1. Introduction
This manual provides detailed instructions for the Coolmay EX3U-8070H-44MT HMI/PLC all-in-one automation controller. It covers product overview, specifications, setup, operation, maintenance, troubleshooting, and user tips to ensure optimal performance and longevity of your device.
1.1 Product Overview
The Coolmay EX3U-80 series HMI/PLC all-in-one machine integrates a human-machine interface (HMI) and a programmable logic controller (PLC) into a single unit, designed for industrial automation applications. It features a military-grade 32-bit CPU with an ASIC dual processor, enabling online monitoring and fast execution speeds of basic instructions (0.24µs).
Key advantages include:
- Enhanced Security: Separate encryption for HMI and PLC to prevent unauthorized access and program reading.
- Robust Programming: Supports 30K steps PLC programs with 12K power-off retention registers, and multiple programming languages (instructions, ladder diagram, SFC).
- Versatile Communication: Compatible with Delta DVP programming port protocol, Modbus RTU, Modbus ASCII, and free port protocols, facilitating interconnection with various external devices like inverters.
- Advanced Control: Supports multiple interrupts (input, timer, communication, high-speed counter, pulse output), motion positioning (linear and circular interpolation, 4-axis linkage), and CAN bus for servo motion control.
- Specialized Functions: Includes electronic cam, weighing, and G-code functionalities.
- Flexible I/O: Equipped with 3.81 pitch pluggable terminals for easy wiring.

2. Specifications
The EX3U-8070H-44MT model offers the following technical specifications:

| Category | Specification |
|---|---|
| Model | EX3U-8070H-44MT |
| Dimensions | 200*146*36mm |
| Cutout Size | 192*138mm |
| Weight | 0.8 kg |
| Input Voltage | 24VDC |
| Power Consumption | 6-7W |
| HMI Features | |
| Screen Type | 7" TFT, 60K colors resistive touch screen |
| Display Size | 154*87mm |
| Resolution | 800*480 pixels |
| RAM | 256MB |
| ROM | NAND Flash 256MB |
| CPU | Dual core 1GHz |
| Operating System | Linux-based |
| HMI COM Ports | Type-C (download), RS232 |
| PLC Features | |
| I/O Level | Input: Passive NPN, common terminal isolated Transistor Output: Low level NPN, COM connected to negative Relay Output: Normally open dry contact |
| DO Type and Load | MT: 2A/point, 4A/4 point COM, 5A/12 point COM MR: 2A/point, 5A/12 point COM |
| High-Speed Counting | Single phase 8 channel 100KHz and 3 AB 100KHz |
| High-Speed Pulse Output | 8 channels, Y0-Y5 is 200KHz, Y6-Y7 is 100KHz |
| PLC COM Ports | 1x TYPE-C, 1x RS232, 1x RS485 |
| Analog Input Types | 0-10V, 0-20mA, 4-20mA, Thermocouple (E, K, S, T, J), PT100/PT1000, NTC10K/50K/100K |
| Analog Output Types | 0-10V, 0-20mA, 4-20mA |
| Programming Software | GX Developer 8.86Q, GX Works2 |
3. Setup
3.1 Physical Installation and Connections
The EX3U-8070H-44MT is designed for snap-on installation. Ensure adequate space for ventilation and access to all ports.
3.1.1 Interface and Indicator Lights
- POWER: Green light indicates power is connected.
- RUN: Green light indicates PLC is running.
- COM: Green light indicates HMI and PLC are communicating.
- Power Terminal: Connect DC24V switching power supply to DC24V and 0V terminals.
- PLC Programming Port: Use MiniB USB or Type-C/RS232 for PLC program download.
- Touch Screen Programming Port: Dedicated port for HMI configuration download.
- USB Interface: For direct connection of a USB flash drive (FAT32 file system).
- SD Card: For storing historical records.
- Network Port: Supports program download and Modbus TCP/IP protocol (PLC and HMI network ports cannot coexist).
- Wireless Network Card: Supports optional WiFi or 4G, occupying the touch screen's USB download port.

3.2 Software Installation
The touch screen software (Vcool) is compatible with XP/WIN7/WIN8/WIN10 systems. If installation issues occur, try reinstalling the system or running with higher user permissions.
- Install Vcool Software: Double-click the Vcool executable and follow the prompts. A device driver installation wizard will appear.
- Install USB Driver: Click 'Next' in the Device Driver Installation Wizard to install the USB driver. A confirmation message will appear upon successful installation.

3.3 Project Creation and Download
- Create New Project: Open Vcool, select 'Create new touch screen program', enter a project name, and select the appropriate model (e.g., TK8070H for EX3U-8070H-44MT).
- Configure Communication: Set the communication protocol (e.g., 'Delta DVP Series' device protocol, COM1/9600/7/E/1).
- Download Configuration:
- USB Download: Connect the HMI to your computer via USB.
- Serial Port Download: Connect via RS232 or RS485.
- Ethernet Download: Connect to the network and specify the IP address.
- Import G-code Files (Optional):
- Copy G-code files to the root directory of a USB drive.
- Insert the USB drive into the HMI.
- On the HMI, navigate to 'System Parameter Settings' -> 'CNC Program Import', select the file, and click 'Import'. Restart HMI after import.

