EARU EASEM-G-TY-W

Contents

EARU Three Phase Tuya WiFi Smart Energy Meter & Protector User Manual

Model: EASEM-G-TY-W

1. Introduction

This manual provides detailed instructions for the installation, operation, and maintenance of your EARU Three Phase Tuya WiFi Smart Bi-Directional Energy Meter with 3 CT Clamps and integrated Leakage, Over/Under Voltage Protector, and Relay Switch Limit. This device is designed for precise energy monitoring and protection in three-phase electrical systems, offering smart control and data access via WiFi.

EARU Three Phase WiFi Smart Energy Meter & Protector with CT Clamps and App Interface

Figure 1: EARU Three Phase WiFi Smart Energy Meter & Protector

2. Safety Information

  • Installation and maintenance should only be performed by qualified electricians.
  • ALWAYS turn off the main power supply before installing or servicing the device to prevent electric shock.
  • This product does not have an isolation function. Ensure power is off before any repairs.
  • The neutral wire (N) of this product is directly connected without a disconnection function.
  • The device must be wired according to the markings on the unit.
  • Although this device has protection functions, it cannot replace a normal circuit breaker. Always install a standard circuit breaker upstream for comprehensive protection.
  • Tighten all clamp screws firmly to avoid damage to the device caused by poor contact.

3. Product Features

  • Bi-Directional Energy Monitoring: Measures both forward (positive) and reverse (negative) energy consumption, ideal for solar installations.
  • Comprehensive Protection: Includes Over Voltage, Under Voltage, Over Current, Under Current, Leakage, Voltage Imbalance, Phase Shortage, and High Temperature protection.
  • Smart Control: Remote control via Tuya Smart / Smart Life app.
  • Voice Control: Compatible with Google Assistant and Amazon Alexa.
  • Programmable Timers: Countdown, Timed, and Recurring timer modes for automated control.
  • Power Failure Memory: Retains data and returns to pre-power failure state upon restoration.
  • Real-time Data Display: LCD screen shows voltage, current, power, frequency, power factor, and energy consumption.
  • Alarm Settings: Customizable thresholds for various protection parameters.
  • Data Logging: Records operation history and energy statistics.
Display modes and list of features

Figure 2: Key Features and Display Modes

4. Package Contents

  • 1 x EARU Three Phase WiFi Smart Energy Meter & Protector Unit
  • 3 x Current Transformer (CT) Clamps (Amperage depends on model purchased)

5. Specifications

Technical Data table

Figure 3: Technical Data

Table 1: Product Specifications
AttributeValue
Model NumberEASEM-G-TY-W
Rated VoltageAC380V (L+N=AC80-240V)
Operation VoltageAC80V-400V (Single Phase)
Rated Current80A/120A/200A/300A/500A/750A/1000A (Depends on CT)
Rated Frequency50/60Hz
Measurement Accuracy±1%/Class 1 (80-300A starts from 0.03A, 500-1000A starts from 0.1A)
Device Data Fresh Speed1 Time/S
App Data Fresh SpeedIf fluctuations in kWh (≥5), V (≥5V), A (≥0.8A), or Temperature (≥5°C) occur → Upload to App immediately; otherwise, upload every 5 minutes.
Power Consumption≤1.5W
Installation35MM Din Rail
Working Temperature-10℃~+55℃
Storage Temperature-40℃~+70℃
Working Humidity5%~95%RH
Dimensions90*72.5*60MM (L*W*H)
Display TypeLCD
Max kWh Record999999kWh
Display Working TimeAlways On
Load Capacity0.05Ib-Imax
StandardIEC62053-21&GB/T17215.321-2008
CertificationCE, FCC
Warranty1 Year
Product dimensions and basic parameters

Figure 4: Product Dimensions

6. Installation

6.1 Mounting

The energy meter is designed for 35mm DIN rail installation. Ensure a secure fit within your electrical panel.

6.2 CT Clamp Installation

The Current Transformer (CT) clamps are crucial for current measurement. Each CT clamp has an arrow or 'P1→P2' / 'K→L' marking on its body or a sticker. This indicates the direction of current flow. The CT supports bidirectional sensing. If the current direction is opposite to the CT's marking, the power reading will be negative. Ensure the CT is applied to the correct cable and its direction is consistent with your measurement needs.

CT Clamp installation diagram and dimensions table

Figure 5: CT Clamp Installation and Dimensions

6.3 Wiring Instructions

Refer to the wiring diagrams below for proper connection. Connect the AC input lines to the appropriate terminals (L1, L2, L3, N) and the CT clamps to the respective phase cables. Ensure all connections are tight and secure.

Important Note: A circuit breaker and a shunt trip device are required for the protection functions to operate. These are NOT included in the package and must be purchased separately if needed.

6.3.1 Energy Meter + Protector Wiring Diagram

Energy Meter + Protector Wiring Diagram

Figure 6: Wiring for Energy Meter with Protector Functions

For the protector function with a shunt trip release:

  • Connect the other wire of the shunt trip release to terminal 16 (Normally Open - NO).
  • Connect the neutral wire (N) from the electric meter to the common (COM) terminal 15.
  • Terminal 15 is the common contact (COM). Terminal 16 is the Normally Open (NO) contact, with a maximum load capacity of 5A.

Wiring Instructions for a Three-Phase Circuit Breaker with an Integrated 220V Shunt Trip Release:

Connect one wire of the shunt trip release to the C-phase (Phase C) point of the circuit breaker's output line. WARNING: This wire can only be connected with the circuit breaker output line, not the input line. If connected to the input line, the Shunt Trip Release will be burnt!

