1. Introduction
The GEYA GYHC Modular Contactor is designed for remote control applications in various alternative networks. These contactors are available in versions with and without manual operation capabilities, offering versatility for a wide range of uses.
Typical applications include:
- Lighting systems
- Heating and ventilation systems
- Roller shutters
- Public hot water control
- Mechanical ventilation systems
- Load-shedding of non-priority circuits
The GYHC contactor series can be extended with auxiliary control, protection, and indication functions to meet diverse application requirements.

2. Safety Information
WARNING: Electrical shock hazard. Installation and maintenance should only be performed by qualified personnel.
- Always disconnect power before installing, servicing, or removing the contactor.
- Ensure all wiring complies with local and national electrical codes.
- Verify correct voltage and current ratings before connecting the device.
- Do not operate the contactor if it appears damaged.
- Keep children away from electrical installations.
3. Specifications
3.1 Technical Parameters
| Main Circuit | Value |
|---|---|
| Rated Voltage (Ue) 1P,2P | 250V AC |
| Rated Voltage (Ue) 3P,4P | 400V AC |
| Frequency | 50Hz |
| Service Life (O-C) Electrical Life | 30000 Times |
| Max Switching Frequency (per day) | 100 |
| Isolation Voltage (Ui) | 500 V AC |
| Class of Pollution | 2 |
| Rated Impulse Withstand Voltage (Uimp) | 2.5KV (4KV @ 12/24/48VAC) |
| Protection Grade (IEC 60529) Breaker body | IP20 |
| Protection Grade (IEC 60529) Installed inside the distribution box | IP40 |
| Operating Temperature | -5°C ~ +60°C (1) |
| Storage Temperature | -40°C ~ +70°C |
| Wet and Heat Resistance (IEC 6068.1) | Class 2 (relative humidity is 95% when the temperature is 55°C) |
| ELSV (extra low safety voltage) | Conforms to version 12/24/48VAC |
| Product control | Conforms to the requirement of SELV (safety extra low voltage) |
(1) When the contactor is installed inside the distribution box, a distance piece should be assembled on both sides of it to facilitate heat dissipation.

3.2 Product Models (En61095)
| Type | Rated Current (In) | Control Voltage (V AC 50Hz) | Contact | Width (Multiple of 9mm) |
|---|---|---|---|---|
| 2P | AC-7a 25A, AC-7b 8.5A | 230...240 | 2NO | 2 |
| AC-7a 40A, AC-7b 15A | 220...240 | 2NO | 2 | |
| AC-7a 63A, AC-7b 20A | 220...240 | 2NO | 4 | |
| 4P | 25A | 220...240 | 4NO | 4 |
| 40A | 220...240 | 4NO | 6 | |
| 63A | 220...240 | 4NO | 6 |

3.3 Detailed Specification Tables
| Automatic Household Contactor Specification Table | |
|---|---|
| GYHC-16 | 2P 16A 2NO, 2P 16A 2NC, 2P 16A 1NO1NC, 3P 16A 3NO, 4P 16A 4NO, 4P 16A 2NO2NC |
| GYHC-20 | 2P 20A 2NO, 2P 20A 2NC, 2P 20A 1NO1NC, 3P 20A 3NO, 4P 20A 4NO, 4P 20A 2NO2NC |
| GYHC-25 | 2P 25A 2NO, 2P 25A 2NC, 2P 25A 1NO1NC, 3P 25A 3NO, 4P 25A 4NO, 4P 25A 2NO2NC |
| GYHC-40 | 2P 40A 2NO, 2P 40A 2NC, 3P 40A 3NO, 4P 40A 4NO, 4P 40A 2NO2NC |
| GYHC-63 | 2P 63A 2NO, 2P 63A 2NC, 3P 63A 3NO, 4P 63A 4NO, 4P 63A 2NO2NC |
| Manual/Automatic Household Contactor Specification Table | |
|---|---|
| GYHC-16M | 2P 16A 2NO, 2P 16A 2NC, 4P 16A 4NO, 4P 16A 2NO2NC |
| GYHC-20M | 2P 20A 2NO, 2P 20A 2NC, 4P 20A 4NO, 4P 20A 2NO2NC |
| GYHC-25M | 2P 25A 2NO, 2P 25A 2NC, 4P 25A 4NO, 4P 25A 2NO2NC |
| GYHC-40M | 2P 40A 2NO, 2P 40A 2NC, 3P 40A 3NO, 4P 40A 4NO, 4P 40A 2NO2NC |
| GYHC-63M | 2P 63A 2NO, 2P 63A 2NC, 3P 63A 3NO, 4P 63A 4NO, 4P 63A 2NO2NC |

