SRNE ASP48100S200-H

Contents

SRNE 10KW Hybrid Solar Inverter User Manual

Model: ASP48100S200-H

Brand: SRNE

1. Introduction

The SRNE ASP series solar energy storage inverter is an all-in-one control inverter that integrates solar energy storage, utility charging, energy storage, and AC sine wave output. It utilizes DSP control for high response speed, reliability, and industrial standard performance through an advanced control algorithm.

This manual provides important information, guidelines, operation, and maintenance for the SPI-10K-SP, SPI-8K-SP, and SPI-12K-SP models. Please follow these instructions during installation, use, and maintenance.

SRNE ASP Series Solar Storage Inverter features
Overview of SRNE ASP Series Solar Storage Inverter features.
Energy flow diagram showing solar generation, battery charging, energy consumption, and battery discharging over time.
Energy flow diagram illustrating solar generation, battery charging, energy consumption, and battery discharging over time.

2. Safety Instructions

This chapter contains important safety instructions. Please read and keep this manual for future reference.

  • Always comply with local requirements and regulations for inverter installation.
  • Beware of high voltage. Turn off the switch of each power source before and during installation to avoid electric shock.
  • For optimum operation, follow required specifications to select appropriate cable size and necessary protective devices.
  • Do not connect or disconnect any connections while the inverter is operating.
  • Do not open the terminal cover when the inverter is working.
  • Ensure the inverter is properly grounded.
  • Never short-circuit AC output and DC input.
  • Do not disassemble this unit. For all repair and maintenance, take it to a professional service center.
  • Never charge a frozen battery.

2.1 Safety Symbols

SymbolDescription
DANGERIndicates hazardous situations which if not avoided will result in death or serious injury.
WARNINGIndicates hazardous situations which if not avoided could result in death or serious injury.
CAUTIONIndicates hazardous situations which if not avoided could result in minor or moderate injury.
NOTICEProvides tips on product operation.

3. Product Overview

The SRNE ASP series inverter is designed for solar energy storage systems. Key features include:

  • Supports lead-acid and Li-ion battery connections.
  • Dual activation function for dormant Li-ion batteries (mains or PV).
  • Supports single-phase parallel and parallel three-phase pure sine wave output.
  • Compatible with 200, 208, 220, 230, and 240Vac voltage levels.
  • Two solar inputs with simultaneous tracking of two solar maximum power charging/carrying capacity functions.
  • Dual MPPT with 99.9% efficiency and maximum 22A current per circuit, suitable for high-power modules.
  • Four charging modes: solar only, mains priority, solar priority, and mixed mains/PV charging.
  • Time-slot charging and discharging settings for off-grid and hybrid grid-connected modes.
  • Stand-alone energy-saving mode to reduce no-load energy losses.
  • Two output modes: utility bypass and inverter output with uninterrupted power supply.
  • LCD large screen dynamic flow diagram for easy system data and status monitoring.
  • 360° protection: short circuit, over current, over/under voltage, overload, etc.
  • Supports CAN, USB, and RS485 communication.
  • N grounding option.

3.1 System Connection Diagram

A complete system consists of PV modules, utility grid/generator, battery, home load, and the inverter. The actual application scenario determines the specific wiring method.

System connection diagram showing PV panel, generator/utility, external battery packs, inverter, and home appliances.
Typical system connection diagram for the SRNE Hybrid Solar Inverter.

3.2 Production Overview (Components)

Diagram showing the front and bottom view of the inverter with numbered components.
Front and bottom view of the inverter with labeled components.
No.ComponentNo.ComponentNo.Component
1LCD screen2LED indicator3Physical button
4ON/OFF rocker switch5PV input (1/1)6Battery (+)
7Battery (-)8Dry contact9RS485/CAN port
10RS48-1 port11USB-B port12Grounding screw
13AC output (L+N)14AC input (L+N)15AC input circuit breaker
16Parallel communication port

4. Setup

4.1 Installation Location

The SPI series is for indoor use only (protection level: IP20). When selecting an installation location, consider the following:

  • A solid wall capable of supporting the inverter's weight.
  • Installation height: flush with the line of sight for easy access and viewing.
  • Sufficient heat dissipation space around the unit.
  • Ambient temperature: -10°C to 55°C (14°F to 131°F) for optimal operation.

