Yudian AI-208/207/218/2181

Yudian AI-208/207/218/2181 Intelligent Thermostat Digital Display Meter User Manual

Models: AI-208, AI-207, AI-218, AI-2181

1. Introduction

The Yudian AI-208/207/218/2181 series intelligent thermostats are digital display meters designed for precise temperature measurement and control in various industrial and experimental settings. These devices feature high-brightness LED displays for clear readings and offer multiple input and output options to suit diverse applications. This manual provides essential information for the safe and effective installation, operation, and maintenance of your thermostat.

Yudian AI-208 Intelligent Thermostat front view

Figure 1: Yudian AI-208 Intelligent Thermostat (Example Model)

2. Setup and Installation

2.1 Physical Installation

The Yudian AI-208/207/218/2181 series thermostats are designed for simple and clear installation. Ensure the mounting panel cutout matches the dimensions of your specific model. The device is secured using spring clips made of anti-oxidation material, which helps reduce contact resistance and ensures a stable connection.

Seven international standard sizes for Yudian thermostats

Figure 2: Available International Standard Sizes (A, B, C, D, E, F, D2 types)

Refer to the diagram above for various international standard sizes and their corresponding cutout dimensions. For example, Type A has an outer dimension of 96x96mm and a cutout of 92x92mm.

2.2 Wiring

The back panel of the product features a clear circuit diagram for easy wiring. Ensure all connections are secure and follow local electrical codes.

Simplified installation and internal display of the meter, showing back panel wiring

Figure 3: Back Panel and Internal Components

Temperature Sensor Wiring Method (Three-wire system):

Detailed wiring diagram for 3-wire temperature sensors

Figure 4: Three-wire Temperature Sensor Wiring Diagram

  • When connecting a thermal resistor (RTD): Terminals 19 and 20 are internally shorted leads. Generally, use terminals marked with the same color.
  • When connecting a thermocouple: Only terminals 18 and 19 need to be connected.

Always ensure the power supply (100-240VAC) is correctly connected to the designated terminals as indicated on the back panel.

3. Operating Instructions

3.1 Front Panel Introduction

The front panel of the thermostat features a high-brightness digital display and control buttons for easy operation.

Front panel introduction and input specifications

Figure 5: Front Panel Layout and Controls

  • PV Display (Process Value): Shows the currently measured value. Display range is typically 999-9999.
  • SV Display (Set Value): Shows the set target value.
  • Signal Indicator Light: Illuminates to indicate output from the corresponding terminal.
  • Set Button (↵): Long press for 5 seconds to enter the parameter modification interface. Short press to confirm a selection or change.
  • Shift Button (◀): Moves the cursor to the left during parameter modification.
  • Up Button (▲): Increases the value during parameter modification.
  • Down Button (▼): Decreases the value during parameter modification.

3.2 Basic Operation

  1. Power On: Connect the device to a stable power supply (100-240VAC). The display will light up.
  2. Viewing Current Temperature: The PV display shows the current measured temperature.
  3. Viewing Set Temperature: The SV display shows the current set temperature.
  4. Changing Set Temperature:
    1. Long press the Set button (↵) for approximately 5 seconds to enter the parameter modification mode.
    2. Use the Shift button (◀) to move the cursor to the desired digit.
    3. Use the Up (▲) or Down (▼) buttons to adjust the value.
    4. Short press the Set button (↵) to confirm the new set value and exit modification mode.
  5. Monitoring Output: Observe the signal indicator lights (OP1, AU1, AU2, RUN) to understand the current output status of the device.

4. Maintenance

To ensure the longevity and optimal performance of your Yudian thermostat, follow these general maintenance guidelines:

  • Cleaning: Regularly wipe the device with a soft, dry cloth. Do not use abrasive cleaners or solvents.
  • Environment: Operate the device within its specified environmental conditions (temperature, humidity) to prevent damage.
  • Connections: Periodically check all wiring connections for tightness and signs of corrosion.
  • Calibration: If you suspect inaccurate readings, consult a qualified technician for calibration.

