About This Manual
This manual provides instructions for the assembly, installation, operation, and troubleshooting of the SUMRY SP/EP Hybrid Solar Inverter. Please read it carefully before installation and operation.
Target Group
This manual is designed for both professionals and end-users. End-users can handle operations that do not require specific skills. Professionals should possess the following qualifications:
- Understanding of inverter operation.
- Knowledge of handling crises and risks associated with electrical equipment.
- Ability to install and commission electrical equipment and fixtures.
- Familiarity with applicable standards and directives.
- Adherence to this manual and all safety knowledge.
Safety Regulations
Warning: This article contains important safety and operation instructions. Please read and save this manual for future reference.
- Always select the appropriate battery setting (lead-acid or lithium) to ensure normal system operation.
- Read all instructions and cautions on the unit and in this manual before use.
- Never short-circuit AC output and DC input. Do not connect to mains when DC input is short-circuited.
- Do not charge non-rechargeable batteries.
- Do not disassemble the unit. For maintenance or repair, send it to a professional technical service center. Incorrect reassembly can lead to electric shock or fire.
- To reduce electric shock risk, disconnect all wiring before maintenance or cleaning. Turning off the device alone is not sufficient.
- Exercise extreme caution with metal tools near batteries to prevent short circuits or sparks that could cause explosions.
- Use appropriate cable sizes for battery connections to ensure optimal operation and safety.
- Strictly follow installation procedures when disconnecting AC or DC terminals.
- Connect the inverter to a permanent grounding wiring system, complying with local requirements.
- Provide a fuse that meets specifications for battery power supply overcurrent protection.
- Warning: Only professional service personnel should repair this equipment. If troubleshooting fails, return the inverter to the local dealer or service center.
Product Overview
The SUMRY SP/EP Hybrid Solar Inverter is a multifunctional off-grid solar inverter, integrating an MPPT solar charging controller, high-frequency pure sine wave inverter, and UPS function module. It is ideal for off-grid backup power and self-use systems. Its high-frequency transformer design allows for reliable power conversion in a compact size.
Features
- Pure sine wave output inverter.
- Supports two battery voltage modes: up to 2300W in 12V battery mode and 4200W in 24V battery mode.
- Selectable utility grid input voltage range based on load requirements (household appliances/personal computers).
- Adjustable charging current via LCD based on battery requirements.
- Simultaneous powering of loads by solar energy and utility grid.
- AC input compatible with mains and generators.
- Automatic restart function upon mains power restoration.
- Overload, over-temperature, and short-circuit protection.
- Intelligent battery charging design for optimized battery life.
- RS485 port for BMS communication.
- Cold start function.
- Built-in MPPT with an operating voltage range of 55V~500V and open circuit voltage of 500Voc.
- Optional WIFI remote monitoring via mobile app or website.
- Optional RGB lamp indicating inverter status with different colors.
Basic System Architecture
The inverter/charger can be integrated into a system with photovoltaic modules, a generator or utility grid, and batteries. Consult your system integrator for specific configurations. This inverter can power various home and office appliances, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

Product Components Overview
The inverter features an LCD screen, status indicators, and function keys for operation and display. The rear panel includes various connection ports.

Setup (Installation)
Unpacking and Inspection
Upon receiving the inverter, unpack it and inspect for any damage. The package should contain:
- Machine x 1
- User manual x 1
Preparation Before Installation
Before connecting any wiring, remove the bottom cover of the inverter by unscrewing two screws.
Mounting the Unit
Consider the following points for installation:
- Do not mount the inverter on flammable construction materials.
- Mount on a solid surface.
- Install the inverter at eye level for easy reading of the LCD display.
- Allow a clearance of approximately 20 cm to the sides and 50 cm above and below the unit for proper air circulation and heat dissipation.
- The ambient temperature should be between 0°C and 55°C for optimal operation.
- Install vertically against the wall, ensuring sufficient space for wiring.
Caution: Suitable for mounting on concrete or other non-combustible surfaces only.
Tighten the screws to fix the installation. M4 or M5 screws are recommended.

Battery Connection
Warning: An independent DC overcurrent protector or disconnect device between the battery and inverter is required. All wiring must be performed by qualified personnel. Use appropriate cables for safety and efficient operation.