WARNING:

  • Do not install the inverter near highly flammable materials.
  • Do not install the inverter in potentially explosive areas.
  • Do not install the inverter and lead-acid battery in enclosed spaces.
  • Do not install the inverter in direct sunlight.
  • Do not install or use the inverter in damp environments.

4.2 Inverter Installation

Mark 4 mounting holes on the wall according to the specified dimensions. Insert two expansion screws above and two M5 size screws below for fixing the inverter.

4.3 Removal of Terminal Cover and Insect-Proof Net

Remove the terminal cover and insect-proof net with a screwdriver for wiring or cleaning. Regularly clean the dustproof net to avoid blocking airflow, which can cause overheating.

4.4 Parallel Wiring

The inverter supports parallel operation of up to six units. When using the parallel function, ensure the parallel communication cable (packaging accessory) is connected correctly and reliably.

WARNING: Cautions for Parallel Connection

  1. PV Wiring: In parallel connection, the PV array of each inverter must be independent. The PV array of PV1 and PV2 for one inverter must also be independent.
  2. Battery Wiring: All solar storage inverters must be connected to the same battery. BAT+ to BAT+ and BAT- to BAT-. Before power on, check and ensure correct connection, wiring length, and cable size to avoid abnormal operation.
  3. AC OUT Wiring: For single-phase parallel connection, all inverters must be connected L-to-L, N-to-N, and PE-to-PE. For three-phase, N-to-N and PE-to-PE, with L lines of all inverters in the same phase connected together. Ensure correct connection, wiring length, and cable size.
  4. AC IN Wiring: All solar storage inverters must be connected L-to-L, N-to-N, and PE-to-PE. Ensure correct connection, wiring length, and cable size. Multiple different AC source inputs are not allowed.
  5. Communication Wiring: Use a DB15 standard computer cable with shielding. Connect the male connector (out) of one inverter to the female connector (in) of the parallel inverter. Tighten DB15 terminal screws to prevent disconnections.
  6. System Wiring Diagrams: Carefully refer to the system wiring diagrams to ensure all wiring is correct and reliable before power on.
  7. Adding Inverters: If adding a new inverter to an already operating system, disconnect battery input, PV input, AC input, and AC output, and ensure all solar storage inverters are powered off before reconnecting.

4.4.1 Single-Phase Parallel Connection Guide Diagram

The parallel communication line and even flow detection line of the inverse control unit need to be connected after screw locking.

Diagram showing two inverters connected in single-phase parallel mode with battery, utility grid, PV arrays, and loads.
Two all-in-one solar charger inverters connected in single-phase parallel.

4.4.2 Three-Phase Parallel Connection Guide Diagram

The parallel communication line of the inverters needs to be connected and then screwed and locked.

Diagram showing three inverters connected in three-phase parallel mode (1+1+1 system) with battery, utility grid, PV arrays, and loads.
Three all-in-one solar charger inverters connected in three-phase parallel (1+1+1 System).

4.5 Cable and Circuit Breaker Model

Refer to the table below for recommended cable sizes and circuit breaker models for PV input, AC input, battery, and AC output connections.

ConnectionModelCable SizeMax. CurrentCircuit Breaker Model
PV INPUTSPI-8K-SP5 mm²/10 AWG22 A2P-25A
SPI-10K-SP5 mm²/10 AWG22 A2P-25A
SPI-12K-SP5 mm²/10 AWG22 A2P-25A
AC INPUTSPI-8K-SP13 mm²/6 AWG (L/N)63A (L/N)2P-63A
SPI-10K-SP13 mm²/6 AWG (L/N)63A (L/N)2P-63A
SPI-12K-SP13 mm²/6 AWG (L/N)63A (L/N)2P-63A
BATTERYSPI-8K-SP34 mm²/2 AWG180 A2P-200A
SPI-10K-SP42 mm²/1 AWG200 A2P-250A
SPI-12K-SP42 mm²/1 AWG200 A2P-250A
AC OUTPUTSPI-8K-SP13 mm²/6 AWG (L/N)63A (L/N)2P-63A
SPI-10K-SP13 mm²/6 AWG (L/N)63A (L/N)2P-63A
SPI-12K-SP13 mm²/6 AWG (L/N)63A (L/N)2P-63A

NOTICE: The wire diameter is for reference only. If the distance between the PV array and the inverter or between the inverter and the battery is long, using a thicker wire will reduce voltage drop and improve system performance.

