Introduction

The PEAKMETER MS5910 is a compact, firm, and durable instrument designed for comprehensive RCD and loop resistance testing. It integrates the latest technology to provide high reliability, stability, and accuracy, making it an ideal tool for electrical inspection and repair. This manual provides detailed instructions for the safe and effective use of your MS5910 tester.

Key Features

  • Measures Trip-Out Current, Trip-Out Time, Contact Voltage, and Loop Resistance.
  • Storage capacity for 100 groups of test results.
  • USB2.0 interface for data transmission to PC.
  • Features Backlight Indication for clear visibility in various lighting conditions.
  • Automatic Power Off function to conserve battery life.
  • Auto/Manual Ranging for flexible measurement.
  • Overheating Alarm and Low Battery Voltage Alarm for user safety and convenience.

Package Contents

Verify that all items listed below are present and undamaged upon unpacking:

  • 1 x PEAKMETER MS5910 RCD/LOOP Tester
  • 1 x Test Lead
  • 3 x Crocodile Clips (Red, Green, Black)
  • 1 x USB Cable
  • 1 x CD (Software/Drivers)
  • 1 x Instructions Manual (Refer to the included PDF for detailed guidance: User Manual PDF)
  • 1 x Black Carrying Bag
  • 1 x Lanyard
PEAKMETER MS5910 tester and included accessories

Image: PEAKMETER MS5910 RCD/LOOP Tester with test lead, crocodile clips, and USB cable.

PEAKMETER MS5910 tester, carrying bag, and accessories

Image: PEAKMETER MS5910 RCD/LOOP Tester, carrying bag, test lead, crocodile clips, and USB cable.

Specifications

Technical specifications table for PEAKMETER MS5910

Image: Detailed technical indicators and RCD test current selection table.

General Specifications

  • Brand: PEAKMETER
  • AC Voltage Measurement: 0V-440V
  • Frequency Measurement: DC, 45Hz-65Hz
  • Multiplying Power of Measurement Current: 0.5, 1, and 5
  • Standard/Selective Type Current Measurement Level: 10, 30, 100, 300, 500mA
  • Power Supply: 6x 1.5V AA batteries (not included)
  • Storage Elevation: 12,000m
  • Usage Elevation: 2,000m CAT III 600V; 3,000m CAT II 600V
  • Dimensions: 195 x 155 x 80mm (7.68 x 6.1 x 3.15 inches)
  • Weight: Approximately 2194g (including packaging)

Detailed Technical Indicators

Technical IndicatorRangeAccuracyResolution
Tripping timex1 IΔN300 (slow 500ms)±3ms0.1ms
x5 IΔN40ms (slow 150ms)
Tripping current(0.2~1.1)IΔN±0.1 IΔN0.05 IΔN
Contact voltage0~99.9V±(10%+0.2V)0.01, 0.1V
AC voltage (UL-N, UL-L, UL-E)0~440V±(3%+3V)1V
FrequencyDC, 45~65Hz±1Hz1Hz
Loop resistance (RL)0~19.9Ω±(10%+0.2V)0.01Ω
10.0~99.9Ω0.1Ω
RL Test current0.5IΔN±(10%+10d)0.05IΔN
Test current multiplierx0.5, x1, x5
Current level (IΔN)10mA, 30mA, 100mA, 300mA, 500mA
Trigger phase Angle0° or 180°

RCD Tests Current Selection Table

IΔN (mA)IΔx1/2 (mA)IΔx1 (mA)IΔx5 (mA)Auto (mA)
105105010
30153015030
10050100500100
3001503001500300
500250500---------500

Setup

1. Battery Installation

  1. Ensure the device is powered off.
  2. Locate the battery compartment on the back of the tester.
  3. Open the battery cover.
  4. Insert 6x 1.5V AA batteries, observing correct polarity.
  5. Close the battery cover securely.
Back view of PEAKMETER MS5910 showing battery compartment and warning label

Image: Back view of the MS5910 tester, indicating the battery compartment and safety warnings.

2. Connecting Test Leads

  1. Connect the provided test lead to the appropriate input terminals on the tester.
  2. Attach the crocodile clips to the test lead ends as needed for your specific measurement. The red clip is typically for Live (L), green for Earth (PE), and black for Neutral (N) or other connections depending on the test.
Test lead and crocodile clips for PEAKMETER MS5910

Image: The test lead with red, green, and black crocodile clips.

