UNI-T UT271A, UT271B, UT271C

Contents

UNI-T UT271 Series Clamp Earth Resistance Tester Instruction Manual

Models: UT271A, UT271B, UT271C

Brand: UNI-T

1. Introduction

The UNI-T UT271 series Clamp Earth Resistance Tester is a professional instrument designed for measuring grounding resistance and leakage current. This manual provides essential information for the safe and effective operation, maintenance, and troubleshooting of your device. Please read this manual thoroughly before use and keep it for future reference.

Three UNI-T UT271 series clamp earth resistance testers (UT271A, UT271B, UT271C) displayed side-by-side.

Figure 1: UNI-T UT271 Series Clamp Earth Resistance Testers

2. Safety Information

Always observe safety precautions when using electrical testing equipment. Failure to do so may result in injury or damage to the instrument.

  • Ensure the device is in good working condition before each use.
  • Do not operate the device in wet environments or explosive atmospheres.
  • Wear appropriate personal protective equipment, such as insulated gloves, when performing measurements.
  • The device features double insulation for enhanced safety.
  • This product is certified with CE, FCC, RoHS, UL, KC, pse, and WEEE standards.

3. Product Overview and Features

The UT271 series offers robust features for accurate and efficient earth resistance and current measurements.

Diagram showing main features of the UNI-T UT271 series: grounding resistance measurement, current measurement (UT271B/UT271C), 500 sets data storage, resistance+current same-screen display, double insulation, fast self-test.

Figure 2: Main Features of the UT271 Series

Key Features:

  • Grounding Resistance Measurement: Accurate measurement of earth resistance.
  • Current Measurement: (UT271B/UT271C only) Measures AC current.
  • Data Storage: Stores up to 500 sets of measurement data.
  • Same-Screen Display: Displays both resistance and current simultaneously for improved efficiency.
  • Double Insulation: Provides enhanced safety during operation.
  • Fast Self-Test: Quick self-inspection function to verify accuracy.
  • 32mm Circular Jaw: Suitable for grounding busbar measurements in most countries and regions.
  • Large Screen LCD Backlit Display: LCD size 46mm × 36mm, easily readable in various lighting conditions.
Close-up of the UNI-T UT271C clamp meter showing a 32mm circular jaw clamping around a rebar, with a red circle indicating the 32mm diameter.

Figure 3: 32mm Circular Jaw

Close-up of the UNI-T UT271C clamp meter's LCD screen showing resistance and current readings simultaneously, with a blue glow indicating backlighting.

Figure 4: Large Screen LCD Backlit Display

4. Setup

4.1 Unpacking and Contents

Upon opening the package, verify that all items are present and undamaged:

  • Main Unit (UT271A, UT271B, or UT271C)
  • Test Loop (1Ω & 10Ω)
  • Carrying Bag
  • User Manual
  • Warranty Card
Image showing the packing list contents: UNI-T UT271 clamp meter, carrying bag, user manual, warranty card, and two standard test rings (1 Ohm and 10 Ohm).

Figure 5: Packing List

Two black rectangular test loops, labeled 'Test loop (1Ω)' and 'Test loop (10Ω)' respectively.

Figure 6: Standard Test Loops (1Ω and 10Ω)

4.2 Battery Installation

The device requires four 1.5V AA batteries for operation. Batteries are not included and must be purchased separately. Refer to the battery compartment for correct polarity when installing.

4.3 Self-Inspection

Before performing critical measurements, it is recommended to conduct a self-inspection using the provided standard test rings to ensure the equipment is working accurately.

  1. Clamp the meter around the 1Ω test ring and observe the reading.
  2. Clamp the meter around the 10Ω test ring and observe the reading.
  3. Compare the readings with the expected values (1Ω and 10Ω).
Two images side-by-side demonstrating the self-inspection process. On the left, a UNI-T UT271C clamp meter is clamped around a 1 Ohm test ring, displaying '010 AC 1.0 Ohm 0.00 A'. On the right, the same meter is clamped around a 10 Ohm test ring, displaying '010 AC 10.0 Ohm 0.00 A'.