4.6 AC Input and Output Wiring

Connect the fire wire, zero wire, and ground wire according to the positions and order shown in the diagram.

Diagram showing AC IN and AC OUT terminal connections.
AC Input and Output Terminal Connections.

DANGER:

  • Before connecting AC input and output, disconnect the circuit breaker to avoid electric shock. Do not conduct live operation.
  • Ensure cables meet requirements. Too thin or poor quality cables pose serious safety hazards.

4.7 Battery Connection

Connect the positive and negative cables of the battery according to the diagram.

Diagram showing battery terminal connections (BAT- and BAT+).
Battery Terminal Connections.

DANGER:

  • Before connecting the battery, disconnect the circuit breaker to avoid electric shock. Do not conduct live operation.
  • Check positive and negative terminals for correct and no reverse connection; otherwise, it may damage the inverter.
  • Ensure cables meet requirements. Too thin or poor quality cables pose serious safety hazards.

4.8 PV Connection

Connect the positive and negative wires of the two strings of PV according to the diagram.

Diagram showing PV input terminal connections (PV1+, PV1-, PV2+, PV2-).
PV Input Terminal Connections.

DANGER:

  • Before connecting PV modules, disconnect the circuit breaker to avoid electric shock. Do not conduct live operation.
  • Ensure the open circuit voltage of series-connected PV modules does not exceed the maximum open circuit voltage of the inverter (500 V for SPI series); otherwise, the inverter may be damaged.

4.9 Dry Contact Wiring

Use a small-sized screwdriver to push back in the direction indicated by the arrow, then insert the communication cable into the dry contact port. (Communication cable section: 0.2 mm² – 1.5 mm²)

Diagram showing dry contact wiring terminals.
Dry Contact Wiring Terminals.

4.10 Grounding Connection

Ensure the grounding terminal is reliably connected to the grounding busbar.

Diagram showing the grounding terminal location.
Grounding Terminal Location.

NOTICE: The grounding cable size shall not be less than 4 mm².

4.11 Final Assembly

After ensuring reliable wiring and correct wire sequence, install the terminal protection cover in place.

4.12 Inverter Start

After confirming reliable wiring and correct wiring sequence, restore the terminal cover to its original position.

  1. Step 1: Close the circuit breaker of the battery.
  2. Step 2: Press the rocker switch at the bottom of the inverter. The screen and indicator will light up, indicating the inverter is enabled.
  3. Step 3: Close the circuit breakers for PV input, AC input, and AC output in sequence.
  4. Step 4: Start loads one by one in order of power from small to large.

5. Operating

5.1 Operation and Display Panel

The inverter's operation and display panel includes an LCD screen, three indicators, and four physical buttons.

Front view of the inverter showing the LCD screen and control buttons.
Inverter front panel with LCD and control buttons.

5.1.1 Physical Buttons

ButtonDescription
SETEnter/Exit the setup menu
UPGo to the next option
DOWNGo to the previous option
ENTERConfirm/Enter the option in setup menu

5.1.2 LED Indicators

IndicatorColorDescription
AC/INVYellowNormally ON: mains bypass output
Flash: inverter output
CHARGEGreenNormally ON: charging completed
Flash: charging
FAULTRedNormally ON: level-1 fault
Flash: level-2 fault
OFF: level-3 or level-4 fault

5.1.3 Display Screen Icons

The LCD screen displays various icons representing system status, power flow, and settings. Refer to the manual for a complete list of icons and their meanings.

5.2 Settings

The inverter offers a comprehensive setup menu to configure various parameters. Access the setup menu using the physical buttons.

NOTICE: Users can change the output voltage via the setup menu. Output voltage corresponds to parameter 38, which can be set from 200V to 240V.

5.2.1 AC Output Mode

The AC output mode corresponds to parameter setting item 01 and 34, allowing the user to manually set the AC output power source.

