GEYA GSP6-C40

Contents

GEYA GPS6 Series Surge Protective Device (SPD) Instruction Manual

Model: GSP6-C40

1. Introduction

The GEYA GPS6 Series Surge Protective Device (SPD) is designed to safeguard electrical systems and on-loading electrical apparatus from damage caused by thunder and instantaneous over-voltage. This device is applicable to power systems such as TN-S, TN-C-S, TT, and IT with an AC frequency of 50/60Hz and a voltage of 380V. It is intended for installation on the connectors of LPZ1 or LPZ2 and LPZ3 zones, adhering to IEC61643-1 and GB18802.1 standards. Each module of the surge protection device includes a fault relief device.

GEYA GPS6 Series Surge Protector units
GEYA GPS6 Series Surge Protector units, showing application in electrical systems.

2. Product Features

  • Internal Protection: Equipped with internal overcurrent and overheat protection, featuring open temperature control.
  • Modular Design: Convenient module design allows for easy installation and online replacement.
  • Performance: Exhibits low leakage current, rapid response time, and reduced residual voltage.
  • Status Indication: Includes a signal indication device: green indicates normal operation, while red signifies an abnormal or fault state.
  • Advanced Technology: Utilizes new technology with high energy, gap discharge electrode (N-PE).
  • Material Quality: The shell is constructed from UL94-V0 flame-retardant PC material, ensuring high protective insulation and preventing fire hazards in case of line faults.
  • Manufacturing Precision: Features fully automatic soldering for stable soldering points, minimizing premature indicator changes.
  • Certified Components: Incorporates core components with certification certificates for enhanced stability and quality.
Flame retardant PC material for GEYA SPD
The device casing is made from UL94-V0 flame-retardant PC material for enhanced safety.

3. Specifications

AttributeValue
Brand NameGEYA
Model NumberGSP6-C40
TypeResidual Current, Circuit breaker
Poles1P/2P/3P/4P
Rated Voltage (Uc)275VAC
Nominal Discharge Current (In (8/20µs))20kA
Maximum Discharge Current (Imax (8/20µs))40kA
Voltage Protection Level (Up)1.5kV
Response Time≤25 NS
Protection GradeIP20
Operating State IndicationGreen (Normal)
Fault IndicationRed (Abnormal)
CertificationCE, RoHS
Is Smart DeviceYes
Dimension drawing of GEYA SPD
Dimension drawing: 54mm width (for 2P), 95mm height, 68mm depth, 45mm module height, 50mm module depth. Unit: mm.
Product size for 1P and 2P GEYA SPD
Product sizes: 1P unit is 36mm wide, 90mm high. 2P unit is 72mm wide, 90mm high.

4. Setup and Installation

The GSP6 series SPD is designed for installation on a 35mm standard DIN rail. Ensure all power is disconnected before attempting installation.

4.1 Installation Steps

  1. Mount the SPD unit securely onto a 35mm DIN rail. The guide buckle design facilitates easier installation.
  2. Connect the appropriate wiring according to the specific pole configuration (1P, 2P, 3P, or 4P) of your system. Refer to the wiring diagrams below.
  3. Ensure all connections are tight and secure.
  4. Verify the operating state indicator is green after power is restored.
Guide buckle design for easier installation
The guide buckle design on the SPD unit simplifies installation onto a DIN rail.

4.2 Wiring Diagrams

Below are the wiring diagrams for different pole configurations. Always ensure proper grounding (PE) connection.

Wiring diagram for 1P GEYA SPD
1P Wiring Diagram: Connect Line (L/N) and Protective Earth (PE). F1 and F2 represent fuses or circuit breakers for protection.
Wiring diagram for 2P GEYA SPD
2P Wiring Diagram: Connect Line (L), Neutral (N), and Protective Earth (PE). F1 and F2 represent fuses or circuit breakers for protection.
Wiring diagram for 3P GEYA SPD
3P Wiring Diagram: Connect three Line phases (L, L, L) and Protective Earth (PE). F1 and F2 represent fuses or circuit breakers for protection.
Wiring diagram for 4P GEYA SPD
4P Wiring Diagram: Connect three Line phases (L, L, L), Neutral (N), and Protective Earth (PE). F1 and F2 represent fuses or circuit breakers for protection.

5. Operating Instructions

Once installed and connected to the power system, the GSP6 SPD operates automatically to protect against surge voltages. There are no user-adjustable settings.

5.1 Status Indicator

Each module of the SPD is equipped with a visual status indicator:

  • Green Indicator: Signifies that the surge protective device is operating normally and providing protection.
  • Red Indicator: Indicates that the surge protective device has absorbed a significant surge and is no longer providing protection. The module needs to be replaced.
Green and Red indicators on GEYA SPD
Visual indicators: Green for normal operation, Red for fault/replacement needed.

6. Maintenance

The GSP6 SPD is designed for minimal maintenance. Regular visual inspection is recommended.

  • Visual Inspection: Periodically check the status indicator on each module. If any indicator is red, the corresponding module has reached its end-of-life and requires replacement.
  • Module Replacement: In case of a red indicator, the faulty module can be replaced online without disconnecting the entire system, thanks to its modular design. Ensure to follow all safety procedures and disconnect power to the specific circuit before replacing a module.
  • Cleaning: Keep the device free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.

7. Troubleshooting

The primary troubleshooting step for the GSP6 SPD involves checking the status indicator.

  • Problem: Red indicator light is on.
  • Solution: A red indicator signifies that the module has absorbed a surge and is no longer functional. The module needs to be replaced. Refer to the 'Maintenance' section for replacement procedures.
  • Problem: No indicator light or device not functioning as expected.
  • Solution: Ensure proper power supply to the circuit and correct wiring connections. If the issue persists, consult a qualified electrician.

8. User Tips

  • Always ensure the power is completely off before performing any installation or maintenance work on electrical systems.
  • For optimal protection, ensure the SPD is correctly matched to your electrical system's voltage and current specifications.
  • Regularly check the status indicators, especially after severe weather conditions, to ensure continuous protection.

9. Warranty and Support

For warranty information, technical support, or service inquiries, please contact GEYA customer service or your authorized dealer. Keep your purchase receipt as proof of purchase.

© 2024 GEYA. All rights reserved.

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.