1. Introduction
This manual provides comprehensive instructions for the assembly, installation, operation, and troubleshooting of the PowMr Hybrid Solar Inverter. Please read this manual carefully before proceeding with installation and operation to ensure safe and efficient use.
The PowMr Hybrid Solar Inverter is a multifunctional off-grid solar inverter that integrates an MPPT solar charging controller, a high-frequency pure sine wave inverter, and a UPS function module. It is designed for off-grid backup power supply and spontaneous self-use systems. The high-frequency transformer design allows for reliable power conversion in a compact size.
For a complete operational system, additional equipment such as photovoltaic modules, a generator, or a utility grid connection may be required. Consult with your system integrator for specific system architectures based on your requirements. An optional Wi-Fi module is available for remote monitoring of the solar system's status via mobile devices or websites.
2. Features
The PowMr Hybrid Solar Inverter offers a range of features designed for efficient and reliable solar power management:
- Dual Battery Voltage Modes: Operates in 12V battery mode with a maximum load of 2300W, and 24V battery mode with a maximum load of 4200W.
- Pure Sine Wave Output: Provides clean and stable power suitable for all types of appliances.
- Configurable Input Voltage Range: Selectable utility grid input voltage range based on load requirements (e.g., household appliances, personal computers).
- Adjustable Charging Current: Charging current can be set via the LCD display to match battery requirements.
- Simultaneous Power Supply: Can power loads concurrently from solar energy and the utility grid.
- AC Input Compatibility: Compatible with both mains power and generators.
- Automatic Restart: Features an automatic restart function when mains power is restored.
- Comprehensive Protection: Includes overload, over-temperature, and short-circuit protection.
- Intelligent Battery Charging: Designed to maximize battery utilization and prolong battery life.
- RS485 Port: For communication with Battery Management Systems (BMS).
- Cold Start Function: Enables the inverter to start without an external AC source.
- Built-in MPPT: Features Maximum Power Point Tracking with an operating voltage range of 55V-500V and an open circuit voltage of 500Voc.
- Optional Wi-Fi Monitoring: Allows remote monitoring of the inverter's status.
- Optional RGB Light: Displays different colors to indicate inverter status.
3. Safety Regulations
Warning: This article contains important safety and operation instructions. Please read and save this manual for future reference.
- Always select the appropriate battery type setting (lead-acid or lithium battery). Incorrect settings may lead to system malfunction.
- Before using the unit, thoroughly read all instructions and cautionary notes on the unit and understand all battery models and relevant chapters in this manual.
- Never short-circuit AC output and DC input. Do not connect to mains power if DC input is short-circuited.
- Do not attempt to charge non-rechargeable batteries.
- Do not disassemble the unit. For maintenance or repair, send it to a professional technical service center. Improper reassembly can result in electric shock or fire.
- To minimize electric shock risk, disconnect all wiring before any maintenance or cleaning. Turning off the device alone does not eliminate this risk.
- Exercise extreme caution when using metal tools near the battery. Sparks from falling tools or short circuits can cause explosions.
- For optimal operation, use the appropriate cable size for battery connections as specified in this manual.
- When disconnecting AC or DC terminals, strictly follow the installation procedure detailed in the "Installation" section.
- Ensure the off-grid solar inverter is connected to a permanent grounding system, complying with local requirements and regulations.
- Install a fuse with the specified rating for battery power supply overcurrent protection.
- Warning: Only professional service personnel should repair this equipment. If troubleshooting does not resolve errors, return the inverter to your local dealer or service center.
4. Installation
This section details the steps for installing your PowMr Hybrid Solar Inverter. Ensure all safety precautions are followed.
4.1. Unpacking and Inspection
Upon receiving the inverter, carefully unpack it and inspect for any damage. The package should contain:
- Inverter Unit x 1
- User Manual x 1 (This document)
4.2. Preparation Before Installation
Before connecting any wiring, remove the bottom cover of the inverter by unscrewing the two screws as shown in the product overview diagram.
4.3. Mounting the Inverter
Consider the following points for optimal installation:
- Do not install the inverter on flammable building materials.
- Mount on a solid surface.
- Install at eye level for easy LCD display readability.
- Maintain a 20-50 cm gap around the equipment for proper ventilation and heat dissipation.
- Ensure the operating environment temperature is between 0-55°C.
- It is best to install it vertically against the wall, leaving space from the ground.
Warning: Suitable for installation on concrete or other non-combustible surfaces only.
Tighten the screws to fix the installation. M4 or M5 screws are recommended for mounting.
4.4. Battery Connection
Warning: An independent DC overcurrent protector or disconnect device must be installed between the battery and the inverter. All wiring must be performed by qualified personnel.
