EARU EAATS-F-CS-80

Contents

EARU Mini ATS Solar PV Dual Power Automatic Transfer Switch

Model: EAATS-F-CS-80

Brand: EARU

1. Product Overview

The EARU Mini Automatic Transfer Switch (ATS) is a compact and efficient device designed to automatically switch between two power sources, such as solar energy and city power, ensuring an uninterrupted power supply. It features both automatic and manual operation modes, providing flexibility and reliability for various applications.

EARU ATS with Solar Energy and City Power diagram

Image: Diagram illustrating the automatic transfer between Solar Energy and City Power.

2. Setup and Installation

This ATS is designed for easy installation on a 35MM Din Rail. Ensure all connections are secure and follow local electrical codes.

2.1 Terminal Wiring

The terminal wiring area accommodates wires from 1-25mm². The wire connection screws are M5, and the recommended torque is 2.5N.m.

2.2 Wiring Diagrams

Refer to the following diagrams for proper wiring of 2P and 4P models:

2P Wiring Diagram

2P Wiring Diagram for EARU ATS

Image: Detailed wiring diagram for the 2P ATS model, showing connections for Generator, Solar Energy, Common Power Supply, Backup Power Supply, Auto/Manual Switch, Load Closing Indication, and Load Output Live Wire.

4P Wiring Diagram

4P Wiring Diagram for EARU ATS

Image: Detailed wiring diagram for the 4P ATS model, showing connections for Backup Power Neutral/Live Wire, Common Power Neutral/Live Wire, Common Power Supply with Electricity Indication, Backup Power Supply with Electricity Indication, Auto/Manual Switch, Load Closing Indication, Operation Handle, Common/Backup Power Supply, and Load Output Live Wire.

2.3 Mounting

The device can be directly installed onto a 35MM Din Rail, commonly found in household lighting distribution boxes. It features securing clips for easy installation.

35MM Standard Rail Installation

Image: The ATS mounted on a 35MM Din Rail within a distribution box.

3. Operating Instructions

The ATS offers both automatic and manual operation modes to manage power transfer between sources.

3.1 Automatic Mode

In automatic mode, the ATS will seamlessly switch power sources in the event of a primary power supply failure. The transfer action time is less than 20 milliseconds, ensuring minimal disruption.

Automatic Transfer Switch Operation Diagram

Image: Diagram illustrating the rapid conversion process between Primary Power Supply and Backup Power Supply when power is out or restored.

Operation in Automatic Mode:

  1. When the switch is in the common power position, and both common and standby power have power, it remains in the common power position. If common power fails, it switches to the standby power position.
  2. When the switch is in the standby position, and common power fails but standby has power, it remains in standby. If common power is restored, it switches back to common power.
  3. If common power is not available and standby is not available, when the PV (Solar) is calling, it will remain in the standby position and will not switch to common power.

Note: The common/standby power supply should be 230V AC. If it is a DC or low voltage power supply, it needs an inverter to convert it to 230V AC (Inverter to AC can only be used for City Grid-PV Energy. City Grid-Generator and City Grid-City Grid can not be used for the inverter).

3.2 Manual Mode

The device features a manual handle and adjustment buttons for direct control over the power supply selection.

Two Modes of Adjustment for EARU ATS

Image: Close-up of the ATS showing the manual/automatic adjustment buttons and the manual handle.

Important: When operating manually, the mode selection switch must be in the 'Manual' position. Do not attempt to manually switch the grey button handle while in 'AUTO' mode, as this may damage the internal coil.

3.3 Operational Demonstration Video

Video: A demonstration of the EARU ATS switching between automatic and manual modes, showing the response to power changes.

4. Maintenance

The EARU ATS is constructed with high-quality, durable materials for long-lasting performance.

  • Material: Made from PA66 flame-retardant material, ensuring high heat resistance, insulation, and safety.
  • Contacts: Utilizes industrial-grade silver contacts, which significantly enhance the product's lifespan and conductivity.
  • Durability: Designed for a mechanical durability of ≥6000 times and electrical endurance of ≥1500 times.

Regular visual inspection for any signs of wear or damage is recommended. Ensure terminals are free from dust and debris. No user-serviceable parts inside; refer to qualified personnel for repairs.

Features of EARU ATS: PA66 Flame-Retardant Material, Industrial Silver Contacts, 35MM Rail Mounting

Image: Visual representation of key features including material, contacts, and mounting.

5. Troubleshooting

If you encounter issues with your ATS, consider the following:

  • No Automatic Switching: Ensure the mode selection switch is set to 'AUTO'.
  • Manual Operation Issues: Verify the mode selection switch is set to 'MANU' before attempting manual adjustments. Operating the manual handle in 'AUTO' mode can cause damage.
  • Power Fluctuations: Check the stability of both primary and backup power sources.
  • No Power Output: Inspect all wiring connections for looseness or damage. Ensure input power is present and within specified voltage ranges.

For persistent issues, consult a qualified electrician or contact customer support.

6. Specifications

ParameterValue
Pole2P/4P
Rated Current80A
Rated Voltage (L+N)AC230V/110V
Frequency50/60Hz
Rated Insulation Voltage690V
Impulse Withstand Voltage8kV
Transfer Action Time20ms
Mechanical Durability≥6000 Times
Electrical Endurance≥1500 Times
Case Grade80
Utilization CategoryAC-31B
Tse ClassPC
CertificationCE
Installation35MM Din Rail
2P Width50mm / 1.97in
4P Width86mm / 3.39in
Height110mm / 4.33in
Depth78mm / 3.07in
Dimensions and product parameters for 2P and 4P models

Image: Detailed dimensions and product parameters for the ATS.

7. Warranty and Support

This EARU Automatic Transfer Switch is CE certified, indicating compliance with European safety, health, and environmental protection requirements. For technical support or warranty inquiries, please contact your retailer or the manufacturer directly.

8. User Tips

  • Enclosure Compatibility: When selecting an enclosure or distribution box, ensure its dimensions are sufficient to accommodate the ATS, considering both its width (50mm for 2P, 86mm for 4P) and depth (78mm).
  • Power Source Voltage: Always ensure that both your common and standby power sources are 230V AC. If using a DC or low voltage source, an appropriate inverter is required to convert it to 230V AC.
  • Safety First: Never attempt to manually switch the grey button handle when the device is in 'AUTO' mode. This can cause damage to the internal components. Always switch to 'MANU' mode for manual adjustments.
  • Professional Installation: For optimal safety and performance, it is highly recommended that installation and wiring be performed by a qualified electrician.