Recommended Battery Cable Specifications:
| Model | Wire Specification | Torque Value |
|---|---|---|
| 12V | 1 * 2/0 AWG (67mm²) | 2-3 Nm |
| 24V | 1 * 1/0 AWG (54mm²) | 2-3 Nm |
Note: The recommended charging current for lead-acid batteries is 0.2C (C is battery capacity).
Lead-Acid Battery Connection Steps:
- Connect the battery using recommended cable specifications.
- Connect all battery packs as needed.
- Insert the ring terminal of the battery cable into the inverter's battery connector and tighten bolts to 2-3 Nm. Ensure correct polarity.
- Connect all battery packs as shown in the diagram below.

Lithium Battery Connection and Setting:
Only lithium batteries matched with BMS communication protocol are allowed. Follow these steps:
- Connect the battery using recommended cable specifications.
- Insert the ring terminal of the battery cable into the inverter's battery connector and tighten bolts to 2-3 Nm. Ensure correct polarity.
- Connect one side of an RJ45 cable to the inverter's BMS communication port.
- Insert the other side of the RJ45 cable into the RS485 communication port on the lithium battery.
Note: If using a lithium battery, ensure the battery and inverter are connected with a BMS communication cable, and select "LIB" mode in the inverter settings.
BMS Communication Port PIN Definition:
| Pin Number | Port Definition |
|---|---|
| 1 | RS485B |
| 2 | RS485A |
| 3-6 | NC (No Connection) |
| 7 | RS485A |
| 8 | RS485B |
To communicate with the lithium battery BMS, press and hold the "ENTER" button, then set the battery type to "LIB" in program 05. Select the matching battery protocol in program 10.
AC Input/Output Connection
Caution: Install a separate AC breaker between the inverter and the AC input power source. This ensures safe disconnection during maintenance and protection from overcurrent. There are two terminal blocks labeled "IN" and "OUT"; do not mis-connect them. All wiring must be performed by qualified personnel. Use appropriate cable sizes.
Suitable Cable Specifications for AC Wires:
| Model | Wire Gauge | Torque Value |
|---|---|---|
| 12V/24V | 1 * 12 AWG | 1.2-1.6 Nm |
AC Input/Output Connection Steps:
- Before connecting, open the DC protector or disconnector.
- Remove 10mm of insulation from the six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to polarities (L, N) on the terminal block and tighten screws. Connect the PE protective conductor (ground, yellow-green) first.
- Insert AC output conductors according to polarities and tighten screws.
- Ensure all wires are firmly connected.
Caution: Ensure all AC cables are connected correctly according to polarity. Appliances like air conditioners require 2-3 minutes to restart; a power shortage and quick recovery can damage them. Check the manufacturer's instructions for such appliances.
PV Connection
Caution: Install a separate DC circuit breaker between the inverter and the PV module. All wiring must be performed by qualified personnel. Use appropriate cables for safety and efficient operation.
PV Module Selection:
When selecting PV modules, consider these parameters:
- Open circuit Voltage (Voc) of PV modules must not exceed the max. PV array open circuit voltage of the inverter.
- Open circuit Voltage (Voc) of PV modules should be higher than the minimum battery voltage.
| Parameter | Value |
|---|---|
| Max. PV Array Power | 4000W |
| I Max. PV | 18A |
| Nominal PV Voltage | 240V |
| PV Array MPPT Voltage Range | 55V-500V |
| Max. PV Array Open Circuit Voltage | 500V |
PV Module Connection Steps:
- Remove 10mm of insulation from positive and negative conductors.
- Check correct polarity of connection cables from PV modules and PV input connectors. Connect positive (+) to positive (+) and negative (-) to negative (-).
- Ensure wires are securely connected.
Final Assembly
After connecting all wires, replace the bottom cover and secure it with screws.
Operating
Power On/Off
After correctly installing the machine and connecting the battery, simply press the On/Off switch to turn on the inverter.
Operation and Display Panel
The front panel of the inverter features an LCD display, LED indicators, and four function keys (ESC, UP, DOWN, ENTER) to show operation status and input/output power information.

RGB Light (Optional)
The RGB light indicates inverter status:
- Green light: Inverter state.
- Blue light: Utility state.
- Red light: Failure state.