Figure 7: Self-Inspection with 1Ω and 10Ω Test Rings

5. Operating Instructions

The UT271 series is designed for ease of use. Familiarize yourself with the controls:

Diagram of the UNI-T UT271C clamp meter highlighting its components: jaw, Power on/off/exit button, Lock/Release Display Key, trigger, and LCD display screen.

Figure 8: Product Appearance Structure

  • Jaw: Opens to clamp around conductors for measurement.
  • Power On/Off/Exit Button: Turns the device on or off, and exits menus.
  • MEM Button: Accesses memory functions for data storage.
  • HOLD Button: Freezes the current display reading.
  • Trigger: Used to open the jaw.
  • LCD Display Screen: Shows measurement readings and status indicators.

5.1 Measurement Methods

5.1.1 Single Point Grounding System (Two-Point Method)

This method is used when a separate grounding body (RB) with good grounding performance is available, such as nearby metal water pipes, fire hydrants, or roof lightning strips. The grounding resistance values of these auxiliary points are typically very small and can be ignored.

  1. Locate the grounding body under test (RA) and a suitable auxiliary grounding body (RB).
  2. Connect RA and RB with a test line.
  3. Clamp the UT271 meter around the test line and read the grounding resistance.
  4. If the instrument reading during the two-point test is less than the required value of the tested grounding system, then both RA and RB are considered qualified.
Diagram illustrating the two-point method for single point grounding system measurement. A UNI-T clamp meter is shown connected between two grounding rods labeled RA and RB.

Figure 9: Single Point Grounding System (Two-Point Method)

5.1.2 Single Point Grounding System (Three-Point Method)

This method is used for more precise measurements or when a suitable auxiliary grounding body for the two-point method is not available. The principle is based on the formula: RA = (R1 + R3 - R2) ÷ 2, where R1, R2, and R3 are resistances measured between different pairs of grounding bodies (RA, RB, RC).

  1. First Step: Connect RA and RB with a test wire and read the first data R1 using the clamp gauge.
  2. Second Step: Connect RA and RC with a test wire and read the second data R2 using the clamp gauge.
  3. Third Step: Connect RB and RC with a test wire and read the third data R3 using the clamp meter.
  4. Calculate RA using the formula: RA = (R1 + R3 - R2) ÷ 2.
Diagram illustrating the three-point method for single point grounding system measurement. It shows three grounding rods (A, B, C) and a UNI-T clamp meter. The diagram details three steps for connecting the meter between different pairs of rods to obtain R1, R2, and R3 readings.

Figure 10: Single Point Grounding System (Three-Point Method)

5.1.3 Multi-Point Grounding System

This method is applicable for complex grounding systems such as those found in transmission towers, communication cable grounding systems, and certain buildings. These systems are typically connected through overhead ground wires (shielding layers of communication cables) to form a comprehensive grounding network.

Diagram illustrating a multi-point grounding system measurement. A UNI-T clamp meter is shown measuring current in a system with multiple grounding points connected via overhead wires, with an equivalent circuit diagram below.

Figure 11: Multi-Point Grounding System

5.1.4 Loop Resistance Definition

The loop resistance encompasses the combined value of the grounding resistance of point A to ground, the resistance of the grounding down-lead metal conductor, the resistance of the metal overhead line, the connection resistance between the grounding downlead and the metal overhead line, and the grounding resistance of point B to ground. For example, if the instrument detects a combined value of 5 ohms for the grounding loops of grid A and grid B, that is, RA + RB + Roverheadline + Rgroundingdown-lead = 5.0Ω, then the grounding resistance of grid A and grid B combined to ground must be less than or equal to 2.5Ω.

Diagram illustrating the definition of loop resistance in a grounding system, showing two grounding grids (A and B) connected by an overhead line and a down-lead, with various resistance components labeled.

Figure 12: Loop Resistance Definition

5.2 Application Examples

The UT271 series is versatile and can be used in various scenarios:

  • Measurement of tower earthing resistance.
  • Measurement of Grounding Resistance of Charging Pile.
  • Measurement of AC current of distribution cabinet.
  • Measurement of leakage current of circuit breaker.
Four images showing the UNI-T UT271 series in different application scenarios: measuring tower earthing resistance, grounding resistance of a charging pile, AC current of a distribution cabinet, and leakage current of a circuit breaker.