4. Operating Instructions
4.1 PLC Programming
The PLC is compatible with Vtool PRO programming software. The 'Model Settings' window allows you to configure program title, PLC model, program capacity, and file name.

You can program in either ladder diagram mode or instruction mode. Ladder diagram programming must be compiled and converted into instruction code or SFC diagram.
4.2 Analog Input/Output
The device supports various analog input types (voltage, current, temperature sensors) and analog output types. Register values correspond directly to analog quantities.
- Analog Input: Read register values from D[1110]~D[1113] for corresponding type settings. Sampling cycles can be adjusted via D1377.
- Analog Output: Set values from 0-4000. Use TO instructions or direct register assignment (D8050~D8057). For current output (4-20mA), set D8058.0~D8058.7=1.
4.3 Weighing Function
The EX3U-8070H/HD supports 2 or 4 weighing functions, utilizing high-precision 24-bit AD conversion. Special registers (R23700-R23707) store weighing values, and R23605-R23608 manage filtering cycles. Calibration is performed via R23985-R23988.

4.4 PID Control
The PID instruction executes proportional, integral, and differential control. It is widely used in mechanical, pneumatic, and electronic equipment.
- Instruction Format: PID S1 S2 S3 D (S1: target value, S2: measured value, S3: parameters, D: output value).
- Parameters: Configure sampling time (S3), proportional gain (S3+1), integral gain (S3+2), differential gain (S3+3), and control mode (S3+4).
4.5 High-Speed Counter and Pulse Output
The PLC supports hardware and software high-speed counters. High-speed pulse output is available on 8 channels (Y0-Y5 at 200KHz, Y6-Y7 at 100KHz).
- High-Speed Counter: Use C232-C255 for single-phase or dual-phase counting.
- High-Speed Pulse Output: Supports variable speed with initial/final speed of 0.
- PWM (Pulse Width Modulation): Use the PWM instruction to specify pulse output cycle and ON time.
- Handwheel Pulse Function: Controls motor rotation based on handwheel input.
4.6 Communication Ports
The PLC features built-in RS232, optional RS485, and CAN ports. It supports MODBUS RTU master/slave communication and network communication.
- MODBUS: Use MODRD (read), MODWR (write), and MODRW (read/write) instructions.
- Network Communication: Automatically detects network status. Supports ETHRW instruction for reading/writing data on Ethernet modules.
5. Maintenance
5.1 General Care
- Keep the device clean and free from dust and debris.
- Regularly check all wiring connections for tightness and integrity.
- Ensure proper ventilation to prevent overheating.
5.2 Software and Firmware Updates
It is recommended to keep your Vcool software and HMI/PLC firmware updated to the latest versions. Updates can be obtained from the official Coolmay website or by contacting customer service.
- Upload Configuration: Use the 'Upload' function in Vcool to retrieve project files, data sampling, or event records from the HMI.
- USB Download Steps: Projects can be updated via a USB flash drive by exporting the project to the USB disk and then using the 'Project Update' section in the HMI's 'Touch Screen Parameter Settings'.

6. Troubleshooting
6.1 Common Issues and Solutions
- Software Installation Failure: If Vcool software fails to install or run, try replacing the computer, reinstalling the operating system, or running the installer with administrator privileges.
- G-code File Not Recognized: Ensure G-code files are placed in the root directory of the USB drive. The USB disk and HMI USB interface cannot be used simultaneously.
- Configuration Download Failure: If a download fails, reopen the host computer software and reconfigure before attempting to download again.
- Abnormal Chasing/Flying Shearing Actions: This may be caused by inequalities in the program. Review and correct the program logic.
- PID Control Issues:
- Ensure PID parameters are within the specified range.
- Verify the measured value (PV) is stable before PID calculations.
- If the scan cycle affects the timer, adjust the scan cycle or use time interrupt subroutines.
- Handwheel Function Abnormalities: If changing the axis (D1816) while M1743 is closed and C232 has a value, the replaced axis will immediately run to the C232 value, posing a safety risk. Always clear C232 when changing axes.
- PWM Output Errors: Check S1/S2 values, command input, and ensure S1 is not greater than S2. Parameter error OxEE7 indicates an issue.
- Ethernet Communication Timeout: If no data is received within 30 seconds, the Ethernet port will automatically close. Reconnect the port.

7. User Tips
- Wiring Convenience: The 3.81 pitch pluggable terminals make wiring easy and efficient.
- Debugging Control Methods: When debugging, pay close attention to whether the control method is internal axis or external axis, as different methods require different programming approaches.
- Safe Handwheel Operation: Avoid directly clearing pulse display values (D1336, D1338) as this can cause the follower axis to return to an incorrect position, potentially leading to safety hazards. Always follow the recommended steps for clearing these values.
8. Warranty and Support
For detailed hardware information, advanced programming guides, and specific touch screen software usage, please refer to the official Coolmay documentation:
- Coolmay EX3U-80 Series Touch Screen PLC All-in-One User Manual (PDF)
- Coolmay L01 Series PLC Programming Manual
- Coolmay TK80 Series Touch Screen User Manual
For technical support or further assistance, please contact Coolmay customer service.