AISET YLD-2612V-2

Contents

AISET YLD-2612V-2 Temperature Controller User Manual

Model: YLD-2612V-2 (YLD-2000 Series)

Brand: AISET

1. Introduction

The AISET YLD series temperature controller, developed by Shanghai Yatai Instrument Co., Ltd., is an intelligent digital temperature control product designed for industrial and commercial applications. It integrates stability, practicality, and cost-effectiveness, utilizing advanced SMT technology and a self-tuning fuzzy PID control algorithm. This manual provides essential information for the safe and effective operation of your YLD-2612V-2 temperature controller.

Key Features:

  • High-performance single-chip microcomputer and SMT technology.
  • High control precision (±0.5~±1°C).
  • Multiple control output modes (relay, DC 4-20mA, 0-10V, SSR drive).
  • High-brightness digital display with temperature correction and power-off memory.
  • Flame-retardant materials and good electromagnetic compatibility.
  • Complies with EU safety and environmental standards (EMC 2014/30/EU, LVD 2014/35/EU, RoHS 2011/65/EU, WEEE 2012/19/EC).

2. Important Safety Warnings

Read carefully before use to avoid injury, equipment damage, or non-compliance with regulations. Installation and maintenance must be performed by trained professionals.

  • This product is for industrial and commercial use only, not for household use. Keep out of reach of children and untrained personnel.
  • Always turn off and isolate the power supply before wiring, maintenance, disassembly, or cleaning to prevent electric shock and equipment damage.
  • Confirm that the power supply voltage matches the controller's rated voltage (AC 187~244V, 50/60Hz) and that the voltage deviation does not exceed ±10%.
  • Do not use the product beyond its rated parameters (voltage, load, temperature) to prevent fire, electric shock, or permanent damage.
  • Avoid installing the controller in flammable, explosive, humid, dusty, or corrosive gas environments. Suitable ambient temperature is -10~55°C, humidity ≤90% (non-condensing).
  • The controller must be correctly grounded in accordance with EU EMC and LVD directives. The protective grounding terminal is mandatory.
  • Do not modify, disassemble, or repair the product without authorization. Unauthorized operations will void the warranty and may violate regulations.
  • In case of abnormal operation (display failure, abnormal heating/cooling, alarm failure, temperature deviation, or sensor error), turn off the power immediately and contact professional maintenance personnel.
  • Disposal of this product must comply with EU WEEE 2012/19/EC directive. Do not discard as household waste; hand it over to qualified recycling institutions.
  • This is a Class A product. In a domestic environment, it may cause radio interference; the user may need to take appropriate measures to reduce interference.

3. Specifications

The following specifications are universal for the YLD series. Specific details for YLD-2612V-2 are highlighted where available.

ItemParameter
Operating VoltageAC 187~244V, 50/60Hz
Control Accuracy±0.5~±1°C; Temperature correction range -9~9°C
Control Range (YLD-2612V-2)0~400°C (PT100 sensor)
Input Signal (YLD-2612V-2)PT100 RTD sensor
Output LoadUp to 10A/250V AC (resistive load); Relay output
Installation Type & SizeFixed panel installation; Common sizes: 48×48mm, 48×96mm, 72×72mm, 96×96mm
Ambient Temperature-10~55°C (general models)
Ambient Humidity≤ 90% (non-condensing)
Power (W)2 W

4. Setup

4.1 Unpacking and Inspection

Carefully unpack the temperature controller and inspect it for any signs of damage. Ensure all components are present. If any damage is found or parts are missing, contact your supplier immediately.

AISET YLD-2612V-2 Product Packaging

Figure 1: Product packaging for YLD-2612V-2, showing model and basic specifications.

4.2 Installation Environment

  • Install the controller in a dry and ventilated place.
  • Keep away from high temperature, humidity, strong electromagnetic interference, flammable/explosive materials, and corrosive gases.
  • Ensure the ambient temperature and humidity are within specified limits (-10~55°C, ≤90% non-condensing).
  • Install firmly according to the panel installation type.
  • Avoid installation near cold/heat sources or in direct sunlight.
  • Keep the sensor away from power cables to avoid electromagnetic interference.

4.3 Wiring Instructions

WARNING: Turn off the power supply before wiring to avoid electric shock. Wrong wiring can cause electric shock, fire, or product damage. Double-check all connections before power-on.

Refer to the product label and the diagram below for correct wiring. Ensure all connections comply with IEC 60335-1:2020 standards for live part protection and terminal identification.

AISET YLD-2612V-2 Wiring Terminals

Figure 2: Internal circuit board showing terminal blocks for wiring. From left to right: N, L, OUT, OUT, ALM, ALM, PT100, PT100, PT100.

  • Power Terminal (L/N): Connect to AC 187~244V power supply. Ensure stable power input and that input power/current are within allowable deviation.
  • Input Terminal (PT100): Connect the PT100 temperature sensor. Ensure a tight connection for accurate signal transmission. Keep the sensor line away from power lines to avoid electromagnetic interference.
  • Output Terminal (OUT): Connect to the load (e.g., heater). Match the load type with the controller's output mode. Ensure load power does not exceed the controller's rated load.
  • Alarm Terminal (ALM): Connect to an external alarm device if used.
  • Ground Terminal (PE): Mandatory grounding is required for safe use and to prevent electrical hazards. The grounding terminal must be marked with the IEC 60335-1:2020 grounding symbol.

