT271 series Clamp Grounding Resistance Tester eliminates the need to disconnect the grounding down lead and does not require auxiliary grounding electrodes. This makes it safe, fast, and simple to use.
The UT271 series clamp grounding resistance meter can measure ground faults that cannot be measured by traditional methods. It measures the combined value of grounding body resistance and grounding lead resistance. Additionally, the B/C type Clamp Grounding Resistance Tester models are capable of measuring leakage current and neutral current in the grounding system.

2. Safety Information
Always observe standard safety precautions when working with electrical equipment. This device is designed for electrical measurements and holds CE certification, indicating compliance with European safety standards.
- Ensure the device is in good working condition before use.
- Do not attempt to measure live circuits beyond the specified voltage limits.
- Wear appropriate personal protective equipment (PPE) such as insulated gloves when necessary.
- Avoid using the device in wet or damp conditions unless specifically rated for such environments.
- Refer to the 'Specifications' section for detailed safety ratings and environmental conditions.
3. Product Overview
The UNI-T UT271 series clamp earth resistance tester is a handheld device designed for efficient and accurate measurement of earth resistance and, for B/C models, AC current. Key features include a large LCD for clear readings, data storage capabilities, and a robust clamp jaw.
3.1 Meter Structure
The meter consists of the following main components:
- Clamp: Φ32mm jaw size for clamping around conductors.
- POWER Key: Used for booting up, shutting down, and quitting operations.
- HOLD Key: Locks or releases the displayed data.
- Trigger: Controls the opening and closing of the clamp.
- Liquid Crystal Display (LCD): Displays measurement readings and symbols.

3.2 Product Variants
- UT271A: Measures earth resistance from 0.01 to 300Ω.
- UT271B: Measures earth resistance from 0.01 to 500Ω and AC current up to 20A.
- UT271C: Measures earth resistance from 0.01 to 1000Ω and AC current up to 20A.



4. Specifications
4.1 General Specifications
| Attribute | Value |
|---|---|
| Dimensions | 260mm × 105mm × 60mm |
| Display Type | Digital Only |
| Power | DC 6V alkaline dry battery (LR6 1.5V × 4PCS) |
| Weight | About 818g (including battery) |
| Working Environment & Humidity | -10°C ~ 40°C; below 80%RH |
| Storage Environment & Humidity | -20°C ~ 60°C; below 70%RH |
| Insulation Resistance | Above 20MΩ (Between circuit and outside shell is 500V) |
| Withstand Voltage | AC 3700V/rms. (Between circuit and outside shell) |
| External Magnetic Electric Field | <40A/m; <1V/m |
| Protection Type | IEC61010-1 (CAT III 300V, CAT IV 150V, Pollution 2); IEC61010-031; IEC61557-1 (Earth resistance) |
| Measurement Time | 1 time/second |
| Data Storage | 500 groups. The flashing "MEM" symbol indicates that the store is full. |
| Overflow Display | Exceed measurement range overflow function: "OL" symbol display |
| Interference Test | Automatically identify interference signals, and indicate with the "NOISE" symbol when the interference current is large |
| Battery Voltage | Low battery voltage symbol reminder |
| Power Consumption | Max about 60mA |
4.2 Measurement Ranges & Accuracy
| Mode | Range | Resolution | Accuracy |
|---|---|---|---|
| Resistance Range | 0.010Ω~0.099Ω | 0.001Ω | ± (1%rdg + 0.01Ω) |
| 0.10Ω~0.99Ω | 0.01Ω | ± (1%rdg + 0.01Ω) | |
| 1.0Ω~49.9Ω | 0.1Ω | ± (1%rdg + 0.1Ω) | |
| 50.0Ω~99.5Ω | 0.5Ω | ± (1.5%rdg + 0.5Ω) | |
| 100Ω~199Ω | 1Ω | ± (2%rdg + 1Ω) | |
| 200Ω~395Ω | 5Ω | ± (5%rdg + 5Ω) | |
| 400Ω~590Ω | 10Ω | ± (10%rdg + 10Ω) | |
| 600Ω~1000Ω | 20Ω | ± (20%rdg + 20Ω) | |
| Current Range* | 0.00mA~9.99mA | 0.01mA | ± (2.5%rdg + 5mA) |
| 10.0mA~99.9mA | 0.1mA | ± (2.5%rdg + 10mA) | |
| 100mA~299mA | 1mA | ± (2.5%rdg + 10mA) | |
| 0.30A~2.99A | 0.01A | ± (2.5%rdg + 0.1A) | |
| 3.0A~9.9A | 0.1A | ± (2.5%rdg + 0.3A) | |
| 10.0A~20A | 0.1A | ± (2.5%rdg + 0.5A) |
*Note: Current Range measurement is limited to UT271B and UT271C models.
5. Setup
5.1 Unpacking and Initial Inspection
Upon receiving your UNI-T Clamp Earth Resistance Tester, carefully unpack all components and inspect for any signs of damage. The package should include:
- Main unit (Clamp Earth Resistance Tester)
- 1Ω test ring
- 10Ω test ring
- 4x 1.5V AA batteries
- Carrying bag
- User manual
- Warranty card/Certificate