  • Utility Priority Output (UTI): Utility is first priority. Utility and solar provide power to load simultaneously when solar is available. Battery provides power only when utility power is not available. (Priority: utility > solar > battery)
  • Solar and Utility Hybrid Output (default): In UTI mode, when not connected to the battery or when the battery is full, solar and utility supply power to the load simultaneously. (Priority: solar > utility > battery)
  • Solar Priority Output (SOL): Solar provides power to loads as first priority. If solar is not available, the utility grid provides power. This mode maximizes solar energy use while maintaining battery power and is suitable for areas with stable power grids. (Priority: solar > utility > battery)
  • Inverter Priority Output (SBU): Solar provides power to loads as first priority. If solar is insufficient or unavailable, the battery is used as a supplement. When battery voltage reaches parameter 04 (Voltage point of battery switch to utility), it switches to utility. This mode maximizes DC energy use in areas with stable grids. (Priority: solar > battery > utility)

5.2.2 Battery Charging Mode

The charging mode corresponds to parameter setting item 06, allowing manual selection.

  • Hybrid Charging (SNU - default): Solar and utility charge the battery simultaneously, with solar as first priority. Utility supplements when solar is insufficient. This is the fastest charging method, suitable for areas with low power supply. (Source priority: solar > utility)
  • Only Solar Charging (OSO): Solar charging only, no mains charging activated. This is the most energy-efficient method, with all battery power from solar, typically used in areas with good radiation conditions.

5.2.3 Timed Charge/Discharge Function

The SPI series features a time-slot charging and discharging function, allowing users to set periods based on local peak and valley tariffs to optimize utility and PV energy use.

Graph showing Peak-Valley Electricity Tariff and energy usage over 24 hours.
Peak-Valley Electricity Tariff and energy usage over 24 hours.

The time-slot charging/discharging function can be enabled/disabled via setup menu parameters 46 and 53. Charging and discharging slots are set in parameters 40-45 and 47-52.

  • Timed Charge and Loading Function: With 3 definable periods, users can set the mains charge/loading period (00:00-23:59). During this period, PV energy is used first; if insufficient, mains supplement.
  • Timed Battery Discharge Function: With 3 definable periods, users can set the battery discharge period (00:00-23:59). During this period, the inverter first uses battery power; if battery power is insufficient, it automatically switches to mains.

5.2.4 Battery Parameters

The inverter supports various battery types, including Lead-acid and Li-ion. Parameters can be configured for each type.

Lead-acid Battery Parameters
Parameter/Battery TypeSealed Lead-acid Battery (SLD)Gel Lead-acid Battery (GEL)Flooded Lead-acid Battery (FLD)User-defined Battery (USE)
Overvoltage disconnect voltage60 V60 V60 V60 V
Equalizing charge voltage58 V56.8 V58 V40 V–60 V (settable)
Boost charge voltage57.6 V56.8 V57.6 V40 V–60 V (settable)
Floating charge voltage55.2 V55.2 V55.2 V40 V–60 V (settable)
Under-voltage alarm voltage44 V44 V44 V40 V–60 V (settable)
Under-voltage disconnect voltage42 V42 V42 V40 V–60 V (settable)
Discharge limit voltage40 V40 V40 V40 V–60 V (settable)
Over-discharge delay time5s5s5s1s–30s (settable)
Equalizing charge duration120 min-120 min0 min–600 min (settable)
Equalizing charge cycle30 d-30 d0 d–250 d (settable)
Boost charge cycle120 min120 min120 min10 min–600 min (settable)
Li-ion Battery Parameters
Parameter/Battery TypeTernary Li-ion Battery (N13/N14)LFP Battery (L16/L15/L14)User-defined Battery (USE)
Overvoltage disconnect voltage60 V60 V60 V
Equalizing charge voltage--40 V–60 V (settable)
Boost charge voltage53.2 V / 57.6 V56.8 V / 53.2 V / 49.2 V40 V–60 V (settable)
Floating charge voltage53.2 V / 57.6 V56.8 V / 53.2 V / 49.2 V40 V–60 V (settable)
Under-voltage alarm voltage43.6 V / 46.8 V49.6 V / 46.4 V / 43.2 V40 V–60 V (settable)
Under-voltage disconnect voltage38.8 V / 42 V48.8 V / 45.6 V / 42 V40 V–60 V (settable)
Discharge limit voltage36.4 V / 39.2 V46.4 V / 43.6 V / 40.8 V40 V–60 V (settable)
Over-discharge delay time30s30s1s–30s (settable)
Equalizing charge duration--0 min–600 min (settable)
Equalizing charge cycle--0 d–250 d (settable)
Boost charge cycle120 min (settable)120 min (settable)10 min–600 min (settable)

