1. Introduction
Thank you for purchasing the HLTNC 2.2KW Air Cooled Spindle Motor and EV210 Inverter VFD Kit. This kit is designed for CNC engraving applications, providing high performance and reliability. The EV210 series of high-performance current vector frequency converters are primarily used to control and regulate the speed and torque of three-phase AC asynchronous motors. They support various PG cards and are suitable for a wide range of automated production equipment, including textile, paper, wire drawing, machine tools, packaging, food, fans, and pumps.
This manual provides detailed information on the functional characteristics, usage methods, product selection, parameter setting, operation debugging, and maintenance inspection of the EV210 series frequency converters. Please read this user manual carefully before use to ensure safe and correct operation.
2. Safety Information and Precautions
When installing, commissioning, and maintaining this system, users must carefully read and follow all safety precautions. The manufacturer is not responsible for any injury or loss resulting from the violation of operating procedures.
2.1 Marking and Definition of Safety Information
| Marking | Definition |
|---|---|
| Danger | Indicates an accident that may result in death or serious injury if not performed as required. |
| Warnings | Indicates that failure to operate as required will result in moderate personal injury or minor injury and some material loss. |
| Note | Indicates matters that need attention in operation or use. |
| Prohibited | Indicates something that is absolutely not allowed to be done. |
| Compulsion | Indicates something that must be done. |
2.2 General Safety Matters
- The inverter is suitable for general industrial three-phase AC asynchronous motors.
- Do not use this inverter in equipment where a malfunction could pose a threat to life or human health (e.g., nuclear power control, aerospace, life support systems). Consult the company for special applications.
- This product is manufactured under strict quality management. For critical equipment, additional safety protection measures must be in place.
- Install in an indoor, well-ventilated location, generally vertically for optimal cooling.
- Ambient temperature should be between -10°C and 40°C. If exceeding 40°C, remove the top cover. If exceeding 50°C, external forced cooling or derating is required.
- Ambient humidity should be below 95% and no water droplets should condense.
- Install in a place with vibration less than 0.5G to prevent drop damage. Avoid sudden impacts.
- Install in an environment away from electromagnetic fields and free of flammable and explosive substances.
- Do not work with wet hands.
- Wiring work must not be done when the power is not fully disconnected.
- Do not open the face cover or perform wiring while the inverter is powered on, as there is a risk of electric shock.
- Wiring, inspection, and other operations must be carried out 10 minutes after the power is turned off.
- Do not install a frequency converter with damaged or missing components.
- The main circuit terminals must be securely connected to the cable to prevent damage to the inverter.
- Grounding terminals must be reliably grounded. For multiple frequency converters, use one-point grounding.
- Do not connect an AC power supply to the output terminals (U, V, W) of the inverter.
- Install a fuseless circuit breaker for circuit protection on the input power side.
- Avoid installing electromagnetic contactors on the output side of the frequency converter during operation.
- For inverters stored for over a year, gradually increase voltage to the rated value with a voltage regulator when powering on.
- Do not touch the inside of the inverter or insert objects into it when powered on.
- Use the power-off restart function with caution.
- If operating beyond 50Hz, ensure the speed range of motor bearings and mechanical devices is compatible.
- Mechanical devices requiring lubrication should not be operated at low speeds for long periods.
- For ordinary motors operating at low frequencies, derating or forced heat dissipation may be required.
- Do not install capacitors or surge current absorbers at the output end of the frequency converter.
- Before first use or after long storage, perform an insulation check on the motor (resistance ≥ 5MΩ).
- For altitudes over 1000 meters, derate the inverter by about 10% for every 1000 meters of elevation.
3. Product Information
3.1 Kit Configuration
- 2.2KW Square engraving machine Spindle with edges (Junction box)
- 2.2KW EV210 Inverter
- ER20A Spanner
3.2 Technical Specifications
The following tables detail the specifications for the 2.2KW air-cooled square spindle and the EV210 Inverter.
For detailed technical specifications, refer to Chapter 2.2 of the full user manual.
3.3 Dimensions
The physical dimensions of the spindle motor and inverter are provided below for installation planning.
3.4 Brake Resistor Selection
Refer to Chapter 2.5 of the full user manual for the Brake Resistor Selection Table. Ensure to select the resistance value specified by the manufacturer. The installation of the brake resistor must consider safety and flammability, keeping it at least 100mm away from the frequency converter.
4. Storage and Installation
4.1 Storage
- Store the product in its original packing box in a dust-free, dry location.
- Ambient storage temperature: -20°C to +65°C.
- Relative humidity: 0% to 95%, non-condensing.
- Storage environment must be free of corrosive gases and liquids.
- For long-term storage, power on the inverter once every half a year for at least 5 hours, gradually increasing the input voltage to the rated value using a voltage regulator.
4.2 Installation Location and Environment
- Install in a well-ventilated area, free from dripping, low temperatures, direct sunlight, high temperatures, heavy dust, corrosive gases, liquids, oil vapor, and metal shavings.
