1. Introduction
The YHDC SCT019 is a split core current transformer designed for accurate AC current measurement without the need to break the primary circuit. It is ideal for monitoring and protection in various electrical systems. Its split core design allows for easy installation on existing power lines or equipment.
This manual provides essential information for the safe and effective installation, operation, and maintenance of your SCT019 current transformer.
2. Safety Information
Please read and understand all safety instructions before installing or operating the device. Failure to follow these instructions may result in electric shock, fire, or serious injury.
- Installation should only be performed by qualified personnel.
- Ensure that the power supply to the circuit being measured is disconnected before installation.
- The secondary winding of the current transformer must never be left open-circuited while current is flowing in the primary circuit. This can lead to dangerously high voltages. Always connect the secondary to a suitable load or short-circuit it if not in use.
- The dielectric strength between the input (bare conductor) and output is AC 800V/1min 50Hz. The dielectric strength between the output and housing is AC 3.5KV/1min 50Hz.
- Do not exceed the rated input current of the transformer.
- The device has a waterproof grade of IP00, meaning it is not protected against water ingress. Avoid exposure to moisture or liquids.
3. Product Overview
3.1 Features
- Split core design for easy installation without disconnecting primary cables.
- Safety lock buckle ensures secure closure.
- High accuracy (0.5% or 1%) for precise current measurement.
- Available with 0.333V or 33mA output types.
- Wide operating temperature range.
- CE certified.
3.2 Applications
The SCT019 current transformer is suitable for a variety of applications, including:
- Current measurement, monitoring, and protection for electrical wiring and equipment.
- Current and power measurement for electric motors, lighting, air compressors, heating and ventilation systems, air-conditioning equipment, and automation-control systems.
- Integration into current, power, and energy monitoring devices.
- Relay protection devices.
- Charging pile monitoring.
- Data center power monitoring.
3.3 Product Visual

4. Specifications
4.1 General Technical Index
- Mounting Type: Free hanging (In-Line)
- Material of Core: Permalloy
- Applicable Standards: GB20840-2014
- Operating Temperature: -25ºC ~ +70ºC
- Storage Temperature: -40ºC ~ +85ºC
- Frequency Range: 20Hz-1KHz
- Waterproof Grade: IP00
- Dielectric Strength:
- Input (bare conductor)/Output: AC 800V/1min 50Hz
- Output/Housing: AC 3.5KV/1min 50Hz
4.2 Model-Specific Parameters and Dimensions
The SCT019 series offers various input/output configurations. Refer to the diagrams below for detailed specifications and dimensions for both Voltage (V) output and Milliampere (mA) output types.

Note for V output type: The electrical parameters are typical values. The actual values shall be subject to the actual measurement of the product. Cable specifications: 0.5mm² black and white parallel lines, length 200cm-205cm. Secondary is not allowed to short circuit.

Note for mA output type: The electrical parameters are typical values. The actual values shall be subject to the actual measurement of the product. Cable specifications: 0.5mm² black and white parallel lines, length 200cm-205cm. Secondary is not allowed to open circuit.
5. Setup and Installation
The SCT019 current transformer is designed for easy installation due to its split core and safety lock buckle.
- Preparation: Ensure the power to the circuit you intend to measure is completely turned off and locked out. Verify with a voltage tester.
- Opening the CT: Locate the safety lock buckle on the side of the current transformer. Gently press or slide the buckle to release the two halves of the split core. The CT will open, allowing you to place it around the conductor.
- Positioning: Place the open current transformer around the single conductor (wire) through which the current to be measured flows. Ensure that only one conductor passes through the CT's opening.
- Closing the CT: Bring the two halves of the split core together until they click securely into place with the safety lock buckle. A proper closure is crucial for accurate readings.
- Wiring the Output:
- The CT comes with 0.5mm² black and white parallel lines, typically 200cm-205cm in length.
- Connect these output wires to your measurement device (e.g., energy meter, data logger, PLC input).
- For V output type (0.333V): Connect the output to a voltage input. The secondary winding must always be connected to a load; it is not allowed to be short-circuited.
- For mA output type (33mA): Connect the output to a current input. The secondary winding must always be connected to a load; it is not allowed to be open-circuited.
- Verification: Once installed and wired, restore power to the circuit and verify that your measurement device is receiving accurate readings.
Refer to Figure 2 and Figure 3 in the Specifications section for detailed wiring diagrams and dimensions relevant to your specific SCT019 model.
6. Operating Instructions
The SCT019 current transformer operates by sensing the magnetic field generated by AC current flowing through the primary conductor. This induces a proportional current or voltage in the secondary winding, which is then outputted to your connected measurement device.
- Ensure the CT is correctly installed around the primary conductor and securely closed.
- Connect the output leads to a compatible measurement device.
- The output signal (0.333V or 33mA, depending on model) is directly proportional to the primary AC current. Your measurement device should be configured to interpret this signal according to the CT's rated input and output. For example, a 100A/0.333V CT will output 0.333V when 100A flows through the primary.
- The frequency range for accurate operation is 20Hz-1KHz.
7. Maintenance
The YHDC SCT019 current transformer is designed for long-term, reliable operation with minimal maintenance.
- Cleaning: Keep the exterior of the CT clean and free from dust and debris. Use a dry, soft cloth for cleaning. Do not use liquid cleaners.
- Inspection: Periodically inspect the CT for any signs of physical damage, loose connections, or corrosion. Ensure the safety lock buckle remains functional and the core is tightly closed.
- Environment: Operate the device within its specified operating temperature and humidity ranges. As it has an IP00 waterproof grade, protect it from water and excessive moisture.
8. Troubleshooting
If you encounter issues with your SCT019 current transformer, consider the following troubleshooting steps:
| Problem | Possible Cause | Solution |
|---|---|---|
| No output or incorrect readings |
|
|
| Inconsistent readings |
|
|
If problems persist, contact YHDC customer support or your distributor for assistance.
9. User Tips
While no specific user feedback was provided, here are some general tips for optimizing the use of split core current transformers:
- Cable Centering: For best accuracy, try to center the primary conductor within the CT's opening.
- Avoid Multiple Conductors: Ensure only the single phase conductor you wish to measure passes through the CT. Passing multiple conductors (e.g., phase and neutral) will result in zero net current measurement.
- Proper Sizing: Select a CT with a rated input current appropriate for the maximum expected current in your application to ensure accuracy and prevent saturation.
- Environmental Considerations: Although rated IP00, protecting the CT from dust and moisture will extend its lifespan and maintain performance.
10. Warranty and Support
The YHDC SCT019 current transformer is manufactured by YHDC, a company with over 30 years of production experience in electromagnetic components and devices. The product is CE certified, indicating compliance with European safety, health, and environmental protection standards.
For warranty information, technical support, or service inquiries, please contact your point of purchase or refer to the official YHDC website. Keep your purchase receipt as proof of purchase.