1. Introduction
The DUOYI DY4100A is a high-precision digital ground resistance tester designed for accurate measurement of ground resistance and various voltages. This instrument is characterized by its high accuracy, strong anti-interference capability, and reliability, making it widely applicable in diverse fields such as electricity, post-power, railway, petroleum, chemical industry, communication, and mining departments.
The DY4100B model extends functionality to include soil resistivity measurements, offering a comprehensive solution for grounding system analysis.


2. Safety Information
WARNING: To prevent electric shock or personal injury, please read all safety information before using the product.
- Always follow local and national safety codes.
- Do not use the instrument if it appears damaged or is operating abnormally.
- Ensure all test leads are properly connected before performing any measurements.
- Avoid touching the test leads or the circuit under test during measurement.
- Do not exceed the maximum input ratings for any function.
- Replace batteries promptly when the low battery indicator appears.
- Keep the instrument dry and clean.
3. Product Overview
3.1. Components and Accessories
The standard package includes the following items:
- DUOYI DY4100A/DY4100B Ground Resistance Tester unit
- Cloth bag for storage and transport
- User Manual / Capacity Certificate
- 2 sets of test lines (red, yellow, green)
- Ground rods: 2 for DY4100A, 4 for DY4100B (for soil resistivity measurement)


3.2. Key Features
- Ground Resistance Measurement: Ranges from 2Ω to 2000Ω with high resolution (0.001Ω).
- Voltage Measurement: AC voltage up to 600V and DC photovoltaic voltage up to 1500V.
- Soil Resistivity Measurement: Available on DY4100B model using the 4-pole method.
- Multi-gear Selection: Rotary dial for easy selection of measurement ranges.
- HD Display Screen: Segment LCD display with backlight for clear readings.
- Overload Protection: Ensures safety and durability of the instrument.
- Interference Voltage Warning: Automatically detects and warns of series interference voltage during tests.
- Data Hold Function: Allows for easy recording of measurements.
- Automatic Shutdown: Powers off after 5 minutes of inactivity to conserve battery.
- Battery Voltage Warning: Displays a battery logo when power is low.
- Test Methods: Supports Simple 2-wire, Precision 3-wire, and Precision 4-wire (DY4100B only) methods.


4. Specifications
| Feature | Description / Value |
|---|---|
| Test Method | Voltage reduction method |
| Soil Resistivity Test | 4 pole methods (Limited to DY4100B applicable) |
| Display | Segment LCD display with backlight |
| Battery Voltage Warning | Battery logo display |
| Continuous Test Times | During 20Ω range, test once per 30 seconds with 1Ω load. Can be performed repeatedly for more than 400 times. |
| Input Exceeds Display | Shows "ol" |
| Automatic Shutdown Function | If no operation for 5 minutes after button operation, the system will enter automatic shutdown state. |
| Overload Protection | AC280V/10 seconds between E-S port |
| Withstand Voltage | AC3540V (50/60Hz) between electrical loop and outer box / 5 seconds |
| Insulation Resistance | Electrical circuit and outer box are 50MΩ or more / DC1000V |
| Overall Dimensions | 173 x 125 x 68 mm |
| Weight | About 600g (including battery) |
| Power Supply | 6 AA5 batteries |
| Scope of Application | Agricultural equipment distribution wires, indoor wiring, electrical machinery, etc. |
4.1. Measurement Ranges and Resolutions
| Measurement Type | Range | Resolution | |
|---|---|---|---|
| Ground Resistance | 2Ω | 0.03 ~ 2.00Ω | 0.001Ω |
| 20Ω | 0.03 ~ 20.00Ω | 0.01Ω | |
| 200Ω | 0.3 ~ 200.0Ω | 0.1Ω | |
| 2000Ω | 3 ~ 2000Ω | 1Ω | |
| Soil Resistivity (DY4100B) | 2Ω | 0.2 ~ 376.8Ω·m | N/A |
| 20Ω | 0.2 ~ 3768Ω·m | N/A | |
| 200Ω | 0.002 ~ 37.68KΩ·m | N/A | |
| 2000Ω | 0.02 ~ 376.8KΩ·m | N/A | |
| Port to Ground Voltage (AC) | 0 ~ 600Vac | 1V | |
| Photovoltaic Voltage (DC) | 0 ~ 1500Vdc | 1V |


5. Setup
5.1. Battery Installation
The DY4100 series requires 6 AA5 batteries for operation. To install or replace batteries:
- Locate the battery compartment on the back of the instrument.
- Open the battery cover.
- Insert 6 AA5 batteries, ensuring correct polarity (+/-).
- Close the battery cover securely.
5.2. Connecting Test Leads and Ground Rods
Proper connection of test leads and ground rods is crucial for accurate measurements. Refer to the specific measurement method diagrams below for detailed wiring.
The instrument has the following ports:
- V: Voltage input
- C: Current electrode (for 3-wire and 4-wire methods)
- P: Potential electrode (for 3-wire and 4-wire methods)
- E/COM: Earth electrode / Common (for all methods)
- S: Potential electrode (for 4-wire soil resistivity, DY4100B only)
- ES: Current electrode (for 4-wire soil resistivity, DY4100B only)