- Choose a vibration-free location that is easy to maintain and inspect, and free from electromagnetic noise.
4.3 Installation Space and Orientation
- Ensure sufficient space around the inverter for maintenance.
- Install the inverter vertically for optimal cooling and air circulation.
- The mounting wall should be made of non-combustible materials (e.g., iron plates).
- When installing multiple inverters in the same cabinet, ensure proper spacing and consider adding baffles or staggering their alignment.
5. Wiring
Accurate wiring is crucial for the safe and proper operation of the spindle motor and inverter. Refer to the diagrams and precautions below.
5.1 Basic Running Wiring Diagram
The inverter wiring consists of a main circuit and a control circuit. Connect them precisely according to the following diagram.
This diagram illustrates the connections between the power input, circuit breaker, inverter (EV210), spindle motor, braking resistor, and control terminals for analog input, RS485 communication, and relay output.
5.2 Terminal Diagram and Jumper Settings
The control loop terminal arrangement and main control board jumper settings are detailed below.
This image shows the jumper settings for J1, J2, J4, and J5, which control grounding, analog output signals, potentiometer selection, and analog input signals respectively.
5.3 Wiring Precautions
- Main Circuit Wiring:
- Select wire diameters according to electrical regulations.
- Use isolation wires or conduits for power wiring, grounding both ends.
- Install an air circuit breaker (NPB) between the power supply and input terminals (R, S, T). Use a leakage circuit breaker with high-frequency countermeasures if applicable.
- Keep power lines and control lines separate; do not place in the same conduit.
- Do not connect AC power to the output terminals (U, V, W) of the inverter.
- Output wiring must not touch metal parts of the inverter housing.
- Do not use components like phase-shifting capacitors, LC, or RC noise filters at the inverter output.
- Keep main circuit wiring away from other control devices.
- For long wiring (over 50m for 220V, 100m for 380V), use an AC motor dedicated to the inverter or install a reactor on the inverter side.
- Reduce carrier frequency for long distances to minimize harmonic leakage current.
- Control Circuit Wiring (Signal lines):
- Signal lines must not be placed in the same wire slot as main circuit wiring.
- Shield and ground signal lines at one end (0.5-2mm² diameter). 1mm² shielded wire is recommended for control lines.
- Ground Wire:
- Grounding terminal E should be grounded in the third type of grounding (below 100Ω).
- Grounding wire should be as short as possible and kept away from power lines of large electrical equipment.
- Ground terminal E must be properly grounded and never connected to the neutral wire.
5.4 Specific Application Precautions
- Reactor Installation: Install a DC or AC reactor if connecting to a large capacity power transformer (600kVA or more) or if the same power supply system is connected to thyristor converters.
- Inverter Capacity: Ensure the motor's rated current does not exceed the inverter's rated output current. For multiple motors, the combined rated current should be less than 1.1 times the inverter's rated output current.
- Starting Torque: If a larger starting torque is required, increase the capacity of the inverter by one size or increase the capacity of both the motor and the inverter.
- Emergency Stop: Set up a mechanical stop/hold structure on equipment requiring emergency stops, as the inverter's protection function does not guarantee an immediate stop.
- Reciprocating Loads: For reciprocating loads, reduce the carrier frequency and peak current to less than 150% to extend IGBT lifespan. Adjust acceleration/deceleration times or increase inverter capacity.
- Motor Use: For standard motors, reduce load torque at low speeds. For pole-changing motors, confirm maximum current and switch poles only when the motor is stopped. For motors with brakes, use an independent brake power supply.
- Power Transmission Structure: For oil-lubricated gearboxes, ensure proper lubrication at low speeds. Be aware of noise, lifespan, and strength issues at high speeds (above 60Hz).
6. Operations and Displays
6.1 Operation Panel Overview
6.2 Key Instructions
| Key Symbol | Name | Feature Description |
|---|---|---|
| PRG | Programming keys | Menu entry or exit, parameter modification |
| ENTER | Determine the key | Go to the menu and confirm parameter settings |
| ▲ | Incrementing keys | Increment data or function code |
| ▼ | Decrement key | Decrement of data or function code |
| RUN/▶ | Run keys | Run/Shift operations in keyboard operation mode |
| STOP/RESET | Stop/Reset key | Stop/reset operation, or shift key to view displayed content when main interface is stopped |
6.3 Initial Parameter Settings
For initial setup, apply the following parameter settings:
- P0-10 = 400
- P0-12 = 400
- P1-04 = 400
- P1-05 = 24000
- P7-03 = H.401F
- P7-12 = 20
- P7-06 = 0.6000
After making these changes, press the “run” button to apply and switch until the desired speed is reached. The EV210 frequency converter will display the speed changes.
To perform a factory reset, set parameter PP-01 = 2.
6.4 Motor Parameter Self-Learning
When using vector control operation mode, accurately input the motor's nameplate parameters. Vector control performance is highly dependent on these parameters. To achieve optimal control, ensure accurate parameters of the controlled motor are obtained.