NOTICE: If no BMS is connected, the inverter will charge according to the battery voltage with a preset charging curve. When the inverter communicates with the BMS, it will follow the BMS instructions to perform a more complex stage charging process.

6. Communication

6.1 Overview

The inverter provides several communication ports for monitoring and control.

6.2 USB-B Port

The USB-B port allows users to read and modify device parameters using host software. Contact the manufacturer for the host software installation package if needed.

Diagram showing USB-B port connection to a computer.
USB-B Port Connection.

6.3 RS485-1 Port

The RS485-1 port connects to a Wi-Fi/GPRS data acquisition module, enabling users to view the inverter's operating status and parameters via a mobile phone app.

Diagram showing RS485-1 port connection to a Wi-Fi/GPRS module and mobile phone.
RS485-1 Port Connection.

6.4 RS485/CAN Port

The RS485/CAN port is used to connect to the BMS (Battery Management System) of Li-ion batteries.

NOTICE: If the inverter needs to communicate with a lithium battery BMS, contact the manufacturer for the communication protocol or to upgrade the inverter to the corresponding software program.

6.5 Dry Contact

The dry contact port has four functions: remote switch on/off, switching signal output, battery temperature sampling, and generator remote start/stop.

FunctionDescription
Remote ON/OFF (Reserve)When pin 1 is connected to pin 2, the inverter will turn off the AC output. When disconnected, the inverter is in normal output.
ON/OFF signal output (Reserve)When battery voltage reaches discharge limit voltage (parameter 15), voltage between pin 3 and pin 1 is 0 V. In normal charge/discharge, voltage between pin 3 and pin 1 is 5 V.
Temperature sampling (reserved)Pins 1 and 4 can be used for battery temperature sampling compensation.
Remote generator start/stopWhen battery voltage reaches under-voltage alarm voltage (parameter 14) or mains switch threshold (parameter 04), pins 6 to 5 are normally open, and pins 7 to 5 are normally closed. When battery voltage reaches mains switch threshold (parameter 05) or battery is fully charged, pins 6 to 5 are normally closed, and pins 7 to 5 are normally open. (5/6/7 pin output: 125 VAC/1 A, 230 VAC/1 A, and 30 VDC/1 A)

NOTICE: If you need to use the remote start/stop function of the generator with dry contact, ensure that the generator has ATS and supports remote start/stop.

7. Maintenance

To maintain optimum and long-lasting working performance, it is recommended to check the following items twice a year:

  1. Ensure that the airflow around the inverter is not blocked and remove any dirt or debris from the radiator.
  2. Check that all exposed conductors are not damaged by sunlight, friction, dry rot, insect, or rodent damage. Repair or replace conductors if necessary.
  3. Verify that indications and displays are consistent with equipment operation. Note any faults or incorrect displays and take corrective action.
  4. Check all terminals for signs of corrosion, insulation damage, high temperatures, or burning/discoloration, and tighten terminal screws.
  5. Check for dirt, nesting insects, and corrosion. Clean anti-insect nets as required.
  6. If the lightning arrester has failed, replace it promptly to prevent lightning damage to the inverter or other equipment.

DANGER: Make sure that the inverter is disconnected from all power sources and that the capacitors are fully discharged before carrying out any checks or operations to avoid the risk of electric shock.

The company is not liable for damage caused by:

  • Improper use or use in a wrong location.
  • Photovoltaic modules with an open circuit voltage exceeding the maximum permissible voltage.
  • Operating temperature exceeding the restricted operating temperature range.
  • Dismantling and repair of the inverter by unauthorized persons.
  • Force majeure: damage during transport or handling of the inverter.

