ATS JTQ2-63

Contents

ATS Automatic Transfer Switch User Manual

Model: JTQ2-63

1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of the ATS Automatic Transfer Switch, Model JTQ2-63. This device is designed to automatically or manually switch between two power sources (e.g., utility power and a generator) to ensure continuous power supply to a load. It is available in 2-pole (2P) and 4-pole (4P) configurations, with a rated current of 63A and compatible with 110V or 220V systems.

2. Safety Information

WARNING: Installation and maintenance should only be performed by qualified personnel. Always disconnect power before working on the switch to prevent electric shock or equipment damage.

  • Ensure all local and national electrical codes are followed.
  • Verify voltage and current ratings match your application.
  • Do not operate the switch with wet hands or in damp conditions.
  • Ensure proper grounding.

3. Product Components and Features

The ATS Automatic Transfer Switch (Model JTQ2-63) features a robust design for reliable power transfer. Key components and indicators include:

Front view of the ATS Automatic Transfer Switch with control panel and handle
Figure 3.1: Front view of the ATS control panel. Shows "Automatic" and "Manual" modes, a central handle for manual operation, and indicator lights for power supply status and closing.
  • Control Panel: Features "Automatic" and "Manual" mode selection.
  • Operating Handle: For manual switching between power sources or to the "0" (off) position.
  • Indicator Lights:
    • Current Power Supply: Indicates which source is currently active.
    • Normal Power Supply: Indicates availability of the normal power source.
    • Backup Power Supply: Indicates availability of the backup power source.
    • Normal Closing: Indicates the switch is connected to the normal power source.
    • Backup Closing: Indicates the switch is connected to the backup power source.
  • Terminal Blocks: Clearly labeled for Normal Power (N), Emergency Power (R), and Load connections.

4. Installation

4.1 Mounting

The ATS switch is designed for panel mounting. Ensure sufficient space for wiring and ventilation.

Rear view of the ATS Automatic Transfer Switch showing mounting plate and holes
Figure 4.1: Rear view illustrating the mounting plate with pre-drilled holes for secure installation.

4.2 Wiring Diagram

Refer to the following diagram for correct wiring connections. Ensure all connections are tight and secure.

Wiring diagram for ATS Automatic Transfer Switch showing Normal Power, Emergency Power, and Load connections
Figure 4.2: Wiring connections. "N" terminals for Normal Power (Live and Neutral), "R" terminals for Emergency Power (Live and Neutral), and "LOAD" for the output circuit.

Wiring Steps:

  1. Connect the Normal Power live line to the "N" live terminal and the Normal Power neutral line to the "N" neutral terminal.
  2. Connect the Emergency Power live line to the "R" live terminal and the Emergency Power neutral line to the "R" neutral terminal.
  3. Connect the Load live line to the output live terminal and the Load neutral line to the output neutral terminal.
  4. Ensure proper grounding for all connected circuits.

Important Note from Product Label:

Detailed product label showing model JTQ2-63, rated voltage 220V/400V, frequency 50/60Hz, and various rated current options (6A to 63A)
Figure 4.3: Product label with technical specifications and wiring notes. Note 1.2(N) for Normal power off instructions (active 220V) and 3.4(N) for Reserve power off instructions (active 220V).

The label indicates specific instructions for normal and reserve power off conditions, particularly for 220V systems. Always refer to the detailed label on your specific unit for precise wiring and operational details.

5. Operation

5.1 Automatic Mode

In Automatic mode, the switch will automatically transfer the load between the Normal Power Supply and the Backup Power Supply based on their availability.

  1. Set the mode selector switch to "Automatic".
  2. When Normal Power is present, the switch will connect to it. The "Normal Power Supply" and "Normal Closing" indicators will illuminate.
  3. If Normal Power fails, the switch will automatically transfer to the Backup Power Supply (if available). The "Backup Power Supply" and "Backup Closing" indicators will illuminate.
  4. When Normal Power is restored, the switch will automatically transfer back to Normal Power (if configured for automatic retransfer).

5.2 Manual Mode

In Manual mode, you can manually switch between power sources using the operating handle.

  1. Set the mode selector switch to "Manual".
  2. To connect to Normal Power, rotate the handle towards the "N" side.
  3. To connect to Emergency Power, rotate the handle towards the "R" side.
  4. To disconnect from both power sources, rotate the handle to the central "0" position.
  5. Always ensure the handle is fully engaged in the desired position.

6. Maintenance

  • Regularly inspect the switch for any signs of damage, loose connections, or overheating.
  • Keep the switch clean and free from dust and debris. Use a dry cloth for cleaning.
  • Do not use abrasive cleaners or solvents.
  • Periodically check terminal screws for tightness.
  • Ensure proper ventilation around the switch.

7. Troubleshooting

ProblemPossible CauseSolution
Switch does not transfer power.No power from either source; incorrect wiring; switch in manual mode.Check power sources; verify wiring according to diagram; ensure switch is in "Automatic" mode for automatic transfer.
Indicator lights are off.No power to the switch; faulty indicator.Check incoming power; contact support if power is present but indicators remain off.
Switch makes unusual noises or smells.Overload; loose connection; internal fault.Immediately disconnect power. Do not operate. Contact qualified electrician or support.

8. Specifications

FeatureDetail
Model NumberJTQ2-63
TypeMini Automatic Transfer Switch
Poles Number2P (2-pole), 4P (4-pole)
Rated Voltage110V, 220V (50/60Hz)
Rated Current63A (also available in 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A variants)
Is Smart DeviceNo
Dimensions (L x W x H)150mm x 120mm x 135mm
WeightApprox. 1.7 kg
OriginMainland China
Side view of the ATS Automatic Transfer Switch with dimensions L150*W120*H135 mm
Figure 8.1: Dimensions of the ATS Automatic Transfer Switch.

9. User Tips

  • Understanding "2P" and "4P": "2P" refers to a 2-pole switch, typically used for single-phase systems where both the live and neutral lines are switched. "4P" refers to a 4-pole switch, commonly used in three-phase systems where all three live phases and the neutral line are switched. Ensure you select the correct pole configuration for your electrical system.
  • Always double-check the voltage and current ratings of your power sources and load to ensure compatibility with the ATS switch.
  • For critical applications, consider having a qualified electrician perform the installation and initial setup.

10. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.