LED Indicator
| LED Indicator | Color | Status | Messages |
|---|---|---|---|
| AC / INV | Green | Solid On | Output is powered by utility in Line mode. |
| Flashing | Output is powered by battery or PV in battery mode. | ||
| CHG | Green | Solid On | Battery is fully charged. |
| Flashing | Battery is charging. | ||
| FAULT | Red | Solid On | Fault occurs in the inverter. |
| Flashing | Warning condition occurs in the inverter. |
Function Keys
| Function Key | Description |
|---|---|
| ESC | To exit setting mode |
| UP | To go to previous selection |
| DOWN | To go to next selection |
| ENTER | To confirm the selection in setting mode or enter setting mode |
LCD Display Icons

LCD Setting
To enter setting mode, press and hold the "ENTER" button for 3 seconds. Use "UP" or "DOWN" to select programs, and "ENTER" to confirm or "ESC" to exit. Key settings include:
- 01 Output Source Priority: Configure whether solar, battery, or utility takes priority for powering loads.
- 02 Maximum Charging Current: Set total charging current for solar and utility chargers.
- 03 AC Input Voltage Range: Select acceptable AC input voltage range (e.g., 90-280VAC for appliances, 170-280VAC for UPS).
- 04 Power Saving Mode: Enable or disable power saving mode.
- 05 Battery Type: Select battery type (AGM, Flooded, User Defined, Lithium).
- 06 Auto Restart When Overload Occurs: Enable or disable auto restart after overload.
- 07 Auto Restart When Over Temperature Occurs: Enable or disable auto restart after over temperature.
- 08 Output Voltage: Set output voltage (e.g., 220V, 230V, 240V).
- 09 Output Frequency: Set output frequency (50Hz, 60Hz).
- 10 Lithium Battery Protocol: Select matching protocol for lithium batteries (e.g., PYLON, PACE).
- 11 Maximum Utility Charging Current: Set maximum charging current from utility.
- 12 Setting Voltage Point Back to Utility Charging: Configure voltage thresholds for switching to utility charging.
- 13 Set Voltage Point Back to Battery Discharge: Configure voltage thresholds for switching back to battery discharge.
- 16 Charger Source Priority: Configure charger source priority (Solar first, Solar and Utility, Only Solar).
- 18 Alarm Control: Turn alarm on or off.
- 19 Auto Return to Default Display Screen: Enable or disable automatic return to default display.
- 20 Backlight Control: Turn backlight on or off.
- 22 Beeps While Primary Source is Interrupted: Enable or disable beeps.
- 23 Overload Bypass: Enable or disable bypass to line mode during overload in battery mode.
- 25 Record Fault Code: Enable or disable fault code recording.
- 26 Bulk Charging Voltage (C.V voltage): Set bulk charging voltage.
- 27 Floating Charging Voltage: Set floating charging voltage.
- 29 Low DC Cut-off Voltage: Set low DC cut-off voltage.
- 33 Battery Equalization: Enable or disable battery equalization.
- 34 Battery Equalization Voltage: Set battery equalization voltage.
- 35 Battery Equalized Time: Set duration for battery equalization.
- 36 Battery Equalized Timeout: Set timeout for battery equalization.
- 37 Equalization Interval: Set interval for battery equalization.
- 39 Equalization Activated Immediately: Activate equalization immediately.
- 48 RGB Lighting: Turn RGB lights on or off.
Maintenance
Clearance and Maintenance for Anti-Dust Kit (Optional)
The inverter comes with a factory-installed anti-dust kit. This kit automatically detects and adjusts the internal thermal sensor to maintain internal temperature, prevents dust ingress, and enhances product reliability in harsh environments.
Maintenance Steps:
- Remove the screws securing the air filter cover.
- Remove the air filter.
- Clean the air filter.
- After cleaning, reinstall the dust removal net and secure the cover.
Notice: The anti-dust kit should be cleaned from dust every one month.
Troubleshooting
This section provides guidance for common issues. For persistent problems, contact professional service personnel.
