GEYA G2R MINI ATS

Contents

GEYA G2R Din Rail Dual Power Automatic Transfer Switch User Manual

Model: G2R-63 | Brand: GEYA

1. Introduction

The GEYA G2R-63 automatic transfer switch (ATS) is a PC class infrequent change-over switch designed for two-station operation (commonly used for main power 'A' and standby power 'B'). It is suitable for AC systems with a frequency of 50-60Hz and rated currents ranging from 6A to 63A.

The primary function of this ATS is to automatically switch to backup power when the main power supply fails, ensuring uninterrupted operation of connected loads. This transfer occurs rapidly (within <50 milliseconds), effectively mitigating inconveniences caused by power outages. When both main and backup power sources are available, the system prioritizes the main power supply.

GEYA G2R-63 Dual Power Automatic Transfer Switch
GEYA G2R-63 Dual Power Automatic Transfer Switch

2. Important Safety Notice

Please read this manual carefully before installing or operating the product. Unauthorized disassembly of the product is strictly prohibited to prevent instrument failure or malfunctions. GEYA Electric shall not be held liable for any errors or omissions that may exist in this document.

2.1. G2R ATS Usage Precautions

  • Voltage Compatibility:
    - 220V ATS models should not be used with a voltage lower than 185V to prevent coil burnout.
    - 110V ATS models should not be used with a voltage lower than 90V to prevent coil burnout.
  • Manual Switching: The switch cannot be manually operated when in automatic mode, as this may cause coil burnout.
  • Phase Sequence (4P ATS): For 4P ATS models, ensure correct connection of the phase sequence to prevent contact burnout.

2.2. General Cautions

  • Professional Installation: Only qualified professionals should install and commission the ATS.
  • Installation Environment: Install the ATS on a clean, dry surface with adequate airflow.
  • Electrical Connections: Ensure all connections are secure to prevent overheating and fire hazards.
  • Neutral-Ground Bonding: Do not connect the neutral line to the grounding system, as this can create hazards.
  • Local Regulations: Ensure compliance with applicable local electrical codes for safety and reliability.

3. Specifications

3.1. Technical Parameters

GEYA G2R-63 Technical Parameters
GEYA G2R-63 Technical Parameters
AttributeValue
Model NumberG2R MINI ATS
Rated Operating Current Ie(A)6A/10A/16A/20A/25A/32A/40A/50A/63A
Rated Insulation Voltage Ui690V
Rated Impulse Withstand Voltage Uimp8kV
Rated Working Voltage UeAC220V/AC110V
Rated Frequency50/60Hz
Auxiliary CircuitAC220V/110V 50/60Hz Ie=5A
Mechanical Life≥8000 times
Electrical Life≥1500 times
Usage CategoryAC-31B
Level AttributePC-grade isolated type
Switching Speed<50 milliseconds
Poles2P
MountingDin Rail Type
CertificationCE
Wireless FunctionalityNo
Battery IncludedNo
EU LVD VoltageLow voltage: Below 50Vac or 75Vdc
High-concerned chemicalnone

3.2. Dimensions

GEYA G2R-63 Dimension Drawing
GEYA G2R-63 Dimension Drawing (2P and 4P)
GEYA G2R-63 Detailed Dimensions
GEYA G2R-63 Detailed Dimensions

Note: Terminal wiring area is suitable for 1~25mm² wires. Wire connection screw is M5, with a recommended torque of 2.5N.m.

3.3. Working Conditions

  • Altitude: Up to 2000 meters
  • Operating Temperature Range: -5°C to +40°C (24-hour average must not exceed +35°C)
  • Storage Temperature Range: -25°C to +55°C (transient peaks up to +70°C)
  • Operating Humidity: Up to 50% at +40°C; up to 90% at +20°C (condensation prevention required)
  • Contamination Level: Level 3
  • Protection Rating: IP30
  • Overvoltage Category: Category III (main circuit), Category II (control/auxiliary circuits)
  • Mounting Orientation: The ATS can be installed vertically or horizontally in cabinets. For specific installation requirements, consult GEYA.

4. Setup and Installation

Installation and wiring must be performed by qualified personnel familiar with this manual. Before installation, check the ATS for any damage or missing parts.

4.1. DIN Rail Installation

  1. Insert the upper end of the ATS base into the DIN rail.
  2. Push the lower end of the ATS base into the DIN rail until the snap fastener locks securely.

4.2. DIN Rail Disassembly

  1. Insert a screwdriver into the round hole of the DIN rail snap fastener at the bottom of the ATS.
  2. Use a screwdriver to pry the DIN rail snap fastener downward.
  3. Tilt the ATS upwards and remove it from the DIN rail.

4.3. Screw Mounting

  1. Pull out the upper and lower snap fasteners located at the bottom of the ATS.
  2. Secure the ATS to the panel with screws.
DIN Rail Installation and Screw Mounting Instructions
DIN Rail Installation and Screw Mounting Instructions

4.4. Wiring Instructions

The ATS is equipped with screw type terminals, each with a width of 7.4 mm, suitable for copper wires with a cross-sectional area of 1 to 16 mm².