6. Operating Instructions
6.1. Power On/Off
To power on the instrument, rotate the central dial from the "关机" (Off) position to the desired measurement range (e.g., 2Ω, 20Ω, 200Ω, 2000Ω, or voltage ranges). To power off, rotate the dial back to "关机". The instrument also features an automatic shutdown function after 5 minutes of inactivity.
6.2. Selecting Measurement Range
Use the large rotary dial in the center of the instrument to select the appropriate measurement range for ground resistance (2Ω, 20Ω, 200Ω, 2000Ω) or voltage (AC600V, DC1500V). For soil resistivity (DY4100B only), select the corresponding range.
6.3. Performing a Test
- Ensure the test leads and ground rods are connected correctly for the desired measurement method (refer to Section 7).
- Select the appropriate range using the rotary dial.
- Press the "测试" (Test) button to initiate the measurement.
- The measurement result will be displayed on the LCD screen.
6.4. Backlight Function
Press the "确认/背光" (Confirm/Backlight) button to turn the display backlight on or off, improving readability in low-light conditions.
6.5. Data Hold Function
The instrument supports a data hold function. While a measurement is displayed, pressing a specific button (usually indicated by a hold symbol or part of the "功能" button group) will freeze the reading on the screen. Press again to release.
6.6. Interference Voltage Warning
The DY4100 series automatically detects and warns of series interference voltage during ground resistance and soil resistivity tests. If an abnormal test result or interference is detected, a warning will be displayed, indicating potential inaccuracies due to external electrical noise.

7. Measurement Methods
The DY4100 series supports various wiring configurations for ground resistance and soil resistivity measurements. Always ensure auxiliary ground electrodes are placed at appropriate distances and the soil is adequately moist for accurate readings.
7.1. Simple 2-Wire Wiring Scheme
This method is suitable for quick checks where a known good ground (e.g., water pipe) is available. Connect the E/COM terminal to the measured grounding body and the V terminal to the known good ground.

7.2. Precision 3-Wire Wiring Diagram
The 3-wire method is commonly used for general ground resistance measurements. It involves the measured grounding body and two auxiliary ground electrodes (P and C). The auxiliary ground electrodes should be placed in a straight line from the measured grounding body, typically 5-10 meters apart.

7.3. Precision 4-Wire Wiring Diagram (DY4100B Only)
This method is used for highly accurate ground resistance measurements, especially when the resistance of the test leads themselves might affect the reading. It uses separate potential (P, S) and current (C, ES) electrodes. This method is limited to the DY4100B model.

7.4. Soil Resistivity 4-Pole Method (DY4100B Only)
The 4-pole method for soil resistivity measurement (Wenner method) requires four auxiliary ground electrodes (H/V, S, ES, E). The electrodes should be placed in a straight line at equal intervals (e.g., 1-30 meters). This method is exclusive to the DY4100B model.

Important Note: If the auxiliary ground electrode resistance is too large, the display value may have errors. This can occur if the electrodes are not tested in a dry place or with lots of small stones and sand. Sprinkle water from the auxiliary part of the ground rod to keep it fully moist. When testing on concrete, flatten the auxiliary grounding rod with water or place it on the auxiliary grounding rod with a damp cloth for testing.
8. Maintenance
- Cleaning: Use a soft, damp cloth to clean the instrument's casing. Do not use abrasive cleaners or solvents.
- Storage: Store the instrument in a dry, cool place, away from direct sunlight and extreme temperatures. If storing for an extended period, remove the batteries to prevent leakage.
- Battery Replacement: Replace all 6 AA5 batteries when the low battery indicator appears on the display. Ensure correct polarity.
- Calibration: For continued accuracy, periodic calibration by qualified personnel is recommended.
9. Troubleshooting
- Display shows "ol"
- This indicates that the input value exceeds the selected measurement range. Rotate the dial to a higher range or check the circuit for excessively high resistance/voltage.
- Inaccurate Readings
- Check battery level; replace if low.
- Ensure test leads are securely connected and not damaged.
- Verify auxiliary ground electrode placement and soil conditions (moisture, presence of stones).
- Check for strong electromagnetic interference in the testing environment.
- Ensure the correct measurement method (2-wire, 3-wire, 4-wire) is being used for the application.
- Instrument does not power on
- Check if batteries are installed correctly and have sufficient charge.
- Ensure the rotary dial is moved from the "关机" (Off) position to a measurement range.
10. User Tips
No specific user tips were available from provided reviews or Q&A. However, general best practices for using ground resistance testers include:
- Always perform a preliminary check of the instrument's functionality before critical measurements.
- For best accuracy, especially in dry conditions, ensure the soil around auxiliary electrodes is moistened.
- When possible, use the 3-wire or 4-wire method for more accurate ground resistance measurements compared to the 2-wire method.
- Keep the test leads untangled and in good condition to avoid measurement errors.
11. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your original point of purchase or the manufacturer directly. Keep your purchase receipt as proof of purchase.