Chiller Controller K.SF305000A

Contents

K.SF305000A Chiller Controller Instruction Manual

Model: K.SF305000A (Compatible with GW511)

1. Product Overview

The K.SF305000A is a versatile control board designed for frozen water machines and industrial chillers. It functions as a central computer motherboard, managing various aspects of the chiller's operation, including temperature control, compressor management, and error detection. This controller is compatible with the GW511 system and offers a robust solution for industrial cooling applications.

K.SF305000A Main Control Board
Figure 1.1: K.SF305000A Main Control Board. This image shows the main circuit board with various terminals, relays, and components. The Chinese text translates to 'Chiller Main Board, Model: SF.305000A, Can replace GW511'.
K.SF305000A Display Board
Figure 1.2: K.SF305000A Display Board. This image displays the digital readout board with multiple 7-segment displays and control buttons.
K.SF305000A Chiller Computer Control Board Set
Figure 1.3: K.SF305000A Chiller Computer Control Board Set. This image shows the main board, display board, and the front panel overlay, indicating a complete control unit.

2. Specifications

The following table details the technical specifications of the K.SF305000A chiller controller:

K.SF305000A Specifications Table
Figure 2.1: K.SF305000A Specifications Table. This image provides a detailed table of electrical and environmental specifications.
Table 2.1: K.SF305000A Technical Specifications
No. Parameter Description
1 Power Supply 220V AC ±10%, 50/60Hz
2 Temperature Range -40°C to 100°C
3 Measurement Accuracy 0.1°C @ 25°C
4 Operating Environment -20°C to 70°C, ≤85% RH (non-condensing)
5 Storage Environment -30°C to 85°C, ≤85% RH (non-condensing)
6 Relay Output 4-way relay
7 Switch Signal Input 8-way switch signal
8 Analog Input 1-way NTC temperature probe
9 Current Input 4-way current (0.3~35A)

3. Installation and Setup

Proper installation is crucial for the safe and effective operation of the K.SF305000A controller. It is recommended that installation be performed by a qualified technician.

3.1 Component Identification

  • Main Control Board: The primary circuit board with all major connections.
  • Display Board: The digital display and button interface.
  • Panel Sticker/Overlay: Provides labels for buttons and display indicators.
  • Temperature Sensor Wire: NTC probe for temperature measurement. (Approx. 3mm diameter, 4.1m length).
  • Mounting Plate (Optional): Metal plate for secure installation of the control board.
  • GW122B Transformer (Optional): Original current transformer for current input.
K.SF305000A Four-Piece Set
Figure 3.1: K.SF305000A Four-Piece Set. Includes main board, display board, panel sticker, and temperature sensor wire.
K.SF305000A Five-Piece Set
Figure 3.2: K.SF305000A Five-Piece Set. Includes main board, display board, panel sticker, metal mounting plate, and temperature sensor wire.
Temperature Sensor Wire
Figure 3.3: Temperature Sensor Wire. This image shows the NTC temperature probe with its cable, approximately 4.1 meters long.
GW122B Original Transformer
Figure 3.4: GW122B Original Transformer. This image shows the current transformer, model GW122B.

3.2 Physical Installation

Refer to the dimension diagrams for precise mounting of the main board and display board.

Main Board and Display Board Installation Dimensions
Figure 3.5: Main Board and Display Board Installation Dimensions. This diagram provides detailed measurements for mounting the main control board (Figure 2.1) and the key/display board (Figure 2.2).
  • Mount the main control board securely within the chiller's electrical enclosure, ensuring adequate ventilation.
  • Install the display board in an accessible location on the chiller's front panel, using the provided panel sticker for labeling.
  • If using, attach the metal mounting plate to provide a stable base for the control board.
  • Route the temperature sensor wire to the desired measurement point within the chiller system.

3.3 Electrical Connections

Carefully follow the electrical connection diagram. Incorrect wiring can damage the unit or lead to unsafe conditions. Ensure power is disconnected before making any connections.

Electrical Connection Diagram
Figure 3.6: Electrical Connection Diagram. This detailed diagram illustrates the wiring for three-phase power input, AC220V connections, various sensor inputs (current, temperature), and compressor wiring for both single and dual compressor setups. Note: The diagram indicates that the number of compressors (single or dual) is set via parameter F-20.
  1. Power Input: Connect the three-phase power supply (R, S, T) and neutral (N) to the designated terminals (J3). Connect AC220V to J1.
  2. Output Connections: Connect chiller fan/pump, compressor 1, and compressor 2 to the respective relay outputs (COM1, COM2).
  3. Sensor Inputs:
    • Current Sensors: Connect current transformers (GW122B) for current detection (CUR1, CUR2).
    • Temperature Probe: Connect the NTC temperature probe to the NTC1 terminal.
    • Switch Signals: Connect various switch signals (e.g., water flow, high/low pressure, overload) to the J6 terminals as indicated.
  4. Display Board Connection: Connect the ribbon cable from the main board to the display board.

4. Operating Instructions

The control panel provides an intuitive interface for monitoring and adjusting chiller parameters.

Chiller Controller Panel Diagram
Figure 4.1: Chiller Controller Panel Diagram. This diagram shows the layout of the display, buttons, and indicator lights, along with a table of error codes.

