Schneider A9C20834

Contents

Schneider ICT Modular Contactor Instruction Manual

Model: A9C20834

Brand: Schneider Electric

1. Introduction

This manual provides essential information for the safe and effective installation, operation, and maintenance of the Schneider ICT Modular Contactor, Model A9C20834. This device is designed for controlling electrical circuits in motor, heating, and lighting applications.

2. Product Overview

The Schneider Acti9 iCT modular contactor is a 4-pole device with 4 normally open (NO) contacts, suitable for AC grid types. It features remote control capability with a self-holding control signal type and includes a trip indication window for local signal indication.

Front view of Schneider ICT modular contactor A9C20834
Figure 1: Front view of the Schneider ICT modular contactor, showing terminal markings A1, A2, 1, 3, 5, 7 and 2, 4, 6, 8, along with 25A rating.
Angled top-rear view of Schneider ICT modular contactor A9C20834
Figure 2: Angled view from the top-rear, providing a different perspective of the terminals and the model number A9C20834.

3. Specifications

FeatureSpecification
Product RangeActi9
Product NameActi9 iCT
Product TypeContactor
Model NumberA9C20834
ApplicationMotor, Heating, and Lighting
Poles4P
Contact Type4 NO (Normally Open)
Rated Operating Current (Ie)25 A AC-7A, 8.5 A AC-7B
Grid TypeAC
Control TypeRemote control
Control Loop Voltage (Uc)220...240 V AC 50 Hz
Grid Frequency50 Hz
Rated Operating Voltage (Ue)400 V AC 50 Hz
Maximum Power1.6W (up to 400 V AC)
Rated Insulation Voltage (Ui)500 V AC 50/60 Hz
Rated Impulse Withstand Voltage (Uimp)4 kV
Control Signal TypeSelf-holding
Local Signal IndicationTrip indication window
Suction Power (VA)4.6 VA
Power Consumption (VA)34 VA (~50Hz)
Installation TypeLock clip locks
Installation Mode35 mm DIN guide rail
Width (multiple of 9mm)4
Altitude81 mm
Breadth36 mm
Profundity60 mm
ColorWhite
Mechanical Life1 million times
Electrical Life (AC-7A)100,000 times (IEC/EN 61095 25 A 50 Hz)
Electrical Life (AC-7B)30,000 times (IEC/EN 61095 8.5 A 50 Hz)
Electrical Life (AC-7C)30,000 times (IEC/EN 61095 50 Hz)
Electrical Life (AC-1)100,000 times (EN/IEC 60947-4-1 50 Hz)
Electrical Life (AC-3, AC-5a, AC-5b)30,000 times (EN/IEC 60947-4-1 50 Hz)
Standards MetIEC/EN 61095
Noise Level30 dB
Heat Dissipation1.6W (on 50/60 Hz)
IP Protection LevelIP20
Pollution Level2
Resistance to Moisture and Heat2 (in accordance with EN 60947-4-1, EN 61095, IEC 1095)
Relative Humidity95% (up to 55 °C)
Working Altitude2000 m
Operating Temperature-5...60 °C
Storage Ambient Temperature-40...70 °C
Side view of Schneider ICT modular contactor with detailed specifications
Figure 3: Detailed side view displaying technical specifications including IEC/EN 61095 standard, Ui 500V, Ue 220/240V~, AC-7a 25A, AC-7b 8.5A, and GB17885 Us/Uc 24V~ AC-7a. Also shows 'Made in FRANCE'.

4. Setup and Installation

The Schneider ICT modular contactor is designed for easy installation on a 35 mm DIN guide rail using its integrated lock clip locks. Ensure all power is disconnected before beginning installation.

4.1 Mounting

  1. Locate a suitable 35 mm DIN rail within your electrical enclosure.
  2. Position the contactor onto the DIN rail, ensuring the lock clips engage securely.
  3. Verify the contactor is firmly seated and cannot be easily dislodged.
Side view of Schneider ICT modular contactor showing DIN rail mounting
Figure 4: Side view of the contactor, illustrating its compact profile and DIN rail mounting mechanism.
Bottom view of Schneider ICT modular contactor showing DIN rail clip
Figure 5: Bottom view of the contactor, highlighting the yellow DIN rail clip and CE certification mark.

4.2 Wiring

Refer to the terminal markings on the device (A1, A2 for control; 1, 3, 5, 7 and 2, 4, 6, 8 for power) and the wiring capacity specifications below. Always follow local electrical codes and safety regulations.

  • Control Loop: Tunnel terminal, 2 cables 1.5 mm² single strand hard wire OR 1 cable 1.5...2.5 mm² single strand hard wire OR 2 cables 1.5...2.5 mm² cord.
  • Power Supply Circuit: Tunnel terminal, 1 cable 1...4 mm² flexible cable.
  • Power Loop: Tunnel terminal, 1 cable 1.5...6 mm² single strand hard wire.

Tightening Torque:

  • Control loop: 0.8 N.m
  • Power supply loop: 0.8 N.m

Ensure all connections are tight and secure to prevent loose contacts and potential hazards.

5. Operating Instructions

The Schneider ICT modular contactor operates via remote control with a self-holding control signal. When the control loop voltage (220-240 V AC 50 Hz) is applied to terminals A1 and A2, the contactor will energize, closing the 4 NO power contacts (1-2, 3-4, 5-6, 7-8) and allowing current to flow through the connected load (motor, heating, or lighting circuit).

A trip indication window provides local visual feedback on the contactor's status.

6. Maintenance

Regular inspection and maintenance are crucial for ensuring the longevity and safe operation of your modular contactor. Always disconnect power before performing any maintenance.

  • Visual Inspection: Periodically check for any signs of physical damage, discoloration, or loose connections.
  • Terminal Tightness: Re-check terminal screw tightness to ensure proper electrical contact.
  • Cleaning: Keep the contactor free from dust and debris. Use a dry, non-abrasive cloth for cleaning.

No user-serviceable parts are inside the sealed unit. Do not attempt to disassemble the contactor.

7. Troubleshooting

If the contactor is not functioning as expected, consider the following:

  • No Operation: Verify that the control loop voltage (220-240 V AC 50 Hz) is correctly applied to terminals A1 and A2. Check for breaks in the control circuit wiring.
  • Intermittent Operation: Inspect all wiring connections for tightness and ensure they meet the specified tightening torque.
  • Overheating: Ensure the contactor is operating within its rated current (25 A AC-7A, 8.5 A AC-7B) and that the ambient temperature is within the operating range (-5 to 60 °C). Check for proper ventilation.
  • No Power to Load: Confirm that the main power supply to the contactor's power terminals (1, 3, 5, 7) is present and that the load is correctly wired to the output terminals (2, 4, 6, 8).

If issues persist, consult a qualified electrician.

8. User Tips

No specific user tips were available from reviews or Q&A for this product. Always ensure professional installation for electrical components.

9. Warranty and Support

This Schneider ICT modular contactor is a genuine original Schneider Electric product. For warranty information, technical support, or service, please refer to the official Schneider Electric website or contact their authorized distributors. Keep your purchase records for any warranty claims.