8. Troubleshooting

8.1 Fault Codes

The inverter displays fault codes to indicate specific issues. Refer to the table below for fault codes, their meanings, and whether they affect output.

Fault CodeMeaningAffect Output or NotDescription
01BatVoltLowYesBattery under-voltage alarm
02BatOverCurrSwYesOvercurrent software protection for average battery discharge current
03BatOpenYesDisconnected battery alarm
04BatLowEodYesUnder-voltage battery discharge stop alarm
05BatOverCurrHwYesBattery overcurrent hardware protection
06BatOverVoltYesCharge overvoltage protection
07BusOverVoltHwYesBus overvoltage hardware protection
08BusOverVoltSwYesBus overvoltage software protection
09PvVoltHighYesPV overvoltage protection
10PvBoostOCSwNoBoost overcurrent software protection
11PvBoostOCHwNoBoost overcurrent hardware protection
12SpiCommErrYesSPI communication fault of master and slave chips
13OverloadBypassYesBypass overload protection
14OverloadInverterYesInverter overload protection
15AcOverCurrHwYesInverter overcurrent hardware protection
16AuxDSpReqOffPWMYesSlave chip OFF request fault
17InvShortYesInverter short-circuit protection
18BussoftfailedYesBus soft-start failure
19OverTemperMpptNoPV heat sink over-temperature protection
20OverTemperInvYesInverter heat sink over-temperature protection
21FanFailYesFan fault
22EEPROMYesMemory fault
23ModelNumErrYesModel setting error
24BusdiffYesPositive and negative bus voltage imbalance
25BusShortYesBus short-circuit
26RlyshortYesInverter AC output backward to bypass AC output
28LinePhaseErrYesMains input phase error
29BusVoltLowYesBus low-voltage protection
30BatCapacityLow1YesAlarm of battery capacity rate below 10% (taking effect after BMS communication is successful)
31BatCapacityLow2NoAlarm of battery capacity rate below 5% (taking effect after BMS communication is successful)
32BatCapacityLowStopYesBattery low-capacity OFF (taking effect after BMS communication is successful)
33CtrlCanCommErrYesParallel control can communication fault
34CanCommFaultYesParallel can communication fault
35ParaAddrErrYesParallel ID (communication address) setting error
37ParaShareCurrErrYesParallel current sharing fault
38ParaBattVoltDiffYesLarge battery voltage difference in parallel mode
39ParaAcSrcDiffYesInconsistent mains input source in parallel mode
40ParaHwSynErrYesHardware synchronization signal error in parallel mode
41InvDcVoltErrYesInverter DC voltage error
42SysFwVersionDiffYesInconsistent system firmware version in parallel mode
43ParaLineContErrYesParallel connection fault
44SerialnumbererrorYesFailure to set the serial number before leaving factory
45Errorsettingofsplit-phasemodeYesSetting error of setting items in parallel mode
58BMSComErrNoBMS communication fault
60BMSUnderTemNoBMS under-temperature alarm (taking effect after BMS communication is successful)
61BMSOverTemNoBMS over-temperature alarm (taking effect after BMS communication is successful)
62BMSOverCurNoBMS overcurrent alarm (taking effect after BMS communication is successful)
63BMSUnderVoltNoBMS under-voltage alarm (taking effect after BMS communication is successful)
64BMSOverVoltNoBMS overvoltage alarm (taking effect after BMS communication is successful)

8.2 Troubleshooting Table

If you encounter a fault, refer to the table below for possible causes and solutions.