  1. Strip the wire to a length of 12 to 15 mm. It is recommended to use a duckbill-shaped terminal for secure connection.
  2. Tighten the screws with a recommended torque of 2.5 Nm to ensure proper tightening without damaging the terminals.
  3. Connect the phase (L) and neutral (N) wires of the main power supply to the input terminals (I) N1 A1.
  4. Connect the phase (L) and neutral (N) wires of the backup power supply to the input terminals (II) N2 A2.
  5. Connect the load output neutral wire to 'N A' and the load output live wire to 'LOAD'.
GEYA G2R-63 Wiring Diagram
GEYA G2R-63 Wiring Diagram
GEYA G2R-63 Panel Description
GEYA G2R-63 Panel Description with labeled components
GEYA G2R-63 Detailed Wiring Instructions
GEYA G2R-63 Detailed Wiring Instructions

Video: GEYA G2R-63 Automatic Transfer Switch demonstration, including wiring and operation in manual and automatic modes.

5. Operation

5.1. Manual/Automatic Mode Selection

The G2R-63 ATS features both manual and automatic operation modes. The selector switch allows you to choose between these modes.

  • Automatic Mode (Auto): This is the recommended mode for reliable operation. In this mode, the ATS automatically detects power failures and switches between the main and backup power supplies.
  • Manual Mode (Manu): This mode allows for manual switching between power sources.

Important:

  • Manual operation can ensure the opening and closing performance of electrical operation, but due to varying operator speeds, it may lead to excessive silver alloy loss.
  • The selector switch should only be pulled to the manual position after all power has been cut off for inspection and maintenance of the operating system and contact information.
  • Normally, keep the selector switch in the automatic position. When manual operation is required, switch to the manual position. After manual operation is complete, return the selector switch to the automatic position.

5.2. Power Transfer Logic

  • When the main power supply (Common Power Supply A) fails, the ATS will automatically switch to the backup power supply (Backup Power Supply B) to continue working.
  • When the main power supply resumes, the ATS will switch back to the main power supply, as it has priority.
  • The switching speed is less than 50 milliseconds.

6. Maintenance

Maintenance and inspection must be performed by qualified personnel after disconnecting all power supplies.

  • Initial Inspection: The first inspection should be completed within 6 months of commissioning.
  • Regular Inspection: Inspect at least once per year. In harsh environments, increase inspection frequency as needed.
  • Routine Cleaning: Periodically remove dust and debris to ensure optimal performance.
  • Electrical Contact Check: Inspect electrical contacts for wear or damage and tighten any loose connections to maintain reliable operation.
  • Humidity Control: Maintain a dry environment to prevent moisture-related malfunctions.
  • Insulation Testing: Routinely test insulation resistance to verify adherence to safety standards. If the ATS is damp or idle for an extended period, dry it thoroughly and measure insulation resistance with a 500V megohmmeter (minimum 10 MΩ).
  • Proper Storage: Store the ATS in a protected environment, shielded from dust, humidity, and physical harm when not in use.

Adhering to these refined maintenance procedures ensures the safe and effective functionality of the ATS.

7. Troubleshooting

  • Coil Burnout: Ensure the operating voltage is within the specified range (e.g., for 220V ATS, voltage should not be lower than 185V; for 110V ATS, not lower than 90V). Also, avoid manual switching while in automatic mode.
  • Contact Burnout (4P ATS): Verify that the phase sequence is correctly connected.
  • Control Circuit Damage: The control circuit TSE is immediately energized. If internal switches malfunction after transfer, the control coil may be damaged. Ensure a stable power supply to avoid coil damage. The coil operates reliably within 85%-110% of its rated voltage; insufficient voltage can cause overheating and failure.
  • Product Malfunctions: Unauthorized disassembly is strictly prohibited and can lead to instrument failure or malfunctions.
  • Dielectric Testing: This product has undergone insulation testing before leaving the factory. Incorrect dielectric testing will damage the control system, and it is strictly prohibited to conduct dielectric testing with ATS.

8. User Tips

  • Easy Installation: Users have found the ATS easy to connect and install, especially with the included DIN rail.
  • DIN Rail Orientation: Some users noted that the unit might fit on a DIN rail better when oriented in a specific way (e.g., upside down), though this might vary by specific setup.
  • Inverter Compatibility: If using with an inverter, ensure the inverter's power is sufficient and consider if a 'forced zero' connection is required for automatic switching from the inverter.
  • Reliability: The product is generally considered reliable, with some units performing flawlessly for years.
  • Switching Delay: Expect a switching delay of approximately 10 seconds when transferring power from an inverter to the mains.

9. Frequently Asked Questions (FAQ)

Q: Is this ATS designed for priority PV (photovoltaic) systems?
A: The GEYA G2R-63 ATS is primarily designed for switching between a main power source (e.g., city power) and a backup power source (e.g., generator). While it can be integrated into systems with PV, its default logic prioritizes the main power supply (Source A) when both are available, rather than specifically prioritizing PV. For dedicated PV priority systems, other ATS models might be more suitable.

10. Warranty and Support

For detailed warranty information, technical support, or any questions regarding the product, please refer to the official user manual PDF or contact GEYA customer service.

You can view the full user manual in PDF format here: GEYA G2R-63 User Manual (PDF)