Coolmay TK8050H

Contents

Coolmay TK8050H HMI Touch Screen LCD Panel User Manual

Model: TK8050H | Brand: Coolmay

1. Introduction and Overview

The Coolmay TK8050H is a 5-inch Human Machine Interface (HMI) touch screen LCD panel designed for industrial monitoring and control applications. Featuring an 800*480 pixel resolution, it supports RS232 and RS485 communication protocols, including Modbus, making it versatile for various industrial automation tasks. This device is built with an ARM9 core industrial-grade CPU, 128MB RAM, and 128MB NOR Flash ROM, ensuring stable and efficient performance. Its robust design includes an IP65-rated front panel for protection in demanding environments.

Angled view of the Coolmay TK8050H HMI displaying a graphical interface with various controls and indicators.
Angled view of the Coolmay TK8050H HMI displaying a graphical interface.
Rear view of the Coolmay TK8050H HMI showing all ports (LAN, COM1/COM2, USB HOST, HMI PLC) and product label.
Rear view of the Coolmay TK8050H HMI with labeled ports.
Play video
Watch video online
Video demonstrating the Coolmay HMI's user interface and physical features.

2. Specifications

The following table details the technical specifications for the Coolmay TK8050H HMI model:

FeatureSpecification (TK8050H)
Model NumberTK8050H
Dimension151*96*36mm
Cut-out size143*86mm
Display Size108*65mm
WeightAbout 0.33 kg
Display Type5" TFT
Resolution800*480 pixels
Brightness300cd/m²
Contrast Ratio400:01:00
BacklightLED (brightness 0-100 adjustable)
Backlight Time60,000 hours
Display Color1677W true color
Touch Type4-wire resistive panel
ROMNAND Flash 128MB
RAM128MB
CPUDual core 1GHZ
Operating SystemBased on Linux system
USB HostUSB 2.0×1 (for program updates, historical data upload/download)
Download PortType-C, RS232, RS485, Network port
EthernetYes (supports program download via network, Modbus TCP)
Serial Port Protocol1 RS232, 1 RS485 (supports MODBUS, free port, conventional PLC protocols)
SD CardOptionally installed
CalendarYes
Input Voltage12-24VDC±10% <150mA @ 24VDC
Protection ClassIP65 (front panel)
Working Temperature-20~60℃
Storage Temperature-20~70℃
Humidity20%~90%RH
SoftwareVcool 1.0.8
CertificationCE
Detailed specification table for Coolmay TK80 series HMI models, including TK8050H.
Full specification table for TK80 series HMI models.

3. Setup and Installation

Proper installation is crucial for the optimal performance and longevity of your HMI panel. Follow these steps carefully:

3.1 Unpacking and Inspection

  1. Carefully unpack the HMI panel and all accessories.
  2. Verify that all components are present: HMI unit, mounting buckles, testing report, and certificate.
  3. Inspect the unit for any signs of physical damage during transit.
Image showing the product packaging and included accessories: mounting buckles, testing report, and certificate.
Product packaging and accessories.

3.2 Panel Mounting

  1. Prepare a panel cutout with dimensions 143mm x 86mm.
  2. Insert the HMI unit into the cutout from the front.
  3. Secure the HMI using the provided mounting buckles on the rear side of the panel.
Diagram illustrating the product interface layout and installation dimensions for panel mounting.
Product interface and installation dimensions.

3.3 Wiring and Connections

Refer to the wiring diagram below for connecting the HMI to your system components:

Wiring diagram showing connections for the HMI, including USB-232 serial port cable, 232 programming cable, AC 220V power, DC24V power supply, Type-C HMI programming cable, and Type-C PLC programming cable.
Wiring diagram for HMI connections.
  • Power Supply: Connect a 12-24VDC power supply to the designated terminals (FG 0V 24V). Ensure the power supply meets the specified voltage and current requirements (<150mA @ 24VDC).
  • Communication Ports:
    • COM1/COM2: Use RS232 or RS485 cables for communication with PLCs or other devices.
    • LAN: Connect an Ethernet cable for network communication, program downloads, and Modbus TCP.
    • USB Host: For connecting a USB disk to update programs or transfer historical data.
    • Download Port (Type-C): Use a Type-C cable for programming the HMI.
  • PLC Connection: Connect the HMI to your PLC using the appropriate programming cable (e.g., Type-C PLC programming cable) and communication ports (RS232, RS485, or Ethernet).

Ensure all connections are secure before powering on the device.

4. Operating Instructions

The Coolmay TK8050H HMI operates on a Linux-based system and uses Vcool 1.0.8 software for programming and interface design. The touch screen allows for intuitive interaction with your industrial processes.

4.1 Powering On and Initial Screen

  1. After ensuring all connections are correct, apply power to the HMI.
  2. The device will boot up, displaying the configured user interface.
  3. The PWR, COM, and RUN indicator lights on the side will show the device status.