Use standard wiring materials and ensure firm connections to prevent poor contact and overheating. The controller can be used at altitudes below 2500 meters for full-load operation. For altitudes above 2500 meters, the load power should not exceed 80% of the rated power.

5. Operating Instructions

5.1 Power On

After completing all wiring and ensuring correct grounding, turn on the power switch. The AISET YLD-2612V-2 will automatically enter the working state. The digital display will show the current measured temperature (PV) and the target temperature (SV). LED indicators will show the working status (heating, cooling, defrosting, alarm, communication, etc.).

AISET YLD-2000 Front Panel

Figure 3: Front panel of the YLD-2000 series controller, showing PV (Process Value) and SV (Set Value) displays, status indicators (RUN, OUT, ALM), and control buttons (SET, AT, TIME).

5.2 Basic Temperature Setting

  1. Press and hold the "SET" key for 2 seconds to enter the target temperature setting mode. The SV display will flash.
  2. Use the "▲" (up) or "▼" (down) key to adjust the target temperature to your desired value. Hold the key for more than 1 second for quick adjustment.
  3. Press the "SET" key again to confirm the setting and exit, or press the "TIME" key to abandon the setting.

5.3 Key Functions

  • Temperature Correction: Enter advanced parameter setting mode (long press "TIME" key for 5 seconds, enter password if set), find the temperature correction parameter (H1), use "▲" or "▼" to adjust the value (-9~9°C), then press "SET" to confirm.
  • Child Lock Setting: Long press the "SET" key for 6 seconds to lock the keys. All short-press operations will be invalid. To unlock, repeat the same long press.
  • Mode Switching (Heating/Cooling): Enter advanced parameter setting mode, set the cooling/heating mode (e.g., F29 for YLD-8830, check manual for YLD-2612V-2 specific parameter).
  • Time Setting: In manual mode, press "SET" to switch to time display. Long press "SET" to enter time adjustment. Adjust hour/minute with "▲" or "▼", then press "SET" to confirm.

5.4 Display & Alarm Introduction

  • Normal Mode: PV displays current measured temperature, SV displays target temperature. LED indicators show heating (RUN/OUT), alarm (ALM), and standby status.
  • Setting Mode: Flashing display indicates the parameter being set.
  • Alarm Mode: When temperature exceeds set range, sensor fails (open/short circuit), or load is abnormal, the ALM indicator lights up. Display shows "00", "98", "OPE" (sensor open circuit), or "SHr" (sensor short circuit) for sensor faults. Alarm code "Axx" may be displayed for other faults.

6. Maintenance

  • Regular Checks: Regularly check wiring, sensor connection, and controller status to ensure stable operation and compliance.
  • Cleaning: Clean the display panel and wiring terminals regularly to avoid dust affecting readings and poor contact. Clean the controller surface with a dry, soft cloth; do not use corrosive cleaners.
  • Calibration: Calibrate the controller regularly through the temperature correction function to maintain measurement accuracy.
  • Environmental Protection: Do not let water, cement slurry, metal particles, or other debris enter the controller.
  • Surface Marks: Ensure product surface marks (CE, RoHS) remain clear and unfaded.

7. Troubleshooting

If the controller exhibits abnormal behavior, refer to the following common issues and solutions:

  • Display Failure / Abnormal Heating/Cooling / Alarm Failure / Temperature Deviation / Sensor Error: Turn off the power immediately and contact professional maintenance personnel. Do not attempt to repair it yourself.
  • Sensor Line Abnormal: Display shows "00", "98", "OPE" (open circuit), or "SHr" (short circuit). Check sensor wiring and sensor integrity.
  • Alarm Code "Axx": Indicates other faults. Refer to the full manual for specific code meanings or contact support.

CAUTION: Use only AISET-approved accessories and peripheral equipment. Do not modify internal parameters without professional guidance.

8. User Tips

  • Verify Model and Sensor: Before installation, double-check that the controller model (YLD-2612V-2) and sensor type (PT100) match your application requirements to ensure proper functionality.
  • Secure Connections: Ensure all wiring connections are tight and secure. Loose connections can lead to inaccurate readings or operational issues.
  • Initial Testing: After setup, perform a low-stakes test to confirm the controller is accurately reading temperature and controlling the load as expected before full deployment.

9. Warranty and Support

9.1 Warranty

AISET YLD series temperature controllers come with a 12-month warranty from the date of delivery. This warranty covers defects caused by materials or workmanship under normal use and installation in accordance with this manual and relevant EU regulations.

The warranty does not cover damage caused by:

  • Improper operation or wrong wiring.
  • Unauthorized disassembly.
  • Non-compliance with EU regulations.
  • External factors or use of non-approved accessories.
  • Failure to follow the instruction manual.
  • Normal wear and tear.

The temperature sensor and communication module (for YLD-7000) are considered vulnerable parts and are not covered by the warranty.

9.2 Support

For detailed operation steps, parameter settings, advanced functions of specific models, or technical support, please refer to the corresponding full-version manual available through the official channels of Shanghai Yatai Instrument Co., Ltd. Contact your supplier or local distributor for further assistance.