6.3.2 Pure Energy Meter Wiring Diagram

Pure Energy Meter Wiring Diagram

Figure 7: Wiring for Pure Energy Meter Functionality

6.3.3 Interface Definition

Interface Definition Table for the meter

Figure 8: Terminal Interface Definitions

7. Operation

7.1 Local Display

The device features an LCD screen that cycles through various parameters. Use the navigation buttons (Up, Down, OK) to view different display modes and settings.

7.2 App Integration (Tuya Smart / Smart Life)

The meter integrates with the Tuya Smart or Smart Life app for remote monitoring and control. Follow these steps to connect your device:

  1. Download the Tuya Smart or Smart Life app from your app store.
  2. Register or log in to your account.
  3. Ensure your device is powered on and in pairing mode (WiFi indicator blinking).
  4. In the app, tap '+' to add a new device. The app should automatically discover the device. If not, select 'Add Manually' and choose 'Breaker' or 'Socket (Wi-Fi)' under Electrical.
  5. Enter your Wi-Fi network credentials (2.4GHz network required).
  6. Once connected, the device will appear in your app, allowing you to view real-time data, energy statistics, operation records, and configure settings.

Video 1: App Pairing and Feature Demonstration

App screenshots showing various settings and alarm configurations

Figure 9: Tuya Smart App Interface for Monitoring and Settings

7.3 Voice Control

The device supports voice control through Google Assistant and Amazon Alexa. After linking your Tuya Smart/Smart Life account to your voice assistant, you can use commands like "Alexa/Google, Turn On The Living Room Light" (if connected to a controlled load) or inquire about energy status.

Voice Control feature with smart speakers

Figure 10: Voice Control Integration

8. Configuration

8.1 Protection and Alarm Settings

The device offers extensive customizable protection settings. These can be configured via the device's buttons or through the Tuya Smart/Smart Life app.

Summary of Alarm Settings and their default values

Figure 11: Alarm Setting Overview

Table 2: Protection and Alarm Parameters
ParameterAdjustable RangeDefault Value
Over Voltage Limit120-300V275V
Under Voltage Limit80-210V175V
Over Current Limit1-100A80A
Under Current Limit1-100A10A
Leakage Current Limit10-100mA30mA
High Temperature Alarm10-85℃85℃
Three-Phase Current Imbalance Alarm10-100%20%
Voltage Three-Phase Imbalance Alarm0-100%20%
Over & Under Voltage Protection Recovery Time1-9999s20s
Over & Under Current Protection Delay0000-9999s5s
Over & Under Current Protection Recovery Time0000-9999s20s
Under & Over Voltage Protection Delay1-9999s3s
Lost Current Recovery Delay Time1-9999s20s
Time Threshold of Lost Flow Event1-999s10s
Energy Consumption Zero ClearingN/ADefault OFF
Factory Settings ResetN/ADefault OFF

8.2 Timer Functions

The app allows you to set various timer functions to automate the device's operation:

  • Countdown Mode: Set a timer for the device to turn off after a specified duration.
  • Timed Mode: Schedule specific ON/OFF times for the device.
  • Recurring Timer Mode: Set daily or weekly schedules for repeated operations.
  • Inching: Configure the device to turn on for a brief period after being triggered.
Countdown, Timed, and Recurring Timer Modes

Figure 12: Timer Function Examples

9. User Tips

  • Wi-Fi Connectivity: If you experience issues with the Wi-Fi function, ensure your router is broadcasting a 2.4GHz network. Check that the device is in pairing mode (blinking Wi-Fi indicator) and verify your Wi-Fi password in the app.
  • Protection Settings: Carefully configure the over/under voltage and current limits to match your specific electrical system requirements to prevent nuisance tripping or inadequate protection.
  • Energy Monitoring: Utilize the app's energy statistics to track daily, monthly, and yearly consumption. This can help identify energy usage patterns and potential savings.

10. Troubleshooting

Table 3: Common Troubleshooting Steps
ProblemPossible CauseSolution
Wi-Fi function not working / Device won't connect to appIncorrect Wi-Fi credentials, 5GHz network, device not in pairing mode, weak signal.Ensure your Wi-Fi is 2.4GHz. Verify Wi-Fi password. Put the device into pairing mode (refer to app instructions for specific steps). Check Wi-Fi signal strength near the device.
Device not powering onNo power supply, incorrect wiring, internal fault.Check main power supply. Verify wiring connections according to diagrams. If power is present and wiring is correct, contact support.
Incorrect energy readingsCT clamp installed incorrectly (reversed direction), faulty CT clamp, incorrect multiplier settings in app.Check CT clamp direction (arrow should point towards load). Ensure CT clamps are securely closed. Verify voltage and current multiplier settings in the app.
Protection (e.g., over-voltage) not triggeringProtection function disabled, threshold set too high/low, no shunt trip release connected.Enable the specific protection function in the app or via device buttons. Adjust the threshold to an appropriate value. Ensure a compatible shunt trip release is correctly wired if using protector features.
Device frequently trips/shuts offProtection thresholds set too sensitively, actual load exceeding limits.Review and adjust protection thresholds (e.g., over current, over voltage) to prevent nuisance tripping. Check actual load to ensure it's within the device's and CT's rated capacity.

11. Maintenance

  • Keep the device clean and free from dust and moisture.
  • Periodically check all wiring connections for tightness and signs of wear or damage.
  • Ensure adequate ventilation around the device to prevent overheating.
  • Check the app regularly for firmware updates to ensure optimal performance and security.

12. Warranty and Support

This EARU energy meter comes with a 1-year warranty from the date of purchase. For technical support, warranty claims, or any questions not covered in this manual, please contact your retailer or the EARU Official Store directly. Please have your product model number (EASEM-G-TY-W) and purchase details ready when contacting support.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.