Battery Alarm Codes
| Alarm Code | Alarm Event | Icon Flashing |
|---|---|---|
| 21 | Battery Cell Over Voltage | (21) |
| 22 | Battery Cell Under Voltage | (22) |
| 23 | Battery Pack Over Voltage | (23) |
| 24 | Battery Pack Under Voltage | (24) |
| 25 | Charging Over Current | (25) |
| 26 | Discharging Over Current | (26) |
| 27 | Charging Cell Over Temperature | (27) |
| 28 | Discharging Cell Over Temperature | (28) |
| 29 | Charging Cell Under Temperature | (29) |
| 30 | Discharging Cell Under Temperature | (30) |
| 34 | Battery capacity is too low | (34) |
| 44 | Battery Cell Voltage Imbalance | (44) |
| 45 | Battery Cell Temperature Imbalance | (45) |
| 46 | Internal Communication Alarm | (46) |
Battery Fault Codes
| Fault Code | Fault Event | Icon |
|---|---|---|
| 21 | Battery Cell Over Voltage | (21) ERROR |
| 22 | Battery Cell Under Voltage | (22) ERROR |
| 23 | Battery Pack Over Voltage | (23) ERROR |
| 24 | Battery Pack Under Voltage | (24) ERROR |
| 25 | Charging Over Current | (25) ERROR |
| 26 | Discharging Over Current | (26) ERROR |
| 27 | Charging Cell Over Temperature | (27) ERROR |
| 28 | Discharging Cell Over Temperature | (28) ERROR |
| 29 | Charging Cell Under Temperature | (29) ERROR |
| 30 | Discharging Cell Under Temperature | (30) ERROR |
| 31 | Ambient Over Temperature | (31) ERROR |
| 32 | Ambient Under Temperature | (32) ERROR |
| 33 | MOS Over Temperature | (33) ERROR |
| 35 | Battery Short Circuit | (35) ERROR |
| 36 | Charge Overvoltage | (36) ERROR |
| 37 | System Failure | (37) ERROR |
| 39 | Charging MOS Fault | (39) ERROR |
| 40 | Discharge MOS Fault | (40) ERROR |
| 41 | Temperature Sensor Fault | (41) ERROR |
| 42 | Battery Cell Fault | (42) ERROR |
| 43 | Sampling Communication Failure | (43) ERROR |
Warning Codes
| Warning Code | Warning Event | Automatic Alarm | Icon Flashing |
|---|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second | (01) |
| 03 | Battery overcharge | Beep once every second | (03) |
| 04 | Battery low voltage | Beep once every second | (04) |
| 07 | Overload | Beep once every 0.5 second | (07) |
| 10 | Output power is derating | Beep twice every 3 seconds | (10) |
| 15 | PV energy is weak | No Beep | (15) |
| EQ | Battery equalization | No Beep | (EQ) |
General Troubleshooting Table
| Problem | LCD/Buzzer | Explanation / Possible Cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD and buzzer active for 3 seconds, then off. | Battery voltage is too low | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. Battery voltage too low. 2. Battery polarity reversed. | 1. Check batteries and wiring. 2. Re-charge battery. 3. Replace battery. |
| Input voltage displayed as 0 on LCD. | Input protector tripped | Check if AC breaker is tripped and AC wiring is connected. | |
| Mains exist but unit works in battery mode. | Power-on icon of LCD flashes, status indicator icon flashes. | Insufficient quality of AC power (shore or generator) | 1. Check if AC wires are too thin/long. 2. Check if generator (if applied) is working or if input voltage range setting is correct (UPS → Appliance). |
| Fault code 07 | Overload error. Inverter overloaded 110%, time is up. | Reduce the connected load by switching off some equipment. | |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Internal temperature of inverter component overheated. | Check whether air flow is blocked or ambient temperature is too high. | |
| Buzzer beeps continuously and status indicator icon is always on. | Fault code 03 | Battery is over-charged. Battery voltage too high. | Return to repair center. Check if spec and quantity of batteries meet requirements. |
| Fault code 01 | Fan fault | Replace the fan. | |
| Fault code 06/58 | Output abnormal | 1. Reduce the connected load. 2. Return to repair center. | |
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit; if error persists, return to repair center. | |
| Fault code 52 | Bus voltage too low. | Restart the unit; if error persists, return to repair center. | |
| Fault code 55 | Output voltage unbalanced. | Restart the unit; if error persists, return to repair center. |
Specifications
The SUMRY SP/EP Hybrid Solar Inverter is available in various models, including SP-2200, SP-3200, SP-4200, SP-7000, and EP-4200H, offering different power capacities and features.