5.2 Battery Installation
The device requires 4x 1.5V AA alkaline dry batteries. To install:
- Locate the battery compartment on the back of the meter.
- Open the battery compartment cover.
- Insert the four AA batteries, ensuring correct polarity (+/-).
- Close the battery compartment cover securely.
6. Operating Instructions
6.1 Function Quick Checking
The following table summarizes quick access functions:
| Function | Key |
|---|---|
| Boot Up / Shutdown / Shutdown Delay/Exit | POWER |
| Test interface, lock storage/Release lock | HOLD key short press |
| View interface, data reading | HOLD key short press |
| Delete data selection interface, NO and YES option switch | HOLD key long press |
| Test interface, enter the review interface | HOLD key long press |
| Delete selection interface, NO isn't delete, YES is delete | HOLD key long press |
6.2 Start Up
Press the POWER key to start the instrument. It will automatically test the LCD, displaying all symbols (Figure 1). Meanwhile, the instrument auto-calibrates, and after startup, it displays "OL Ω" and "0.00mA", then automatically enters the Resistance + Current measurement mode (Figure 2).
If an abnormal boot and self-calibration occur, the instrument will display the "Er" symbol, indicating a boot error (Figure 3).
Important: Before booting up, the trigger should be withheld one or two times to ensure the jaws are well closed. In booting, be sure to keep the natural static state of the Meter; do not overturn the Meter, nor impose any external force on the clamp. Otherwise, the accuracy of measurement cannot be guaranteed.

6.3 Resistance Measurement
After booting up and auto-inspection, the display will show "OL Ω" and be ready to proceed with resistance measurement. At this point, press the trigger and open the jaws, clamp the measured loop, read, and get the resistance value.
If the user thinks it is necessary, the test can be done with the test ring as shown in the figure. It shows a value that should be consistent with the nominal value on the test ring.
Nominal value of test ring is in condition of temperature of 20 °C. It is normal to find the difference of numerical 1 word between the shown value and the nominal value.
For instance: If the nominal value of the test ring is 1.0Ω, showing 0.9 Ω or 1.1 Ω is normal and accepted.
Display "OL Ω" indicates that the measured resistance value exceeded the upper limit range of the meter.
Display "OL A" indicates that the measured current exceeded the upper limit range of the meter.
Display "L0.01Ω" indicates that the measured resistance value exceeded the lower limit range of the meter.

6.4 Data Lock/Release/Storage
In test mode, press the HOLD key to lock the present display value and display the HOLD symbol. This lock value is automatically numbered and stored as a set of data. Then press the HOLD key to release the locking, the HOLD symbol will disappear, and the meter will return to measurement state. By repeating the above operations, it can store 500 sets of data. If the memory is full, the MEM symbol will flash display.
As indicated in Figure 5, lock the measured resistance 5.8Ω, lock the measured current 188mA, and save it as data unit No.001.
As indicated in Figure 6, lock the measured resistance 1.8Ω, and save it as data unit No.500.
If the storage is full, the MEM symbol flashes. After turning off and then on, the stored data will not be lost.

6.5 Data Review / Clear
Long press the HOLD key to enter the stored data review mode. If there is no stored data, it will be displayed as Figure 7. When there is stored data, the default display is the 001st group of stored data, as Figure 8.
Short press the HOLD key and step down 1 to review the stored data.
In the data review mode, long press the HOLD key to enter the data deletion selection interface, and press the HOLD key to select "no" or "YES". Display "no", long press the HOLD key again to return to the data test interface, and display "YES". Long press the HOLD key again to clear all stored data. After the data is cleared, return to the data test interface. And the data cannot be restored after it is cleared.
6.6 Shutdown
After the meter is switched on, press the POWER key to shut it down.
After the meter starts up for 5 minutes, the LCD screen enters a flashing state, and would automatically shut down after the flashing state is sustained for 30 seconds to reduce battery consumption. Press the POWER key in the flashing state to delay the shutdown and keep it working. In HOLD state, it is required to first press the HOLD key or Power key to quit from the HOLD state, then press the POWER key to shut it down.
7. Display Examples and Symbols
7.1 LCD Screen
The LCD screen provides various indicators and symbols to inform the user about the meter's status and measurements:
- Low battery symbol
- Number of data storage
- AC symbol
- Clamp opening symbol
- 4-digit current indication
- Current unit symbols
- Interference symbol
- 4-digit resistance data
- Resistance unit symbol
- Data lock symbol
- Data lookup symbol
- Data storage symbols

