Renke RS-WS-N01-8

Contents

Renke RS-WS-N01-8 Temperature and Humidity Sensor Instruction Manual

Model: RS-WS-N01-8 | Brand: Renke

1. Introduction

The Renke RS-WS-N01-8 is a compact temperature and humidity sensor designed for environmental monitoring. It features a built-in sensor, standard DIN35 guide rail mounting, and RS485 communication with Modbus-RTU protocol. This manual provides essential information for the proper installation, operation, and maintenance of the device.

Video 1: Product Introduction and Overview.

2. Product Features

  • Integrated temperature and humidity sensor in a compact size.
  • Standard DIN35 guide rail mounting for easy installation in power distribution cabinets.
  • RS485 communication interface with standard Modbus-RTU protocol.
  • Configurable communication address and baud rate.
  • Wide operating temperature range: -40℃ to +60℃.
  • Pluggable terminals for simplified installation and maintenance.
  • 10-30V DC wide voltage power supply.
Renke RS-WS-N01-8 sensor features

Figure 1: Key features of the RS-WS-N01-8 sensor, including indicator light, pluggable terminal, built-in sensor, and hollow heat dissipation design.

3. Setup and Installation

3.1 Physical Installation

The RS-WS-N01-8 sensor is designed for standard DIN35 guide rail installation. Follow these steps:

  1. Ensure the power supply is disconnected before installation.
  2. Locate a suitable DIN35 rail within your power distribution cabinet or desired mounting location.
  3. Align the sensor's mounting clips with the DIN35 rail.
  4. Press firmly until the sensor clicks securely into place on the rail.
Standard 35mm rail installation for Renke sensor

Figure 2: Illustration of standard 35mm DIN rail installation for the sensor.

3.2 Wiring

The sensor uses pluggable terminals for electrical connections. Connect the power supply and RS485 communication lines as follows:

  • Power Supply: Connect a 10-30V DC power source to the designated power terminals. Observe polarity.
  • RS485 Communication: Connect the RS485 A and B lines to your Modbus master device.

Refer to the product's terminal markings for precise connections. The pluggable terminals simplify wiring and future maintenance.

3.3 Initial Configuration

The sensor communicates using the Modbus-RTU protocol. Before operation, you may need to configure the communication address and baud rate to match your Modbus network. Consult the Modbus communication protocol documentation for detailed instructions on setting these parameters. Typically, these are configured via software connected to the Modbus master.

4. Operating Instructions

Once installed and powered, the RS-WS-N01-8 sensor will begin measuring temperature and humidity. Data can be accessed via the RS485 Modbus-RTU interface.

4.1 Data Acquisition via Modbus-RTU

To read temperature and humidity data, your Modbus master device (e.g., PLC, industrial computer, data logger) should send Modbus-RTU read requests to the sensor's configured address. The sensor will respond with the current temperature and humidity values.

The data view typically shows real-time data, overrun alarms, historical data queries, data output, and SMS/email alerts when integrated with an environmental monitoring cloud platform.

Environmental monitoring data view

Figure 3: Example of data display and monitoring interface, showing real-time data, alarms, and historical trends.

4.2 Environmental Monitoring Cloud Platform Integration

The sensor can be connected to an environmental monitoring cloud platform via a monitoring host or network concentrator. This allows for advanced features such as:

  • Real-time data display.
  • Overrun alarms (e.g., temperature/humidity exceeding set thresholds).
  • Historical data query and analysis.
  • Data output for reporting.
  • SMS and email alerts for critical events.
Environmental monitoring cloud platform diagram

Figure 4: Diagram illustrating the connection of RS485 transmitters to a monitoring host and an environmental monitoring cloud platform for data transmission and services.

5. Maintenance

The Renke RS-WS-N01-8 sensor is designed for long-term stability and minimal maintenance. However, regular checks can ensure optimal performance.

  • Cleaning: Periodically inspect the sensor for dust or debris accumulation, especially around the sensing elements and ventilation slots. Clean gently with a soft, dry cloth. Avoid using harsh chemicals or abrasive materials.
  • Connection Check: Ensure all electrical connections at the pluggable terminals remain secure.
  • Software Updates: If using a connected monitoring system, ensure the software and firmware are up-to-date for best performance and security.
  • Long-term Stability: The sensor boasts excellent long-term stability with humidity drift ≤1%RH/year and temperature drift ≤0.1℃/year. Recalibration is generally not required frequently under normal operating conditions.

6. Troubleshooting

If you encounter issues with your RS-WS-N01-8 sensor, consider the following common troubleshooting steps:

  • No Power/No Indicator Light:
    • Check the 10-30V DC power supply connection and ensure it is active.
    • Verify correct polarity of the power connections.
  • No Data Output/Communication Errors:
    • Confirm RS485 A and B lines are correctly connected to the Modbus master.
    • Verify the communication address and baud rate settings on both the sensor and the Modbus master match.
    • Check for proper termination resistors on the RS485 bus if applicable.
    • Ensure the Modbus master is sending valid Modbus-RTU requests.
  • Inaccurate Readings:
    • Ensure the sensor is not exposed to direct sunlight, strong drafts, or close to heat/cold sources that could affect local readings.
    • Check for any physical obstructions or debris on the sensor's ventilation slots.
    • Verify the sensor is operating within its specified work environment range (-20℃~60℃, 0~80%RH).

If problems persist, contact technical support for further assistance.

7. Specifications

ParameterValue
Product NameRS485 temperature humidity transmitter
BrandRenke
Model NumberRS-WS-N01-8
Power Supply10-30V DC
Maximum Power Consumption0.3W
Output SignalRS485 (Modbus-RTU communication protocol)
Humidity Measurement Range0~100% RH
Temperature Measurement Range-40℃~80℃
Humidity Accuracy (Default)±3%RH (at 60%RH, 25℃)
Temperature Accuracy (Default)±0.5℃ (at 25℃)
Humidity Accuracy (High Precision)±2%RH (at 60%RH, 25℃)
Temperature Accuracy (High Precision)±0.4℃ (at 25℃)
Temperature Display Resolution0.1℃
Humidity Display Resolution0.1%RH
Humidity Long-term Stability≤1%RH/year
Temperature Long-term Stability≤0.1℃/year
Humidity Reaction Time≤8s (at 1m/s wind speed)
Temperature Reaction Time≤25s (at 1m/s wind speed)
Work Environment-20℃~60℃, 0~80%RH
Dimensions (L x W x H)65mm x 46mm x 28.5mm (approx.)
Renke RS-WS-N01-8 sensor dimensions

Figure 5: Approximate dimensions of the RS-WS-N01-8 sensor.

8. User Tips

  • For optimal accuracy, ensure the sensor is placed in a location representative of the environment you wish to monitor, away from direct heat sources, cold drafts, or areas with stagnant air.
  • When integrating with a Modbus network, always double-check the communication parameters (address, baud rate, parity, stop bits) to prevent communication errors.
  • Utilize the pluggable terminals for quick and secure wiring, and ensure they are fully seated to maintain reliable connections.
  • Consider using a dedicated environmental monitoring cloud platform for advanced data logging, analysis, and alert functionalities, especially in critical applications.

9. Warranty and Support

For any technical inquiries, support, or warranty claims, please contact the manufacturer or seller directly.

  • Email: h784914676@126.com
  • WhatsApp: +8615173134620

Please provide your product model number (RS-WS-N01-8) and a detailed description of your issue when contacting support.

© 2023 Renke. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.