PEAKMETER MS5910

Contents

PEAKMETER MS5910 Digital RCD/Loop Resistance Tester

User Instruction Manual

1. Introduction

The PEAKMETER MS5910 is a compact, firm, and durable digital RCD/Loop Resistance Tester designed for electrical inspection and repair. It incorporates the latest technology to provide reliable and accurate measurements for various electrical parameters. This manual provides detailed instructions for the safe and effective use of your MS5910 tester.

Front view of the PEAKMETER MS5910 RCD/Loop Tester
Figure 1: Front view of the PEAKMETER MS5910 RCD/Loop Tester.

2. Key Features

  • Measures Trip-Out Current, Trip-Out Time, Contact Voltage, and Loop Resistance.
  • Capable of storing up to 100 groups of test results.
  • Data can be transmitted to a PC via a USB 2.0 interface.
  • Features backlight indication for improved visibility.
  • Automatic Power Off function to conserve battery life.
  • Auto/manual ranging for flexible measurements.
  • Equipped with overheating and low battery voltage alarms.
  • High reliability, stability, and accuracy for professional use.
PEAKMETER MS5910 highlighting its measurement capabilities
Figure 2: MS5910 highlighting its measurement capabilities.

3. Package Contents

Please check the package carefully to ensure all items are present and undamaged:

  • 1 x RCD/LOOP Tester MS5910 (batteries not included)
  • 1 x Test Lead set
  • 3 x Crocodile Clips (red, green, black)
  • 1 x USB Cable
  • 1 x CD (containing software/drivers)
  • 1 x Instruction Manual
  • 1 x Black Carrying Bag
  • 1 x Lanyard
MS5910 device with included accessories
Figure 3: MS5910 device with included accessories.

4. Setup

  1. Battery Installation: The MS5910 requires 6x 1.5V AA batteries (not included). Open the battery compartment cover on the back of the device, insert the batteries according to the polarity indicators, and securely close the cover.
  2. Connecting Test Leads: Connect the test leads to the appropriate input terminals on the tester. Ensure a secure connection. The crocodile clips can be attached to the test leads for easier connection to circuits.
  3. USB Connection (Optional): For data transfer to a PC, connect the provided USB cable to the USB interface on the rear of the MS5910 and to your computer. Install the necessary drivers and software from the included CD.
Rear view of the MS5910 showing AC input and USB interface
Figure 4: Rear view of the MS5910 showing AC input and USB interface.
MS5910 with test leads connected
Figure 5: MS5910 with test leads connected.

5. Operating Instructions

The MS5910 features a rotary switch and several buttons for selecting functions and performing measurements.

  1. Power On/Off: Rotate the main dial from 'OFF' to any measurement function to power on the device. Return the dial to 'OFF' to power off.
  2. Function Selection: Use the large rotary switch to select the desired measurement mode (e.g., LOOP, RCD x1/2, x1, x5, AUTO RAMP).
  3. Measurement Parameters: Use the 'SET' button and arrow keys to adjust specific parameters like multiplying power (0.5, 1, 5) or standard/selective current levels (10, 30, 100, 300, 500mA).
  4. Initiating Measurement: Press the 'MEASURE' button to start a test. The results will be displayed on the LCD screen.
  5. Reading and Storing Data:
    • Press 'READ' to view stored data.
    • Press 'MEMO' to store the current measurement result. The device can store up to 100 groups of test results.
    • Press 'CLEAR' to delete stored data.
  6. Display Backlight: Press the 'LIGHT' button to toggle the display backlight.
  7. Display Options: Use the 'DISPLAY' button to cycle through different display modes or information.
  8. Slow Mode: The 'SLOW' button may be used for specific tests requiring a slower measurement cycle.
  9. Data Transfer: Connect the device to a PC via the USB cable and use the provided software to download stored data.

6. Specifications

ParameterValue
BrandPEAKMETER
ModelMS5910
AC Voltage Measurement0V - 440V
Frequency MeasurementDC, 45Hz - 65Hz
Multiplying Power of Measurement Current0.5, 1, 5
Standard/Selective Type Current Measurement Level10, 30, 100, 300, 500mA
Power Supply6x 1.5V AA batteries (not included)
Storage Elevation12,000m
Usage Elevation2,000m CAT III 600V; 3,000m CAT II 600V
Dimensions (L*W*H)195mm * 155mm * 80mm (7.68in * 6.1in * 3.15in)
WeightApproximately 2194g (2.194 kg)
Dimensions of the MS5910 RCD/Loop Tester
Figure 6: MS5910 dimensions.

7. Troubleshooting

  • Low Battery Voltage Alarm: If the low battery indicator appears, replace all 6x AA batteries immediately to ensure accurate measurements and proper device function.
  • Overheating Alarm: If an overheating alarm is triggered, discontinue use and allow the device to cool down in a well-ventilated area before resuming operation. Ensure proper ventilation during use.
  • Loop Resistance Measurement (RL) below 3 ohms: The MS5910 supports loop resistance (RL) measurement and can display values at a minimum of 3 ohms. This model does not support measurement results of 1-2 ohms. If you require measurements in this range, this device may not be suitable.
  • No Display/Device Not Powering On: Check battery installation and ensure batteries are fresh. Verify the rotary switch is set to a measurement function and not 'OFF'.

8. User Tips

  • RCD Type Compatibility: The MS5910 is designed for general RCD testing. If you are testing specific types of RCDs (e.g., Type A, Type B), ensure the tester's capabilities align with the RCD type. The device primarily tests AC type differentials.
  • Data Management: Regularly transfer stored data to your PC to keep records and free up device memory. Organize your test results for easy retrieval and analysis.
  • Environmental Conditions: Always operate the device within the specified usage elevation and temperature ranges to maintain accuracy and prolong its lifespan.

9. Maintenance

  • Cleaning: Clean the device regularly with a soft, dry cloth. Do not use abrasive cleaners or solvents.
  • Storage: When not in use for extended periods, remove the batteries to prevent leakage and store the device in its carrying bag in a cool, dry place, away from direct sunlight and extreme temperatures.
  • Calibration: For professional use, periodic calibration by a qualified service center is recommended to ensure continued accuracy.
  • Test Leads: Inspect test leads and crocodile clips for any signs of wear, damage, or frayed insulation before each use. Replace damaged accessories immediately.

10. Warranty and Support

For warranty information, technical support, or service inquiries, please refer to the documentation provided with your purchase or contact the manufacturer/seller directly. Keep your purchase receipt as proof of purchase.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.