1. Introduction
The EARU EAPDX-3P series is a sophisticated three-phase adjustable voltage and current protector designed to provide comprehensive protection for electrical systems. This device monitors voltage, current, and phase sequence, automatically disconnecting the load in the event of abnormal conditions such as overvoltage, undervoltage, overcurrent, three-phase voltage imbalance, or incorrect phase sequence. It features an automatic reset function to restore power once conditions return to normal, ensuring continuous operation and safeguarding connected equipment. This manual provides detailed instructions for installation, operation, and maintenance of the EAPDX-3P protector.

2. Product Features
The EAPDX-3P protector offers a comprehensive set of features for robust electrical system protection:
- Overvoltage Protection: Safeguards equipment from excessive voltage levels.
- Undervoltage Protection: Prevents damage due to insufficient voltage.
- Overcurrent Protection: Protects against excessive current draw.
- Three-Phase Voltage Imbalance Protection: Detects and protects against imbalances between phases.
- Phase Sequence Protection: Ensures correct phase rotation for sensitive equipment.
- Voltage and Current Manual Error Correction: Allows for precise calibration of displayed values.
- Power-on Delay: Configurable delay before power restoration to protect equipment during startup.
- Protection Trip Delay: Adjustable delay before tripping, preventing nuisance trips from momentary fluctuations.
- Recovery Delay: Configurable delay before automatic reset after a fault, allowing the system to stabilize.
- Automatic Reset Function: Automatically restores power after fault conditions clear.
- Real-time Display: Provides live voltage and current readings for each phase.
- Adjustable Parameters: All protection thresholds and delays are user-configurable.
- Durable Design: Engineered for heat and cold resistance, suitable for various environments.



3. Specifications
| Property | Value |
|---|---|
| Type | Mini |
| Model Number | EAPDX-3P |
| Brand Name | EARU |
| Is Smart Device | No |
| Rated Supply Voltage | AC 3*220V (N-L1/L2/L3) |
| Rated Frequency | 50/60Hz |
| Over Current Protection Setting Range | 1-63A/100A (Default 30A) |
| Continuous Over Current Protection Times | 0-20 Times (Default OFF) |
| Over Voltage Protection Setting Range | 230-300V (Default 270V) |
| Over Voltage Protection Recover Setting Range | 225-295V (Default 265V) |
| Under Voltage Protection Setting Range | 140-210V (Default 170V) |
| Under Voltage Protection Recover Setting Range | 145-215V (Default 175V) |
| Voltage & Current Protection Recover Delay | 1-500s (Default 30s) |
| Voltage & Current Protection Trip Delay | 0.1-30s (Default 1.0s) |
| Voltage & Current Manual Error Calibration Range | -9.5-9.5% (Default 0%) |
| Three Phase Voltage Imbalance Protection Setting Range | 20-99V (Default 20V) |
| Three Phase Voltage Imbalance Protection Recover Setting Range | 5-94V (Default 20V) |
| Phase Sequence Protection | ON/OFF (Default ON) |
| Power On Delay | 1-500s (Default 10s) |
| Voltage Hysteresis | 5V |
| Voltage Accuracy | <1% |
| Max. operating Phase Voltage | 350V |
| Pollution Degree | 3 |
| Altitude | ≤2000m |
| Ambient Temperature | -25°C ~ +50°C |
| Permissible Relative Humidity | ≤50% at 40°C |
| Storage Temperature | -25°C ~ +55°C |
| Self-consumption Power | ≤2W |
| Electrical and Mechanical Life | >100,000 cycles |
| Origin | Mainland China |
| Certification | CE |

4. Setup and Installation
The EAPDX-3P protector is designed for DIN rail mounting. Ensure all connections are made by a qualified electrician following local electrical codes and safety regulations.
4.1 Wiring Diagram
Connect the incoming three-phase power supply (N, L1, L2, L3) to the 'IN' terminals and the protected load to the 'OUT' terminals. Refer to the diagram below for correct wiring.

4.2 Dimensions
The physical dimensions of the protector are important for proper installation planning. Refer to the diagram for detailed measurements.