Figure 13: Application Scenarios

The following table provides grounding standards for various common scenarios:

Table showing grounding standards for various common scenarios, including independent lightning protection, safety protection, AC/DC working earthing, anti-static, common earthing electrode, ground resistance of military facilities, and lightning protection for plant equipment.

Figure 14: Grounding Standards for Various Common Scenarios

6. Maintenance

  • Cleaning: Use a soft, dry cloth to clean the instrument. Do not use abrasive cleaners or solvents.
  • Storage: Store the device in a cool, dry place. The recommended storage temperature is -10°C to 60°C, with humidity below 80% RH.
  • Battery Replacement: Replace batteries promptly when the low battery indicator appears to ensure accurate measurements.

7. Troubleshooting

  • No Display/Power On: Check battery installation and ensure batteries are not depleted.
  • Inaccurate Readings: Perform a self-inspection using the 1Ω and 10Ω test rings. Ensure proper clamping and contact with the conductor.
  • 'Noise' Symbol Displayed: The device automatically identifies interference signals. Try to minimize external electrical interference.
  • 'MEM' Symbol Flashing: Indicates that the data storage is full. Clear stored data if new measurements need to be saved.
  • 'OL' Indication: Indicates an overload condition. The measured value exceeds the device's range.

8. Specifications

Below are the technical specifications for the UNI-T UT271 series Clamp Earth Resistance Testers:

FunctionRangeResolutionAccuracyUT271AUT271BUT271C
Resistance0.01Ω-0.099Ω0.001Ω±(1%rdg+0.01Ω)√√√
0.10Ω-0.99Ω0.01Ω±(1%rdg+0.01Ω)√√√
1.0Ω-49.9Ω0.1Ω±(1%rdg+0.1Ω)√√√
50.0Ω-99.5Ω0.5Ω±(1.5%rdg+0.5Ω)√√√
100Ω-199Ω1Ω±(2%rdg+1Ω)√√√
200Ω-395Ω5Ω±(2.5%rdg+5Ω)√√√
400Ω-590Ω10Ω±(10%rdg+10Ω)√√√
Current0.00mA-9.99mA0.01mA±(2.5%rdg+1mA)√√
10.0mA-99.9mA0.1mA±(2.5%rdg+10mA)√√
0.30A-2.99A0.01A±(2.5%rdg+0.1A)√√
3.0A-9.9A0.1A±(2.5%rdg+0.5A)√√
SourceDC 6V, No.5 alkaline dry battery (LR6 1.5V×4)
Jaw SizeΦ32mm
Ω + A Same Screen DisplaySupporting (UT271B, UT271C)
Data Storage500 sets
Jamming TestAutomatically identify interference signals, indicated by the "Noise" symbol when the interference current is high
Battery VoltageLow battery voltage symbol reminder
Power ConsumptionMax is about 80mA
Time of MeasurementOnce per second
LCD Size46mm×36mm
Caliper Gauge Size260mm×105mm×60mm
Insulation Resistance20MΩ or above (500V between circuit and casing)
Withstand VoltageAC 3700Vrms (Between circuit and enclosure)
Weight of Caliper MeterApproximately 818g (including battery)
Operating Temperature and Humidity-10°C ~ 40°C; Below 80% RH
Storage Temperature and Humidity-20°C ~ 60°C; Below 80% RH
External Magnetic Field and Electric Field<40A/m; <1V/m
Suitable for Safety RegulationsIEC61010-1 (CAT Ⅲ 300V, CAT Ⅳ 150V, pollution degree 2); IEC61010-031; IEC61557-1 (grounding resistance); JJG 1054-2009 Verification Regulation for Clamp Grounding Resistance Meter

Figure 15: Product Technical Specifications

9. User Tips

  • For consistent and reliable measurements, always ensure the test points are clean and free from rust or corrosion.
  • When measuring in areas with potential electrical interference, try to perform measurements at different times or locations to confirm readings.
  • Regularly check the battery level, especially before extended use, to avoid interruptions during critical measurements.

10. Warranty and Support

Your UNI-T UT271 series Clamp Earth Resistance Tester comes with a standard manufacturer's warranty. Please refer to the included Warranty Card for specific terms and conditions. For technical support, service, or additional product information, please visit the official UNI-T website.

Video 1: Official UNI-T UT271 Series Product Overview and Application Demonstration

Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.