5. Troubleshooting

This section provides basic troubleshooting steps for common issues. For more complex problems, contact technical support.

  • No Display: Check power connections and ensure the power supply is within the specified voltage range (100-240VAC).
  • Inaccurate Readings: Verify the sensor type is correctly configured and the sensor is properly connected. Check for any physical damage to the sensor or wiring.
  • No Output: Check the set value (SV) against the process value (PV) to ensure the control logic is met. Verify wiring to the output device.
  • "ORAL" Display: This indicates a broken line or over-range measurement for the sensor. Check sensor wiring and ensure the sensor is within its operating range.

6. Specifications

6.1 General Specifications

  • DIY Supplies: Electrical
  • Origin: Mainland China
  • Certification: None
  • Working Principle: Electronic thermostat
  • Power: 220V (Note: Device supports 100-240VAC)
  • Thermostat Temperature Range: 0℃-999℃

6.2 Input Specifications

ParameterDescription/Range
Thermocouple TypesK (-200~1372℃), E (-200~1000℃), J (-200~1200℃), T (-200~400℃)
Thermal Resistance TypePT (-200~800℃)
Standard Signal Input0-100mV
Accuracy0.3%FS ±1 digit
Cold Junction Compensation±1℃
Sampling Resolution1℃ or 0.1℃
Sampling Period0.5s
Broken Line Over-range MeasurementDisplay "ORAL"

6.3 Output Module Selection

The AI-2 series economic meters offer various output modules:

AI-2 series economic meter model composition and module selection

Figure 6: AI-2 Series Model Composition and Module Selection

ModuleDescription
GControl solid state relay, drive output DC5V/30mA
L0Relay switch, 2A/250V, Xiamen Hongfa
L1Relay switch, 3A/250V, Xiamen Hongfa
L2Relay switch, 1A/250V, Japan Omron
L3Two-way relay normally open, 2A/250V, Xiamen Hongfa
L5Two-way relay normally open, 2A/250V, Japan Panasonic

7. Warranty and Support

For warranty information, please refer to the terms and conditions provided at the time of purchase. For technical support or service inquiries, please contact your vendor or the manufacturer directly.

8. User Tips

  • Always ensure the correct sensor type is selected in the device settings to match your physical sensor for accurate readings.
  • When installing, double-check all wiring connections to prevent short circuits or incorrect operation.
  • Keep the device in a clean, dry environment to prolong its lifespan.

Related Documents - AI-208/207/218/2181

Preview Yudian AI-8x88/8x68 Multi-Loop Intelligent Controller User Manual
Comprehensive user manual for the Yudian AI-8x88 and AI-8x68 Multi-Loop Intelligent Controllers. This document details product overview, model definitions, technical specifications, wiring methods, panel operations, communication protocols, parameter registers, and alarm explanations, providing essential information for installation, configuration, and operation in industrial automation systems.
Preview Yudian AI Series AI-518/518P Operation Instruction Manual
Comprehensive operation instruction manual for the Yudian AI Series AI-518 and AI-518P artificial intelligence industrial controllers. Covers features, specifications, wiring, operation, parameters, and programming.
Preview Руководство по эксплуатации и гарантийный талон для канальных кондиционеров RRUM
Полное руководство пользователя и гарантийный талон для канальных кондиционеров RRUM, включая инструкции по эксплуатации, технические характеристики, коды ошибок и условия гарантии.
Preview Руководство по эксплуатации и гарантийный талон Fe RRUM кассетных кондиционеров
Подробное руководство пользователя и гарантийный талон для кассетных кондиционеров Fe RRUM. Информация по установке, эксплуатации, обслуживанию и устранению неисправностей.
Preview KEYENCE AI Series Pattern Matching Sensor: Advanced Area Detection
Discover the KEYENCE AI Series Pattern Matching Sensor, offering redefined area detection with its proprietary AIA technology. Learn about its easy one-button teaching, versatile detection modes (Presence/Absence, Differentiation), and user-friendly features for industrial automation.