Using appropriate cable for battery connection is crucial for system safety and efficient operation. Refer to the table below for recommended cable specifications:
| Model | Wire Specification | Torque Value |
|---|---|---|
| 12V | 1 * 2/0 AWG (67mm²) | 2-3 Nm |
| 24V | 1 * 1/0 AWG (54mm²) | 2-3 Nm |
Note: The recommended charging current for lead-acid batteries is 0.2C (C = battery capacity).
Steps for Battery Connection:
- Connect the battery using the recommended battery cable specifications.
- Connect all necessary battery packs.
- Insert the ring terminal of the battery cable into the inverter's battery connector, ensuring it is flat. Tighten the bolts with a torque of 2-3 Nm. Verify correct polarity (+ to + and - to -) between the battery and inverter.
Warning: Shock Hazard! Installation must be performed with care due to high battery voltage in series.
Caution: Do not place anything between the flat part of the inverter terminal and the ring terminal to prevent short circuits or overheating. Do not apply antioxidant to the terminal before tightening. Before making the final DC connection or closing the DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).
Connect all battery packs as shown in the following diagrams:
4.5. Lithium Battery Connection (Optional)
If using lithium batteries, only those matched with the BMS communication protocol are allowed.
Steps for Lithium Battery Connection:
- Connect the battery according to the recommended battery cable specifications.
- Insert the ring terminal of the battery cable into the inverter's battery connector, ensuring it is flat. Tighten the bolts with a torque of 2-3 Nm. Verify correct polarity (+ to + and - to -) between the battery and inverter.
- Connect one side of the RJ45 cable to the BMS communication port of the inverter.
- Insert the other side of the RJ45 cable into the RS485 communication port on the lithium battery.
Note: If you choose a lithium battery, ensure the battery and inverter are connected with a BMS communication cable, and select "LIB" mode for the battery type in the inverter settings.
Communication and Setting of Lithium Battery:
- Connect the RJ45 communication cable between the inverter and battery. Confirm that the lithium battery BMS port's PIN corresponds with the inverter BMS communication port.
- To enable communication with the lithium battery BMS, press and hold the "ENTER" button, then set the battery type to "LIB" in program 05. Select the matching battery protocol in Program 10.
4.6. AC Input/Output Connection
Caution: Before connecting to the AC input power source, install a separate AC breaker between the inverter and the AC input power source. This ensures safe disconnection during maintenance and protection from overcurrent. There are two terminal blocks marked "IN" and "OUT"; do NOT mis-connect them. All wiring must be performed by qualified personnel. Use appropriate cable sizes for AC input connection to reduce risk of injury.
Suitable cable specifications for AC wires:
| Model | Wire Gauge | Torque Value |
|---|---|---|
| 12V/24V | 1 * 12 AWG | 1.2-1.6 Nm |
Steps for AC Input/Output Connection:
- Before making AC input/output connections, ensure the DC protector or disconnector is open.
- Remove 10mm of insulation from the six conductors. Shorten phase L and neutral conductor N by 3mm.
- Insert AC input wires according to the polarities indicated on the terminal block and tighten the terminal screws. Ensure the PE protective conductor (yellow-green) is connected first.
- Insert the AC output conductor according to the polarity identification at the terminal and tighten the screw.
- Verify all wires are firmly connected.
Caution: Ensure all AC cables are connected with correct polarity. Appliances like air conditioners require 2-3 minutes to restart after a power outage to balance refrigerant gas. A short power shortage and recovery can damage connected appliances. Check the air conditioner manufacturer's guidelines if it has a time-delay function.
4.7. PV Connection
Caution: Before connecting the PV module, install a DC circuit breaker between the inverter and the PV module. All wiring must be performed by qualified personnel. Use appropriate cable sizes for PV module connection to reduce risk of injury.
Suitable cable specifications for PV wires:
| Model | Wire Gauge | Torque Value |
|---|---|---|
| 12V/24V | 1 * 16 AWG | 1.2-1.6 Nm |
PV Module Selection:
When selecting PV modules, consider the following parameters:
- The open circuit voltage (Voc) of PV modules must not exceed the maximum PV array open circuit voltage of the inverter.
- The open circuit voltage (Voc) of PV modules should be higher than the minimum battery voltage.
PV System Parameters:
- Max. PV Array Power: 4000W
- I Max. PV: 18A
- Nominal PV Voltage: 240V
- PV Array MPPT Voltage Range: 55V-500V
- Max. PV Array Open Circuit Voltage: 500V
Steps for PV Module Connection:
- Remove 10mm of insulation from the positive and negative conductors.