3.4 Dimensions


4. Installation
The GEYA GYHC Modular Contactor is designed for installation on a standard 35mm DIN guide rail. It can be mounted vertically or with a slight tilt (up to 30 degrees).
4.1 Wiring Instructions
Follow the wiring diagrams and torque specifications carefully to ensure a secure and safe connection. Use appropriate tools for stripping wires and tightening terminals.
| Type | Rated Current | Stripping Length | Circuit | Torque | Copper Line | |
|---|---|---|---|---|---|---|
| Hard Line | Flexible Line or Haze Line Terminal | |||||
| GYHC | 16-100A | 9mm | Control Loop | 0.8Nm | 1.5~2.5mm² | 1.5~2.5mm² |
| 16&25A | 9mm | Power Loop | 3.5Nm | 1.5 x 6mm² | 1 x 4mm² | |
| 40A-63A | 14mm | 6 x 2.5mm² | 6 x 16mm² | |||
| 100A | 6 x 35mm² | 6 x 35mm² | ||||
| GYHCS, GYHCC | PZ1.4mm | 9mm | - | 0.8Nm | 1.5 x 2.5mm² | 1.5 x 2.5mm² |
| 2 x 1.5mm² | 2 x 2.5mm² | |||||
| Type | Wiring Terminal | Rated Torque | Copper Line | |
|---|---|---|---|---|
| Hard Line | Flexible Line | |||
| GYHC24 | Power supply (N/P) | 1Nm | 0.5~10mm² | 0.5~6mm² |
| Input (Y1/Y2) | 2x0.5~2x2.5mm² | 2x0.5~2x2.5mm² | ||
| Type | Wiring Terminal | Copper Line | |
|---|---|---|---|
| Hard Line | Flexible Line | ||
| TI24 Connector | Spring clamp terminal | 1x0.5~1.5mm² | 1x0.5~1.5mm² |

4.2 Installation and Wiring Demonstration Video
Watch this video for a visual guide on wiring and operating the manual version of the AC contactor.
5. Operation
The GEYA GYHC Modular Contactor with manual operation features a selector switch with multiple positions to control its state.
5.1 Operating Modes
- Position O (Manual Turn Off): The contactor is manually turned off.
- Position auto (Automatic Operation): The contactor operates automatically based on the control signal (A1/A2).
- Position I (Manual Turn On): The contactor is manually turned on.
- Position I+P (Manual Permanent Turn On): The contactor is manually turned on and remains in this state.
When the A1/A2 control circuit is powered on, the contactor will return to the 'auto' (automatic) mode, overriding any manual 'I' or 'O' settings. To manually operate the contactor, push the paddle up or down to the desired position. To return to automatic mode from a manual 'I' or 'O' position, ensure the A1/A2 control circuit is powered, and the contactor will reset to 'auto'.


6. Maintenance
Regular maintenance ensures the longevity and reliable operation of your GEYA GYHC Modular Contactor.
- Visual Inspection: Periodically check the contactor for any signs of physical damage, discoloration, or loose connections.
- Cleaning: Ensure the contactor and its surroundings are free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquids or abrasive cleaners.
- Terminal Tightness: Over time, terminal screws can loosen. Periodically check and re-tighten all terminal connections to the specified torque (refer to Section 4.1).
- Heat Dissipation: Ensure adequate ventilation around the contactor, especially if distance pieces were used during installation to prevent overheating.
Always disconnect power before performing any maintenance.
7. Troubleshooting
If you encounter issues with your GEYA GYHC Modular Contactor, consider the following common troubleshooting steps:
- Contactor Not Engaging/Disengaging:
- Check if the control voltage (A1/A2) is present and within the specified range.
- Verify that the selector switch is in the 'auto' position for automatic operation, or the correct manual position for manual control.
- Inspect control wiring for loose connections or breaks.
- Overheating:
- Ensure proper ventilation and that no objects are obstructing airflow around the contactor.
- Verify that the load current does not exceed the contactor's rated current.
- Check for loose terminal connections, which can cause resistance and heat buildup.
- Auxiliary Contacts Not Functioning:
- Ensure auxiliary contacts are correctly installed and wired according to their specific diagrams.
- Verify that the main contactor is engaging properly, as auxiliary contacts operate in conjunction with the main contacts.
- Check for compatibility if using third-party auxiliary contact modules.
If the problem persists after these checks, contact qualified technical support.
8. User Tips
- Adding Auxiliary Contacts: For advanced control applications, the GYHC Modular Contactor can be extended with auxiliary contacts. Ensure you select compatible auxiliary contact modules and follow their specific installation and wiring instructions. This allows for additional control and feedback functionalities.
- Space Optimization: These modular contactors are designed to be compact, offering up to 70% space saving compared to traditional contactors. Plan your distribution box layout to take advantage of this feature for a cleaner and more efficient installation.
- Quiet Operation: The contactors are engineered for super-quiet operation, with noise levels less than 15dB, making them ideal for residential and noise-sensitive environments.
9. Warranty and Support
GEYA products are manufactured to high-quality standards and are certified to required industry standards, including CE, CB, SAA, ISO 9001, UK CA, and RoHS. This product comes with a manufacturer's warranty against defects in materials and workmanship under normal use.
For technical support, warranty claims, or further inquiries, please contact GEYA Official Store or refer to the contact information provided by the manufacturer. Keep your purchase receipt for warranty validation.