Halisense HLS-KWL Series Temperature Acquisition Module

Contents

Halisense Temperature Acquisition Module User Manual

Models: HLS-KWL-2PT, HLS-KWL-4PT, HLS-KWL-8PT, HLS-KWL-16PT, HLS-KWL-2TC, HLS-KWL-4TC, HLS-KWL-8TC, HLS-KWL-16TC

1. Product Overview

The Halisense HLS-KWL series offers a range of PT100 and Thermocouple sensor temperature acquisition modules with RS485 Modbus output. These modules are designed for industrial applications requiring precise temperature measurement and reliable data communication. Available in 2, 4, 8, and 16 channel configurations, they support various thermocouple types (K/S/R/B/N/E/J/T) and PT100 sensors.

Halisense 8-channel PT100 Temperature Acquisition Module
Figure 1: Halisense 8-channel PT100 Temperature Acquisition Module
Overview of Halisense Temperature Acquisition Modules with different channel counts and sensor types
Figure 2: Various Halisense Temperature Acquisition Modules

2. Setup and Wiring

Proper wiring is crucial for the accurate and reliable operation of the temperature acquisition module. Ensure all connections are secure and follow the diagrams below.

2.1 Power Supply

The module requires a DC 6-36V power supply. Connect the positive (+) and negative (-) terminals to the corresponding power input on the module.

2.2 Communication

The module uses an isolated RS485 communication port. Connect the A and B terminals to your RS485 master device.

2.3 Sensor Connections

2.3.1 PT100 Module Wiring

PT100 modules support both 2-wire and 3-wire PT100 sensors. Refer to the diagram for correct connection.

PT100 Module wiring diagram showing 2-wire and 3-wire sensor connections
Figure 3: PT100 Module Wiring Diagram (2-wire and 3-wire)

2.3.2 Thermocouple Module Wiring

Thermocouple modules require connecting the sensor signal input (IN) and common (COM) terminals. Ensure correct polarity for accurate readings.

Thermocouple Module wiring diagram showing IN, COM, RS485, and DC power connections
Figure 4: Thermocouple Module Wiring Diagram

3. Operating Instructions

The modules communicate using the Modbus RTU protocol over RS485.

3.1 Communication Parameters

  • Baud Rate: Configurable from 1200 to 115200 bps (default 9600 bps).
  • Data Update Rate: 10HZ/channel for PT100 modules, 2HZ/channel for Thermocouple modules.
  • Mailing Address (Thermocouple): 1-247.

3.2 Communication Power Indication

The module features an indicator light for communication status:

  • Solid Light: System is running normally.
  • Flashing Light: Indicates active communication.

4. Maintenance

The module is designed for industrial environments with robust protection features. Regular checks of wiring and connections are recommended.

  • Protection Features: Includes self-restoring fuse, anti-reverse diode, and TVS diode for overvoltage, overcurrent, and anti-reverse connection protection.
  • Temperature Correction (Thermocouple): Software setting offset (-20.0~20.0°C) can be applied for fine-tuning temperature readings.

5. Troubleshooting

  • No Reading / Error Alarm: Check for sensor disconnects. Ensure sensors are properly connected and within their operational range.
  • Communication Failure: Verify RS485 wiring (A/B terminals), baud rate settings, and power supply. The communication power indicator should flash during active communication.
  • Incorrect Readings: Check sensor type selection (PT100 vs. Thermocouple), wiring polarity, and apply software temperature correction if necessary for thermocouple modules.
  • Module Not Powering On: Ensure DC 6-36V power supply is correctly connected and functional. The module has reverse polarity surge protection.

6. Specifications

The modules feature industrial-grade quality with isolated communication and a high-speed 32-bit microprocessor from STMicroelectronics.

6.1 PT100 Module Specifications

ParameterValueParameterValue
Supply power6-36V DCCommunication portIsolated RS485
Number of channels1-16 channelTemperature range-200~850°C
Power consumption<200mWSensor type2 or 3 wires
Temperature accuracy±0.3°CResolution0.1°C
Acquisition rate100KHZ/channelData Update10HZ/channel
Error alarmSensor disconnects detection
Baud rate1200~115200 (default 9600)

6.2 Thermocouple Module Parameters

ParameterValueParameterValue
Supply power6-36V DCCommunication portIsolated RS485
Number of channels1-16 channelOperating temperature-20~75°C
Power consumption<200mWMailing address1-247
Temperature accuracy±1°CResolution0.1°C
Acquisition rate100KHZ/channelData Update2HZ/channel
Error alarmSensor disconnects detection
Temperature correctionSoftware setting offset (-20.0~20.0°C)
Sensor typeK/S/R/B/N/E/J/T type thermocouple
Baud rate1200~115200 (default 9600)

6.3 Thermocouple Temperature Range Table

Sensor TypeTemperature Measurement Range
K type-270~1370°C
S type-50~1700°C
R type-50~1700°C
B type250~1800°C
N type-200~1300°C
E type-270~1000°C
J type-200~1200°C
T type-270~400°C

6.4 Physical Dimensions

Dimensions vary by channel count and module type. Below are examples:

Dimensions for 2-channel PT100 module: 82mm x 54mm x 32mm
Figure 5: 2-channel PT100 Module (82x54x32mm)
Dimensions for 4-channel PT100 module: 90mm x 90mm x 40mm
Figure 6: 4-channel PT100 Module (90x90x40mm)
Dimensions for 8-channel PT100 module: 115mm x 90mm x 40mm
Figure 7: 8-channel PT100 Module (115x90x40mm)
Dimensions for 16-channel PT100 module: 175mm x 90mm x 40mm
Figure 8: 16-channel PT100 Module (175x90x40mm)
Dimensions for 2-channel Thermocouple module: 82mm x 54mm x 32mm
Figure 9: 2-channel Thermocouple Module (82x54x32mm)
Dimensions for 4-channel Thermocouple module: 82mm x 54mm x 32mm
Figure 10: 4-channel Thermocouple Module (82x54x32mm)
Dimensions for 16-channel Thermocouple module: 115mm x 90mm x 40mm
Figure 11: 16-channel Thermocouple Module (115x90x40mm)

7. User Tips

  • Configuration Software: For advanced settings and configuration, ensure you have the necessary software. If not readily available, contact Halisense support for assistance.
  • Wiring Verification: Always double-check all wiring connections before applying power to prevent damage and ensure accurate readings.
  • Environmental Considerations: While designed for industrial use, avoid exposing the module to extreme conditions beyond its specified operating temperature range (-20~75°C for Thermocouple modules).

8. Warranty and Support

For detailed technical support, warranty information, or specific inquiries regarding your Halisense Temperature Acquisition Module, please refer to the official product documentation or contact Halisense customer service.

A comprehensive user manual in PDF format is available for download: View User Manual (PDF)

© 2023 Halisense. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.