- Check the correct polarity of the connection cable from PV modules and PV input connectors. Connect the positive pole (+) of the connection cable to the positive pole (+) of the PV input connector, and the negative pole (-) to the negative pole (-).
- Ensure the wires are securely connected.
4.8. Final Assembly
After connecting all wires, reinstall the bottom cover and secure it with the screws.
Video 4.1: Wiring Guide for PowMr All-in-one Solar Inverter (POW-HVM4.2M-24V). This video demonstrates the steps for connecting the battery, AC input, AC output, PV input, grounding the inverter, and powering it on.
5. Operation
5.1. Power On/Off
After correctly installing the machine and connecting the battery, simply press the On/Off switch to power on the inverter.
5.2. Operation and Display
The operation and display panel, located on the front of the inverter, includes an LCD screen and four function keys for indicating operational status and input/output power information.
RGB Light (Optional)
The optional RGB light indicates the inverter's status:
- Green Light: Inverter state
- Blue Light: Utility state
- Red Light: Failure state
LED Indicator
| LED Indicator | Status | Messages |
|---|---|---|
| AC/INV (Green) | Solid On | Output is powered by utility in Line mode. |
| CHG (Green) | Flashing | Output is powered by battery or PV in battery mode. |
| CHG (Green) | Solid On | Battery is fully charged. |
| CHG (Green) | Flashing | Battery is charging. |
| FAULT (Red) | Solid On | Fault occurs in the inverter. |
| FAULT (Red) | Flashing | Warning condition occurs in the inverter. |
Function Keys
The inverter features four function keys for navigation and settings:
- ESC: Exits setting mode.
- UP: Navigates to the previous selection.
- DOWN: Navigates to the next selection.
- ENTER: Confirms selection in setting mode or enters setting mode.
LCD Display Icons
The LCD screen displays various icons to provide information about the inverter's status and operation. These include input source information (AC, PV), configuration program and fault information, and output information.
For detailed information on specific icons and their meanings, please refer to the full PDF user manual available for download. View User Manual (PDF)
LCD Setting
To enter setting mode, press and hold the "ENTER" button for 3 seconds. Use the "UP" or "DOWN" buttons to select programs, and "ENTER" to confirm or "ESC" to exit.
Key settings include:
- Program 01: Output Source Priority (SBU, Solar First, Utility First)
- Program 02: Maximum Charging Current (10A-100A)
- Program 03: AC Input Voltage Range (Appliances, UPS)
- Program 04: Power Saving Mode (Enable/Disable)
- Program 05: Battery Type (AGM, Flooded, User-Defined, LIB)
- Program 06: Auto Restart when Overload Occurs (Enable/Disable)
- Program 07: Auto Restart when Over Temperature Occurs (Enable/Disable)
- Program 08: Output Voltage (220V, 230V, 240V)
- Program 09: Output Frequency (50Hz, 60Hz)
- Program 10: Lithium Battery Protocol (PYLON, PACE)
- Program 11: Maximum Utility Charging Current (10A-100A)
- Program 12: Setting Voltage Point back to Utility Charging
- Program 13: Set Voltage Point back to Battery Discharge
- Program 16: Charger Source Priority (Solar First, Solar and Utility, Only Solar)
- Program 18: Alarm Control (On/Off)
- Program 19: Auto Return to Default Display Screen (Enable/Disable)
- Program 20: Backlight Control (On/Off, Stay at latest screen)
- Program 22: Beeps while Primary Source is Interrupted (On/Off)
- Program 23: Overload Bypass (Enable/Disable)
- Program 25: Record Fault Code (Enable/Disable)
- Program 26: Bulk Charging Voltage (C.V voltage)
- Program 27: Floating Charging Voltage
- Program 29: Low DC Cut-off Voltage
- Program 33: Battery Equalization (Enable/Disable)
- Program 34: Battery Equalization Voltage
- Program 35: Battery Equalized Time
- Program 36: Battery Equalized Timeout
- Program 37: Equalization Interval
- Program 39: Equalization Activated Immediately (Enable/Disable)
- Program 48: RGB Lighting (On/Off)
Operating Mode Description
The inverter supports various operating modes:
- Standby Mode / Power Saving Mode: In standby, the inverter is not actively powering loads but can charge the battery. In power saving mode, the output is off if the connected load is very low or not detected.
- Line Mode: The unit provides output power from the mains and can also charge the battery.
- Battery Mode: The unit provides output power from the battery and PV power.
6. Specifications
This section provides detailed technical specifications for the PowMr Hybrid Solar Inverter (Model: POW-HVM4.2K-24V-D).