Fault CodeMeaningCauseSolution
/No screen displayNo power input, or device switch is offCheck battery/PV air-switch, ensure switch is ON; press any button to exit sleep mode.
01Battery under-voltageBattery voltage lower than parameter [14]Charge battery until voltage exceeds parameter [14].
03Disconnected batteryBattery not connected, or BMS in discharge protectionCheck battery connection, circuit breaker, and BMS communication.
04Battery over-dischargeBattery voltage lower than parameter 12Manual reset: Turn off power, restart. Auto reset: Charge battery until voltage is higher than parameter [35].
06Rechargeable battery overvoltage protectionBattery in overvoltage stateManually turn off power, restart. Discharge battery until voltage is below recovery threshold.
13Bypass overload (software detection)Bypass output power/current overloadedReduce load power, restart device. Refer to item 11 in Protection Function.
14Inverter overload (software detection)Inverter output power/current overloadedReduce load power, restart device. Refer to item 11 in Protection Function.
19Over-high temperature of PV input heat sinkPV input heat sink temperature exceeds 90°C for 3sWait until temperature is below over-temperature recovery, then charge and discharge return to normal.
20Over-high temperature of inverter output heat sinkInverter output heat sink temperature exceeds 90°C for 3sWait until temperature is below over-temperature recovery, then charge and discharge return to normal.
21Fan faultSoftware detects fan faultShut down, manually flick fan, check for foreign objects.
26AC input relay short-circuitStuck relay for AC outputManually shut down, restart. If fault recurs, contact service personnel.
28Mains input phase faultAC input phase inconsistent with AC output phaseEnsure AC input phase is same as AC output phase.

NOTICE: If you encounter a fault that cannot be solved by the methods in the table above, please contact our after-sales service for technical support and do not disassemble the equipment yourself.

9. Specifications

Detailed technical specifications for the SRNE ASP series hybrid solar inverter.

CategoryParameterSPI-8K-SPSPI-10K-SPSPI-12K-SPSettable
INVERTER OUTPUT
Rated Output Power8000W10000W12000W
Max. Peak Power16000W20000W24000W
Rated Output Voltage230Vac (Single phase)Y
Load Capacity of Motors5HP6HP6HP
Rated AC Frequency50/60HzY
WaveformPure Sine Wave
Switch Time10ms (typical)
Parallel capacity1-6 Units
OverloadAfter triggering the overload protection the inverter will resume output after 3 minutes, 5 consecutive overloads will switch off the output until the inverter is restarted. (102%<load<110%) ±10%: error and output shutdown after 5mins; (110% < load < 125%) ±10%: error and output shutdown after 10s. Load > 125% ±10%: error reported and output switched off after 5s.
BATTERY
Battery TypeLi-ion / Lead-Acid / User DefinedY
Rated Battery Voltage48Vdc
Voltage Range40-60VdcY
Max. Grid/Generator Charging Current150AY
Max.Hybrid Charging Current180A200A200AY
PV INPUT
Num. of MPPT Trackers2
Max.PV array power5500W+5500W (SPI-8K-SP), 6600W+6600W (SPI-10K-SP, SPI-12K-SP)
Max. Input current22A+22A
Max. Voltage of Open Circuit500Vdc/500Vdc
MPPT Voltage Range125-425Vdc/125-425Vdc
GRID / GENERATOR INPUT
Input Voltage Range90-275Vac
Frequency Range50/60Hz
Bypass Overload Current63A
EFFICIENCY
MPPT Tracking Efficiency99.9%
Max. Battery Inverter Efficiency92%
GENERAL
Dimensions620x435x130mm
Weight27kg
Protection DegreeIP20, Indoor Only
Operating Temperature Range-10~55°C, >45°C derated
Noise<60dB
Cooling MethodInternal Fan
COMMUNICATION
Embedded InterfacesRS485 / CAN / USB / Dry contactY
External Modules (Optional)Wi-Fi / GPRSY
CERTIFICATION
SafetyIEC62109-1, IEC62109-2
EMCEN61000-6-1, EN61000-6-3
RoHSYes

10. Warranty and Support

The SRNE Hybrid Solar Inverter comes with a 2-year warranty. For any technical support or issues not covered in the troubleshooting section, please contact the seller or an authorized service center. Do not attempt to disassemble or repair the unit yourself.

For further details, you may refer to the official user manual PDF: SRNE All-in-one Solar Charge Inverter User Manual (PDF).

11. User Tips

  • Flexible Operation: The inverter can operate effectively even without batteries, sharing the load directly with solar panels. This can make a significant difference in energy usage.
  • Voltage Compatibility: While the inverter is rated for 230Vac output, the settings menu allows adjustment between 200V and 240V, offering flexibility for different regional requirements.
  • Battery Capacity: Ensure the battery capacity of your system is correctly matched to your load requirements and application scenarios to avoid insufficient power or wasted generation. Consult the manual or customer service for recommendations.