4.2 Navigating the Interface

The HMI features a 4-wire resistive touch panel. Use a stylus or your finger to interact with the on-screen elements.

  • Buttons and Inputs: Tap on buttons, input fields, and other controls to trigger actions or enter data.
  • Parameter Settings: Access parameter setting screens to adjust operational values for your connected PLC or industrial equipment.
  • Monitoring: View real-time data, status indicators, and alarms from your industrial process.

4.3 Programming and Data Management

  • Vcool Software: Use the Vcool 1.0.8 software on a PC to design and upload your HMI projects. Connect the HMI to the PC via the Type-C download port or Ethernet.
  • USB Host Functionality: The USB Host port allows you to connect a USB flash drive for:
    • Updating the HMI's firmware or application programs.
    • Uploading historical data logs from the HMI.
  • Cloud Platform Integration: The HMI can be integrated with the Coolmay cloud platform via Ethernet, WiFi (if optional module installed), or 4G (if optional module installed) for remote monitoring and management.
Screenshot of the Vcool software interface for HMI programming, showing various design elements and protocol settings.
Vcool software interface for HMI programming.
Diagram illustrating the Coolmay cloud platform connectivity, showing how the HMI connects to the cloud via Ethernet/WiFi/4G for monitoring and management.
Coolmay cloud platform connectivity.

5. Maintenance

Regular maintenance ensures the longevity and reliable operation of your Coolmay TK8050H HMI.

  • Cleaning: Use a soft, lint-free cloth slightly dampened with water or a mild, non-abrasive cleaner to clean the screen and casing. Avoid harsh chemicals, solvents, or abrasive materials that could damage the display or plastic.
  • Environmental Conditions: Ensure the HMI operates within its specified temperature range (-20~60℃) and humidity range (20%~90%RH). Avoid direct sunlight, excessive heat, or extreme cold.
  • Connections: Periodically check all cable connections (power, communication, USB) to ensure they are secure and free from corrosion or damage.
  • Firmware Updates: Keep the HMI firmware and Vcool software updated to the latest versions to benefit from performance improvements and new features.
  • Front Panel Protection: The front panel is IP65 rated, offering protection against dust and low-pressure water jets. While robust, avoid directly spraying water onto the unit or submerging it.

6. Troubleshooting

If you encounter issues with your HMI, refer to the following troubleshooting tips:

  • No Power:
    • Check the power supply connection and ensure it's providing the correct voltage (12-24VDC).
    • Verify the power cable is not damaged.
    • Ensure the power source is active.
  • Screen Not Responding to Touch:
    • Ensure the screen is clean and free from debris.
    • Restart the HMI.
    • If the issue persists, the touch panel may require recalibration or service.
  • Communication Errors:
    • Check all communication cables (RS232, RS485, Ethernet) for secure connections and damage.
    • Verify the communication parameters (baud rate, data bits, stop bits, parity) in the HMI and connected device (e.g., PLC) match.
    • Ensure the correct communication protocol (e.g., Modbus) is selected.
  • Program Download Issues:
    • Ensure the HMI is properly connected to the PC via the Type-C download port or Ethernet.
    • Verify the Vcool software is correctly configured for the HMI model and connection type.
    • If using a USB drive for updates, ensure the drive is formatted correctly and the program file is in the root directory.
    • Important: During USB download, do not remove the cable until the process is complete.
    Front view of the HMI displaying a 'USB Download.... Don't remove cable.' message.
    HMI displaying a USB download warning.
  • System Freezes or Unresponsive:
    • Perform a hard reset by disconnecting and reconnecting the power.
    • If the problem recurs, there might be a software or hardware issue requiring further diagnosis.

7. User Tips

Based on user feedback and common practices, here are some tips for using your Coolmay TK8050H HMI:

  • Backup Your Projects: Always back up your HMI project files on your computer and a separate storage device. This prevents data loss in case of unexpected issues.
  • Test Connections Thoroughly: Before deploying the HMI in a critical application, thoroughly test all communication links with your PLC and other devices to ensure stable data exchange.
  • Optimize UI Design: For industrial environments, design your HMI screens with clear, large buttons and easily readable text to minimize errors and improve operator efficiency.
  • Leverage Cloud Features: If remote monitoring is beneficial for your application, explore the Coolmay cloud platform integration for real-time data access and management from anywhere.
  • Consult User Manuals: For detailed programming and advanced features, refer to the official “CoolMay TK80 Series (Vcool) User Manual” and “CoolMay TK80 Series User Manual” referenced in the specifications.

8. Warranty and Support

Coolmay products are designed for reliability and performance. For any technical assistance or warranty inquiries, please contact Coolmay PLC Official Store directly.

  • Certification: The TK8050H HMI is CE certified, indicating compliance with European safety, health, and environmental protection requirements.
  • Technical Support: For specific programming questions, troubleshooting beyond this manual, or advanced configurations, reach out to the manufacturer's support team.
Image showing three CE Certificates of Conformity for Coolmay products.
CE Certificates of Conformity.
Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.