6.1. Line Mode Specification
| Parameter | Value |
|---|---|
| Input Voltage Waveform | Sinusoidal (utility or generator) |
| Nominal Input Voltage | 230Vac |
| Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) |
| Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) |
| High Loss Voltage | 280Vac±7V |
| High Loss Return Voltage | 270Vac±7V |
| Max AC Input Voltage | 300Vac |
| Nominal Input Frequency | 50Hz / 60Hz (Auto detection) |
| Low Loss Frequency | 40±1Hz |
| Low Loss Return Frequency | 42±1Hz |
| High Loss Frequency | 65±1Hz |
| High Loss Return Frequency | 63±1Hz |
| Output Short Circuit Protection | Battery mode: Electronic Circuits |
| Efficiency (Line Mode) | >95% (Rated R load, battery full charged) |
| Transfer Time | 10ms typical (UPS); 20ms typical (Appliances) |
6.2. Inverter Mode Specification
| Parameter | 12V-2300VA/2300W | 24V-4200VA/4200W |
|---|---|---|
| Rated Output Power | DC12V-2300VA/2300W | DC24V-4200VA/4200W |
| Output Voltage Waveform | Pure Sine Wave | |
| Output Voltage Regulation | 230Vac±5% | |
| Output Frequency | 60Hz or 50Hz | |
| Peak Efficiency | 94% | |
| Overload Protection | 5s@≥150% load; 10s@105%~150% load | |
| Surge Capacity | 2* rated power for 5 seconds | |
| Nominal DC Input Voltage | 12 Vdc | 24Vdc |
| Cold Start Voltage | 11.5 Vdc | 23.0Vdc |
| Low DC Warning Voltage | ||
| @ Load < 20% | 11.0 Vdc | 22.0Vdc |
| @ 20% ≤ Load < 50% | 10.7 Vdc | 21.4Vdc |
| @ Load ≥ 50% | 10.1 Vdc | 20.2Vdc |
| Low DC Warning Return Voltage | ||
| @ Load < 20% | 11.5 Vdc | 23.0Vdc |
| @ 20% ≤ Load < 50% | 11.2 Vdc | 22.4Vdc |
| @ Load ≥ 50% | 10.6 Vdc | 21.2Vdc |
| Low DC Cut-off Voltage | ||
| @ Load < 20% | 10.5 Vdc | 21.0Vdc |
| @ 20% ≤ Load < 50% | 10.2 Vdc | 20.4Vdc |
| @ Load ≥ 50% | 9.6 Vdc | 19.2Vdc |
| High DC Cut-off Voltage | 16 Vdc | 32Vdc |
| No Load Power Consumption | 20W | 30W |
| Saving Mode Power Consumption | <10W | <15W |
6.3. Charging Mode Specification
| Parameter | 12V | 24V |
|---|---|---|
| Utility Charging Mode Battery Model | 12V | 24V |
| Charging Current (UPS) @ Nominal Input Voltage | 100A | |
| Bulk Charging (Flooded Battery) | 14.6 | 29.2 |
| Voltage (AGM / Gel Battery) | 14.1 | 28.2 |
| Floating Charging Voltage | 13.5Vdc | 27Vdc |
| Charging Algorithm | 3-Step | |
| Max. PV Array Power | 4000W | |
| I Max. PV | 18A | |
| Nominal PV Voltage | 240V | |
| PV Array MPPT Voltage Range | 55V-500V | |
| Max. PV Array Open Circuit Voltage | 500V | |
| Max Charging Current | 100A | |
6.4. General Specifications
| Parameter | Value |
|---|---|
| Operating Temperature Range | -20°C to 55°C |
| Storage Temperature | -20°C~60°C |
| Dimension (D*W*H), mm | 405*305*108 |
| Net Weight, kg | 6.7 |
7. Maintenance
7.1. Clearance and Maintenance for Anti-Dust Kit (Optional)
The inverter comes with a factory-installed anti-dust kit. This kit helps prevent dust from entering the inverter and activates an internal thermal sensor to adjust the internal temperature, enhancing product reliability in harsh environments.
Maintenance Steps:
- Remove the screws securing the anti-dust kit.
- Carefully remove the air filter.
- Clean the air filter. After cleaning, reinstall the dust removal net into the inverter.
Notice: The anti-dust kit should be cleaned of dust every one month.