7.2 Special Symbols Description
- Clamp opening symbol: The clamp is in the open state, and cannot measure. This symbol may appear if the trigger is artificially pressed, or if the clamps have been seriously polluted, and can no longer continue to measure.
- "Er" (Error) symbol: The boot-up error symbol, which may appear when booting or the clamp opening.
- Low battery voltage symbol: When the battery voltage is lower than 4.8V, the symbol shows. At this time, it cannot guarantee the accuracy of the measurements. Batteries should be replaced.
- "OL Ω" symbol: Indicates that the measured resistance has exceeded the upper limit range of the meter.
- "L0.01Ω" symbol: Indicates that the measured resistance has exceeded the lower limit range of the meter.
- "OL A" symbol: Indicates that the measured current has exceeded the upper limit range of the meter.
- Alarm symbol: When the alarm function is turned on, the symbol is displayed. When the measured value is greater than the critical value of the alarm setting, the symbol flashes, and the meter makes an intermittent "beep-beep-beep---" sound.
- MEM (Full data storage) symbol: Memory is full of data units of 99, and cannot continue to store data.
- MR (Data access) symbol: Data access display, and display the number of the saved data at the same time.
- NOISE symbol: When the earth circuit tested has a large interference current, this symbol flashes, and the meter gives a warning sound of "bee-bee-bee-bee-". The accuracy of the test cannot be guaranteed at this time.
7.3 Display Examples

8. Maintenance
8.1 Cleaning
To maintain the accuracy and longevity of your meter, keep it clean. Wipe the exterior with a soft, dry cloth. Do not use abrasive cleaners or solvents. Ensure the clamp jaws are free from dirt and debris, as this can affect measurement accuracy.
8.2 Battery Replacement
When the low battery symbol appears on the LCD, replace the batteries promptly to ensure accurate measurements. Refer to section 5.2 for battery installation instructions.
8.3 Storage
When not in use for extended periods, store the meter in its carrying bag in a dry environment, away from direct sunlight and extreme temperatures. The recommended storage environment is -20°C to 60°C with humidity below 70% RH.
9. Troubleshooting
This section provides solutions to common issues you might encounter:
- "Er" (Boot Error) Display: This indicates a boot-up error. Ensure the clamp jaws are clean and fully closed before powering on. If the problem persists, the jaw surface might be dirty or there could be a mechanical issue. Check for any obstructions or damage to the clamp.
- "OL Ω" or "L0.01Ω" Display: These symbols indicate that the measured resistance is outside the meter's measurable range (either too high or too low). Verify that the circuit being tested falls within the specified resistance range for your model (e.g., UT271A: 0.01-300Ω, UT271C: 0.01-1000Ω).
- "OL A" Display: This indicates that the measured current has exceeded the upper limit range of the meter. Ensure the current in the circuit is within the meter's specified current range (up to 20A for UT271B/C).
- "NOISE" Symbol Flashing: This indicates significant interference current in the earth circuit being tested, which can affect measurement accuracy. Try to minimize external electrical noise sources or re-test in a different environment if possible.
- Low Battery Symbol: Replace the batteries immediately. Continued use with low battery voltage may lead to inaccurate readings.
- Inaccurate Readings: Ensure the clamp jaws are clean and fully closed. Perform a self-check using the provided 1Ω and 10Ω test rings to verify the meter's calibration. Environmental factors like temperature and humidity can also affect accuracy; ensure operation within specified conditions.
10. User Tips
To get the most out of your UNI-T Clamp Earth Resistance Tester, consider the following tips:
- Regular Self-Check: Utilize the included 1Ω and 10Ω test rings to periodically verify the meter's accuracy. This helps ensure reliable measurements, especially before critical tasks.
- Understand Measurement Methods: The UT271 series supports various grounding system measurements, including 2-point, 3-point, and multi-point methods. Familiarize yourself with these techniques for different applications.
- Applications: This meter is versatile and can be used for a wide range of applications, such as measuring earth resistance for iron towers, charging stations, and transmission poles, as well as measuring AC current in distribution boxes and leakage current in circuit breakers.
- Data Storage: Make use of the 500-group data storage feature to record and review measurements over time. This is particularly useful for monitoring trends or documenting compliance.
- Environmental Awareness: Be mindful of environmental conditions. High interference can affect readings, indicated by the "NOISE" symbol.
11. Warranty and Support
The UNI-T Clamp Earth Resistance Tester comes with a 12-month warranty from the date of purchase, covering manufacturing defects and malfunctions under normal use. Please retain your proof of purchase for warranty claims.
For technical support, troubleshooting assistance, or warranty inquiries, please contact your retailer or the official UNI-T customer service. Refer to the product packaging or official UNI-T website for contact details.