Table 1: Specification of LINE Mode (EP-4200H)
| Parameter | Specification |
|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Nominal Input Voltage | 230Vac |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) |
| High Loss Voltage | 280Vac±7V |
| High Loss Return Voltage | 270Vac±7V |
| Max AC Input Voltage | 300Vac |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) |
| Low Loss Frequency | 40±1Hz |
| Low Loss Return Frequency | 42±1Hz |
| High Loss Frequency | 65±1Hz |
| High Loss Return Frequency | 63±1Hz |
| Output Short Circuit Protection | Battery mode: Electronic Circuits |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) |
Table 2: Specification of Inverter Mode (EP-4200H)
| Parameter | Specification |
|---|---|
| Rated Output Power | DC12V-2300VA/2300W; DC24V-4200VA/4200W |
| Output Voltage Waveform | Pure Sine Wave |
| Output Voltage Regulation | 230Vac±5% |
| Output Frequency | 60Hz or 50Hz |
| Peak Efficiency | 94% |
| Overload Protection | 5s@≥150% load; 10s@105%~150% load |
| Surge Capacity | 2* rated power for 5 seconds |
| Nominal DC Input Voltage | 12 Vdc; 24Vdc |
| Cold Start Voltage | 11.5 Vdc; 23.0Vdc |
| Low DC Warning Voltage (@Load < 20%) | 11.0 Vdc; 22.0Vdc |
| Low DC Warning Voltage (@20% ≤ Load < 50%) | 10.7 Vdc; 21.4Vdc |
| Low DC Warning Voltage (@Load ≥ 50%) | 10.1 Vdc; 20.2Vdc |
| Low DC Warning Return Voltage (@Load < 20%) | 11.5 Vdc; 23.0Vdc |
| Low DC Warning Return Voltage (@20% ≤ Load < 50%) | 11.2 Vdc; 22.4Vdc |
| Low DC Warning Return Voltage (@Load ≥ 50%) | 10.6 Vdc; 21.2Vdc |
| Low DC Cut-off Voltage (@Load < 20%) | 10.5 Vdc; 21.0Vdc |
| Low DC Cut-off Voltage (@20% ≤ Load < 50%) | 10.2 Vdc; 20.4Vdc |
| Low DC Cut-off Voltage (@Load ≥ 50%) | 9.6 Vdc; 19.2Vdc |
| High DC Cut-off Voltage | 16 Vdc; 32Vdc |
| No Load Power Consumption | 20W; 30W |
| Saving Mode Power Consumption | <10W; <15W |
Table 3: Specification of Charging Mode
| Utility Charging Mode | 12V | 24V |
|---|---|---|
| Battery Model | Flooded Battery | |
| Charging Current (UPS) @Nominal Input Voltage | 100A | |
| Bulk Charging | 14.6 | 29.2 |
| Voltage (AGM / Gel Battery) | 14.1 | 28.2 |
| Floating Charging Voltage | 13.5Vdc | 27Vdc |
| Charging Algorithm | 3-Step | |
Table 4: General Specifications
| Parameter | Specification |
|---|---|
| Operating Temperature Range | -20°C to 55°C |
| Storage Temperature | -20°C~60°C |
| Dimension (D*W*H), mm | 405*305*108 |
| Net Weight, kg | 6.7 |
Warranty and Support
All SUMRY products come with a 1-year warranty from the store. For any issues or repairs, please contact professional service personnel or the local dealer/service center. Do not attempt to disassemble the unit yourself.
A detailed user manual in PDF format is available for download: View User Manual (PDF)
User Tips
- Battery Connection is Essential: This inverter requires a battery to operate. Ensure the battery is properly connected before connecting solar panels.
- Check for Included WiFi Module: Some users have reported receiving a WiFi module even when ordering a 'without WiFi' configuration. Check your package contents.
- Robust Build Quality: The inverter features a sturdy case made of thick metal, with good terminals and convenient connections, indicating a durable design.
- Consider the Weight: The inverter is noted to be heavier than similar products, suggesting more robust internal components and heat dissipation features like larger radiators.
- Initial Power-Up: The inverter can be started from the power supply alone, outputting 230 Volts at 50 Hz with a no-load power consumption of around 30 Watts.
- Adjustable Charging Settings: The inverter allows for setting the charge current, for example, up to 80A in the settings.