8. Troubleshooting
This section provides common problems, their possible causes, and recommended solutions.
| Problem | LCD/Buzzer Indication | Explanation / Possible Cause | What to do |
|---|---|---|---|
| Unit shuts down automatically during startup process. | LCD and buzzer active for 3 seconds, then off. | Battery voltage is too low. | 1. Re-charge battery. 2. Replace battery. |
| No response after power on. | No indication. | 1. Battery voltage is far too low. 2. Battery polarity is connected reversed. |
1. Check if batteries and wiring are connected well. 2. Re-charge battery. 3. Replace battery. |
| Input voltage displayed as 0 on LCD. | Input protector is tripped. | Check if AC breaker is tripped and AC wiring is connected well. | |
| Mains exist but unit works in battery mode. | Power-on icon flashes, status indicator icon flashes. | Insufficient quality of AC power (Shore or Generator). | 1. Check if AC wires are too thin/long. 2. Check if generator (if applied) is working well or if input voltage range setting is correct (UPS → Appliance). |
| Fault code 07 | Overload error (110% overload, time up). | Reduce connected load by switching off some equipment. | |
| Fault code 05 | Output short circuited. | Check if wiring is connected well and remove abnormal load. | |
| Fault code 02 | Internal temperature of inverter component is overheated. | Check whether air flow is blocked or ambient temperature is too high. | |
| Buzzer beeps continuously and status indicator icon is always on. | Fault code 03 | Battery is over-charged. Battery voltage is too high. | Return to repair center. Check if specifications and quantity of batteries meet requirements. |
| Fault code 01 | Fan fault. | Replace the fan. | |
| Fault code 06/58 | Output abnormal. | 1. Reduce the connected load. 2. Return to repair center. |
|
| Fault code 08/09/53/57 | Internal components failed. | Return to repair center. | |
| Fault code 51 | Over current or surge. | Restart the unit. If the error persists, return to repair center. | |
| Fault code 52 | Bus voltage is too low. | Restart the unit. If the error persists, return to repair center. | |
| Fault code 55 | Output voltage is unbalanced. | Restart the unit. If the error persists, return to repair center. |
8.1. Warning Codes
The inverter also provides warning codes for less critical issues:
| Warning Code | Warning Event | Automatic Alarm |
|---|---|---|
| 01 | Fan is locked when inverter is on. | Beep three times every second. |
| 03 | Battery overcharge. | Beep once every second. |
| 04 | Battery low voltage. | Beep once every second. |
| 07 | Overload. | Beep once every 0.5 second. |
| 10 | Output power is derating. | Beep twice every 3 seconds. |
| 15 | PV energy is weak. | No Beep. |
| EQ | Battery equalization. | No Beep. |
9. Battery Equalization
The equalization function, integrated into the charge controller, helps reverse the buildup of negative chemical effects like stratification (where acid concentration is higher at the bottom of the battery). Equalization also aids in removing sulfate crystals that may accumulate on the battery plates. Regular equalization is recommended to maintain overall battery capacity.
9.1. How to Apply Equalization Function
To use this feature, you must first enable the battery equalization function in monitoring LCD setting program 33. You can then apply equalization using one of the following methods:
- Set the equalization interval in program 37.
- Activate equalization immediately in program 39.
9.2. When to Equalize
In the float stage, when the set equalization interval is reached, or if equalization is activated immediately, the controller will initiate the Equalize stage.
9.3. Equalize Charging Time and Timeout
During the equalize stage, the controller supplies power to charge the battery until its voltage reaches the battery equalization voltage. Constant voltage regulation then maintains the battery voltage at this level. The battery remains in the Equalize stage until the set battery equalized time is reached.
If the battery equalized time expires and the battery voltage has not reached the equalization voltage point, the charge controller will extend the equalized time until the battery voltage is achieved. If the battery voltage is still below the equalization voltage after the extended time, the charge controller will stop equalization and return to the float stage.
10. User Tips
- Lithium Battery Compatibility: While the inverter supports lithium batteries, ensure that if you are using LiFePO4 batteries, they are compatible with the inverter's BMS communication protocol. Always verify the specific battery type (e.g., LiFePO4) is supported and correctly configured in program 05 and 10 for optimal performance and safety.
- Cable Sizing: Always use the recommended cable sizes for battery, AC, and PV connections to prevent overheating and ensure efficient power transfer.
- Ventilation: Maintain adequate clearance around the inverter to ensure proper airflow and prevent overheating, especially in enclosed spaces.
11. Warranty and Support
For technical support, warranty claims, or service, please contact PowMr directly. Only professional service personnel should attempt repairs. If troubleshooting steps do not resolve an issue, please contact the service center.
Shenzhen Hehejin Industrial Co., Ltd.
- Tel/Fax: +86755-28219903
- Email: support@powmr.com
- Web: www.powmr.com
- Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China
Model Number: POW-HVM4.2K-24V-D