Operating Instructions

Safety Warning: Always ensure the circuit under test is de-energized before making connections, unless the test specifically requires a live circuit (e.g., RCD testing). Follow all local electrical safety regulations.

1. Power On/Off

  • Press the 'LIGHT' button to turn on the backlight.
  • The device powers on automatically when a test mode is selected via the rotary switch.
  • The device features an Auto Power Off function to save battery.

2. RCD Testing (Trip-Out Current, Trip-Out Time, Contact Voltage)

  1. Connect the test leads to the circuit: Red to Live (L), Black to Neutral (N), Green to Earth (PE).
  2. Turn the rotary switch to the 'RCD' section. Select the desired current multiplier (x1/2, x1, x5) and nominal RCD current (IΔN) using the 'SET' button and arrow keys.
  3. For Trip-Out Time: Select the desired IΔN and multiplier. Press 'MEASURE'. The display will show the tripping time.
  4. For Trip-Out Current (Ramp Test): Select 'AUTO RAMP' on the rotary switch. Press 'MEASURE'. The tester will gradually increase current until the RCD trips, displaying the trip current.
  5. For Contact Voltage: This is typically measured during RCD tests. The tester will display the contact voltage (Uc) during the test sequence.

3. Loop Resistance Testing (L-N, L-PE, L-L)

  1. Connect the test leads according to the desired loop:
    • L-N: Red to Live, Black to Neutral.
    • L-PE: Red to Live, Green to Earth.
    • L-L: Red to Live 1, Black to Live 2 (for multi-phase systems).
  2. Turn the rotary switch to the 'LOOP' section and select the desired loop type (L-N, L-PE, L-L).
  3. Press 'MEASURE'. The display will show the loop resistance (RL).
  4. Note: The device supports loop resistance measurement from 3 ohms upwards. Measurements below 3 ohms (e.g., 1-2 ohms) are not supported.

4. Data Storage and Transfer

  1. To store a test result: After a measurement, press the 'MEMO' button. Use the arrow keys to select a memory location, then press 'ENTER'.
  2. To recall stored data: Press the 'READ' button. Use the arrow keys to navigate through stored results.
  3. To clear stored data: Press the 'CLEAR' button.
  4. To transfer data to PC: Connect the MS5910 to your computer using the provided USB cable. Install the software from the included CD. Follow the software instructions to download and analyze stored data.

Maintenance

1. Cleaning

  • Wipe the device with a soft, damp cloth. Do not use abrasive cleaners or solvents.
  • Ensure the device is dry before storage or next use.

2. Battery Care

  • Replace batteries when the Low Battery Voltage Alarm is indicated.
  • Remove batteries if the device will not be used for an extended period to prevent leakage.

3. Storage

  • Store the tester in its black carrying bag to protect it from dust and physical damage.
  • Keep the device in a cool, dry place, away from direct sunlight and extreme temperatures.

Troubleshooting

  • Device does not power on: Check battery installation and ensure batteries are not depleted. Replace if necessary.
  • Inaccurate readings: Ensure test leads are securely connected and not damaged. Verify the correct test mode and settings are selected.
  • RCD does not trip during test: Double-check connections. Ensure the RCD is functional and correctly rated for the test. If the RCD still doesn't trip, it may be faulty.
  • Loop resistance reading '---' or error: Ensure proper connection to the circuit. Confirm the loop resistance is within the supported range (3 ohms or higher).
  • Data transfer issues: Ensure the USB cable is properly connected and the PC software is correctly installed. Refer to the software's instructions for troubleshooting connection problems.

User Tips

  • RCD Type Compatibility: The MS5910 is designed for standard RCD testing. If you are testing specialized RCDs (e.g., Type A, Type B for DC components), verify compatibility with the device's specifications. The provided specifications primarily indicate testing for AC type RCDs.
  • Regular Calibration: For professional use, consider periodic calibration of the device to ensure continued accuracy.
  • Read the Full Manual: For detailed operational procedures and safety guidelines, always refer to the complete user manual PDF provided with the product.

Warranty and Support

For warranty information, technical support, or service inquiries, please refer to the documentation included with your purchase or contact the seller directly. Keep your purchase receipt as proof of purchase.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.