5. Operation
The EAPDX-3P features a clear digital display for real-time monitoring and intuitive buttons for parameter configuration.
5.1 Control Panel and Display
The device displays real-time voltage (V) and current (A) for each phase (L1, L2, L3). Indicators for Power, Over-voltage (>V), Under-voltage (<V), and Over-current (>I) are also present.


5.2 Button Functions
- SET (Menu key): Used to enter the setting menu and switch between parameters.
- Digit+ / Up: Used to increase parameter values.
- Digit- / Down: Used to decrease parameter values.
- Manual ON/OFF (Power button): Used to manually turn the output on/off and to save settings.
5.3 Setting Parameters
To enter the setting mode, press and hold the SET button for 3 seconds. Use the Digit+ / Up and Digit- / Down buttons to adjust values. Short press the SET button to switch to the next parameter. To save all settings and exit, briefly press the Manual ON/OFF (power) button. If no operation is performed within 10 seconds, the system will automatically revert to the default interface without saving changes.
The following parameters can be adjusted:
- Overvoltage Protection Setting: Adjustable Range: 230-300V, Default: 270V.
- Overvoltage Protection Recovery Setting: Adjustable Range: 225-295V, Default: 265V.
- Overvoltage Recovery Delay: Adjustable Range: 1-500s, Default: 30s.
- Overvoltage Actuation Delay: Adjustable Range: 0.1-30s, Default: 1.0s.
- Undervoltage Protection Setting: Adjustable Range: 140-210V, Default: 170V.
- Undervoltage Recovery Delay: Adjustable Range: 145-215V, Default: 175V.
- Undervoltage Trip Delay: Adjustable Range: 0.1-30s, Default: 1.0s.
- Overcurrent Protection Value: Adjustable Range: 1-63A/100A, Default: 30A.
- Continuous Overcurrent Protection Attempts: Adjustable Range: 0-20 Times, Default: OFF.
- Three-phase Voltage Error Value: Adjustable Range: -9.5-9.5%, Default: 0%.
- Three-phase Voltage Imbalance Protection Threshold: Adjustable Range: 20-99V, Default Setting: 20V.
- Restoration Value For Three-phase Voltage Imbalance: Adjustable Range: 5-94V, Default Value: 20V.
- Phase Sequence Protection Switch: OFF/ON, Default: ON.
- Power-on Delay: Adjustable Range: 1-500s, Default: 10s.

6. Maintenance
The EARU EAPDX-3P protector is designed for minimal maintenance. However, periodic checks can help ensure its longevity and reliable operation:
- Visual Inspection: Regularly inspect the device for any signs of physical damage, loose connections, or discoloration.
- Cleaning: Keep the device clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use abrasive cleaners or solvents.
- Connection Checks: Periodically verify that all wiring connections are secure and tight.
- Environmental Conditions: Ensure the operating environment remains within the specified temperature and humidity ranges to prevent premature failure.
Always disconnect power before performing any maintenance or inspection.
7. Troubleshooting
If the protector is not functioning as expected, consider the following common issues:
- No Display/No Power: Check the incoming power supply and ensure all connections are secure. Verify the circuit breaker upstream is not tripped.
- Frequent Tripping: Review the set protection parameters (overvoltage, undervoltage, overcurrent, imbalance). These might be set too sensitively for your application. Check for actual fault conditions in the electrical system.
- Does Not Reset Automatically: Ensure the recovery delay setting is appropriate. If a persistent fault exists, the device will not reset until the fault is cleared. Check for continuous overcurrent protection attempts setting (if set to OFF, it won't attempt to reset after a certain number of overcurrent trips).
- Incorrect Voltage/Current Readings: If the displayed values appear incorrect, perform a manual error correction as described in the operation section.
- Phase Sequence Error: If the phase sequence protection trips, verify the phase order of the incoming supply.
If the problem persists after checking these points, contact a qualified electrician or the manufacturer for assistance.
8. User Tips
No specific user tips from reviews or Q&A were available for this product. However, general best practices for electrical protection devices include:
- Always ensure proper grounding for all electrical installations.
- Regularly monitor the display to understand the typical operating parameters of your system.
- When adjusting settings, make small incremental changes and observe the system's behavior.
- Keep this manual in a safe and accessible place for future reference.