6.5 Running Test Video
A running test video demonstrating the setup and operation is available:
This video demonstrates the unboxing, wiring, parameter setting, and operation of the spindle motor and inverter kit.
7. Functional Parameter Table
The EV210 inverter features extensive functional parameters organized into groups (P0, P1, P2, etc.). These parameters control various aspects of the inverter's operation, including motor control mode, frequency sources, acceleration/deceleration times, motor characteristics, and fault protection settings.
For a complete list and detailed descriptions of all functional parameters, please refer to the full EV210 series User Manual (PDF) available for download: EV210 User Manual (PDF).
The PDF manual contains detailed tables for:
- Brief Table of Basic Functional Parameters (Chapter 6.1, pages 28-30)
- Brief Table of Monitoring Parameters (Chapter 6.2, pages 55-61)
- Modbus Communication Protocol (Appendix 1, pages 68-81)
- Instructions for Macro Parameter Settings (Appendix 2, page 81)
8. EMC (Electromagnetic Compatibility)
Electromagnetic compatibility (EMC) ensures that electrical equipment operates stably in an environment with electromagnetic interference without interfering with other equipment. The EV210 series converters comply with IEC/EN61800-3:2004 standards.
8.1 EMC Guidance
- Harmonics Effects: Install an AC input reactor in areas with poor grid quality to mitigate higher harmonics.
- Electromagnetic Interference and Installation Precautions:
- Ensure proper grounding for the frequency converter and other electrical products.
- Avoid arranging power input/output lines and weak current signal lines in parallel; arrange vertically if possible.
- Use shielded cables or steel pipes for output power lines, with reliable grounding. Use twisted-pair shielded control lines for disturbed equipment.
- For motor cables longer than 100 meters, install an output filter or reactor.
- Dealing with Interference from Peripheral Equipment:
- Install a surge suppressor on interfering devices.
- Install a filter at the input of the frequency converter.
- Shield and reliably ground control signal lines and detection lines.
- Leakage Current: Reduce distributed capacitance by minimizing distance between inverter and motor. Lower carrier frequency to reduce leakage current, but note this may increase motor noise. Install an output reactor if necessary.
- EMC Input Filter Installation: Use filters strictly according to rated values. Ensure the metal casing of the filter has good contact with the metal ground of the installation cabinet. Connect the filter's ground to the PE terminal ground of the frequency converter. Install the filter as close as possible to the inverter's power input.
9. Troubleshooting
If an anomaly occurs during operation, the inverter will block PWM output, enter fault protection, and display a flashing fault code on the keyboard, with the ALM indicator lit. Refer to the table below for common fault codes and countermeasures. If the problem persists, contact customer support.
For a comprehensive list of fault diagnoses and countermeasures, please refer to Chapter 8 of the full EV210 series User Manual (PDF) available for download: EV210 User Manual (PDF).
| Faults Name | Operation Panel Display | Troubleshooting | Countermeasures |
|---|---|---|---|
| Inverter unit protection | FU01 | Short circuit in output, long wiring, module overheating, loose wiring, main control board abnormality, driver board abnormality. | Eliminate peripheral faults, install reactor/filter, check air duct/fan, plug in all wires, seek technical support. |
| Accelerate overcurrent | FU02 | Ground/short circuit in output, incorrect control mode/parameter ID, short acceleration time, inappropriate torque boost, low voltage, rotating motor, sudden load increase, inverter too small. | Eliminate peripheral faults, perform motor parameter ID, increase acceleration time, adjust torque boost/V/F curve, adjust voltage, select speed tracking start, cancel sudden load, use larger inverter. |
| Under-voltage fault | FU09 | Momentary power outage, input voltage out of range, abnormal bus voltage, rectifier/buffer resistor malfunction, driver board abnormality, control board abnormality. | Reset faults, adjust voltage, seek technical support. |
| Inverter overload | FU10 | Load too heavy/motor locked, inverter too small. | Reduce load, check motor/machinery, use higher power rating inverter. |
| Module overheating | FU14 | High ambient temperature, air duct blockage, damaged fan, module thermistor damage, inverter module damaged. | Reduce ambient temperature, clean air ducts, replace fan, replace thermistor, replace inverter module. |
10. User Tips
- The spindle motor and inverter kit is generally well-packed and arrives in good condition.
- The build quality is often excellent, with smooth operation and low vibration.
- Ensure to verify all components against the description upon arrival.
- If you encounter any issues with delivery or product functionality, contact the seller directly.
- The kit is complete with the inverter (falownik) as advertised.
11. Warranty and Support
For warranty information, technical support, or any product-related inquiries, please contact the HLTNC Automation Store directly. Refer to your purchase documentation for specific contact details.
The company is committed to the continuous improvement of the product, and the product features will be continuously upgraded. The information provided is subject to change without further notice. (Revision Date: December 6, 2024)