4.1 Panel Overview

  • Display: Shows PV (Process Value - real-time temperature) and SV (Set Value - set temperature).
  • Indicator Lights:
    • POWER: Power indicator.
    • RUN: Running status.
    • ERROR: Fault indicator.
    • COMP1/COMP2: Compressor 1/2 running indicators.
  • Buttons:
    • RESET/MUTE: Reset faults or mute alarms.
    • PUMP: Control pump operation.
    • COMP1/COMP2: Enable/disable compressor 1/2.
    • OFF: Turn off the unit.
    • ADJUST (UP/DOWN): Adjust parameter values.
    • SET: Enter/confirm settings.

4.2 Basic Operation

  1. Power On: Ensure all connections are secure. Press the power button (if available, otherwise power is supplied directly). The POWER indicator should light up.
  2. Monitoring Temperature: The display will show the current real-time temperature (PV) and the set temperature (SV).
  3. Setting Temperature:
    • Press the SET button to enter parameter setting mode.
    • Use the UP and DOWN buttons to adjust the desired set temperature (SV).
    • Press SET again to confirm and exit.
  4. Compressor Control: Use the COMP1 and COMP2 buttons to manually enable or disable individual compressors if needed.
  5. Pump Control: Use the PUMP button to control the circulation pump.
  6. Shut Down: Press the OFF button to turn off the chiller controller.

5. Troubleshooting

The controller is equipped with diagnostic features to help identify and resolve operational issues. Refer to the error code table on the panel diagram (Figure 4.1) for specific fault indications.

5.1 Error Codes and Solutions

Table 5.1: Common Error Codes and Descriptions
Code Description Possible Cause / Solution
E01 Reverse phase Check three-phase power wiring for correct phase sequence.
E02 #1 Comp. high press Compressor 1 high pressure alarm. Check refrigerant, condenser, and fan.
E03 #1 Comp. low press Compressor 1 low pressure alarm. Check refrigerant, evaporator, and expansion valve.
E04 #2 Comp. high press Compressor 2 high pressure alarm. Check refrigerant, condenser, and fan.
E05 #2 Comp. low press Compressor 2 low pressure alarm. Check refrigerant, evaporator, and expansion valve.
E06 #1 Comp. overload Compressor 1 overload. Check current, motor, and power supply.
E07 #2 Comp. overload Compressor 2 overload. Check current, motor, and power supply.
E08 Cold medium short Refrigerant shortage or low level. Check refrigerant charge.
E09 Cold pump overload Chiller pump overload. Check pump motor and current.
E10 Cool pump overload Cooling pump overload. Check pump motor and current.
E11 Cold medium short Refrigerant shortage or low level. Check refrigerant charge.
E12 Low temp. Low temperature alarm. Check setpoint, refrigerant, and heat load.
E13 Sensor open Temperature sensor circuit open. Check sensor wiring and connection.
E14 Sensor short Temperature sensor circuit short. Check sensor wiring and connection.
E15 Freezing Freezing alarm. Check water flow, temperature setpoint, and anti-freeze settings.

5.2 General Troubleshooting Tips

  • No Power: Check power supply, circuit breakers, and wiring connections.
  • Display Not Working: Ensure the ribbon cable connecting the main board and display board is properly seated.
  • Compressor Not Starting: Check for error codes, ensure set temperature is below current temperature, and verify compressor enable settings.
  • Inaccurate Temperature Reading: Inspect the NTC temperature probe for damage or improper placement.
  • Persistent Errors: If an error persists after attempting the suggested solutions, contact technical support.

6. Maintenance

Regular maintenance helps ensure the longevity and optimal performance of your K.SF305000A chiller controller.

  • Keep Clean: Periodically clean the control board and display panel to prevent dust and debris buildup, which can affect performance and lead to overheating. Use a soft, dry cloth.
  • Environmental Conditions: Ensure the operating environment adheres to the specified temperature and humidity ranges (-20°C to 70°C, ≤85% RH non-condensing) to prevent damage to electronic components.
  • Connection Checks: Annually inspect all electrical connections for tightness and signs of corrosion. Re-tighten as necessary.
  • Sensor Integrity: Verify that temperature probes and current transformers are securely connected and free from physical damage.
  • Software/Firmware: While not user-serviceable, be aware that some industrial controllers may have firmware updates. Consult with a professional if you suspect a software-related issue.

7. User Tips

  • Professional Installation: Due to the electrical nature and complexity of chiller systems, it is highly recommended to have this controller installed by a qualified electrician or HVAC technician.
  • Parameter Backup: Before making significant changes to settings, note down the original parameters. This allows for easy restoration if unintended issues arise.
  • Regular Monitoring: Periodically check the display for normal operation and any early warning signs of issues, such as unusual temperature fluctuations or intermittent error codes.
  • Consult Documentation: For advanced settings or specific chiller configurations, always refer to the complete system documentation provided by your chiller manufacturer.

8. Warranty and Support

For any technical assistance, warranty claims, or further inquiries regarding the K.SF305000A chiller controller, please contact your point of purchase or the manufacturer's customer support. Ensure you have your product model number and any relevant purchase details available when seeking support.

This product is intended for use by trained professionals in industrial settings. Improper installation or use may void the warranty and pose safety risks.