1. Introduction

The MASTECH MS5902 is a versatile electrical testing device designed to simplify the identification of circuit breakers and fuses, as well as to test the wiring condition of electrical sockets. This manual provides detailed instructions for the safe and effective use of your MS5902 device.

MASTECH MS5902 Circuit Breaker Finder and Socket Tester

Figure 1: MASTECH MS5902 Circuit Breaker Finder and Socket Tester (Receiver and Transmitter)

2. Safety Information

  • Warning: Exercise extreme caution when using the MS5902 in large circuit breaker panels.
  • Do not use the device when the voltage exceeds 120V/230V AC.
  • Always ensure the power is OFF at the fixture before installing the transmitter if using a socket adapter.
  • This device is intended for use by qualified personnel or under the supervision of a professional.
  • Keep the device clean and dry.

3. Key Features

  • Automatic and quick identification of correct circuit breakers or fuses.
  • Rapid and easy identification of circuit socket conditions.
  • Integrated flashlight function for use in dark environments.
  • Audible (buzzers) and visual (lights) indicators.
  • Battery low voltage alarm.
  • Suitable for renovation, installation, and acceptance of power grids in residential, office, and industrial settings.

4. Specifications

Parameter Value
Model Number MS5902
Type Circuit Breaker Finder, Socket Tester
Material Plastic
Color Green/Black
Dimensions (L*W*H) Approx. 198x40x50mm
Plug Type (Transmitter) EU (230V/50Hz), US (125V/60Hz)
Operating Voltage AC220V/50HZ (EU), AC110V/60HZ (US)
Operating Temperature 0 ~ 50℃
Security Rating IEC1010-1 CATII 600V
Battery (Receiver) 9V Battery (not included)
Customization Yes
High-concerned chemical None
Labeled diagram of MS5902 receiver and transmitter components

Figure 2: Labeled components of the MS5902 Receiver and Transmitter

5. Package Contents

The package typically includes:

  • 1 x MS5902-R Receiver (Circuit Breaker Finder)
  • 1 x MS5902-T Transmitter (Socket Tester)

Note: A 9V battery for the receiver is NOT included and must be purchased separately.

Package contents showing receiver, transmitter, and carrying pouch

Figure 3: Typical package contents

6. Setup

6.1 Battery Installation (MS5902-R Receiver)

The MS5902-R Receiver requires a 9V battery (not included) for operation. When the yellow LED on the MS5902-R illuminates, it indicates a low battery and requires replacement.

  1. Locate the battery compartment on the back of the MS5902-R Receiver.
  2. Unscrew and remove the battery compartment cover.
  3. Insert a new 9V battery, ensuring correct polarity.
  4. Replace the cover and screw it securely.

7. Operating Instructions

7.1 Locating a Circuit Breaker or Fuse

  1. Ensure the pillar on the MS5902-T Transmitter is set to the left position (Breaker Find mode).
  2. Plug the MS5902-T Transmitter into the receptacle (socket) you wish to test.
    • If testing a candescent light fixture, install a socket adapter (purchased separately) first. Ensure the light fixture's switch is OFF before installing the adapter. Then plug the MS5902-T into the adapter and turn the switch ON.
  3. Go to the main circuit breaker panel box.
  4. Turn on the MS5902-R Receiver. The red LED will illuminate.
  5. Place the tip (chapiter) of the MS5902-R directly onto each circuit breaker or fuse.
  6. Slide the tip of the MS5902-R down each breaker along both sides of the panel. The MS5902-R will beep frequently, indicating relative signal strength.
  7. Repeat the process. On the third pass, the MS5902-R will emit a distinct beep, the red LED will turn off, and the green LED will light up ONLY when positioned over the circuit breaker powering the MS5902-T Transmitter.
  8. To confirm, push the identified breaker to the OFF position and check that the LED on the MS5902-T Transmitter in the outlet turns off. This confirms you have found the correct breaker or fuse.
MS5902 Circuit Breaker Finder in use with an EU socket

Figure 4: Using the MS5902 to locate a circuit breaker (EU version shown)

MS5902 Circuit Breaker Finder in use with a US socket

Figure 5: Using the MS5902 to locate a circuit breaker (US version shown)

7.2 Testing a Socket

The MS5902-T Transmitter also functions as a socket tester to check for correct wiring.

  1. Ensure the pillar on the MS5902-T Transmitter is set to the right position (Socket Test mode).
  2. Plug the MS5902-T Transmitter into the socket you wish to test.
  3. Observe the indicator lights on the MS5902-T. Refer to the nameplate on the transmitter for the meaning of different light patterns (e.g., CORRECT, MISSING EARTH, LIVE EARTH REVERSE, LIVE NEUTRAL REVERSE, MISSING NEUTRAL).
MS5902 Transmitter (Socket Tester) with indicator legend

Figure 6: MS5902 Transmitter in Socket Test mode (EU version shown)

MS5902 Transmitter (Socket Tester) with US plug and indicator legend

Figure 7: MS5902 Transmitter in Socket Test mode (US version shown)

7.3 Flashlight Function

The MS5902-R Receiver includes a built-in flashlight to assist in dimly lit areas, such as inside breaker panels.

  • Press the dedicated light switch button on the receiver to turn the flashlight ON or OFF.
Close-up of MS5902 receiver with flashlight illuminated

Figure 8: Flashlight feature of the MS5902 Receiver

8. Maintenance

  • Keep the device clean by wiping it with a dry cloth.
  • Do not use abrasive cleaners or solvents.
  • Store the device in a cool, dry place away from direct sunlight and extreme temperatures.

9. Troubleshooting

Problem Possible Cause Solution
Receiver (MS5902-R) not turning on or weak signal. Low or dead 9V battery. Replace the 9V battery in the receiver. The yellow LED indicates low battery.
Transmitter (MS5902-T) indicators not lighting up. No power to the socket, incorrect voltage, or faulty socket. Check if the socket is live. Ensure the voltage is within the device's operating range (120V/230V AC). Consult a qualified electrician if the socket is suspected to be faulty.
Difficulty locating the correct breaker. Interference from other circuits, or not following the scanning procedure correctly. Ensure you perform multiple passes over the breakers as instructed. Minimize other electrical activity during testing.

10. User Tips

  • Remember that the 9V battery for the receiver is not included in the package. Have one ready before you start using the device.
  • For best results when locating a breaker, ensure the circuit you are testing is the only one drawing significant power from that panel.
  • The flashlight is very useful in dark breaker boxes; don't forget to use it!

11. Warranty and Support

For warranty information, technical support, or service inquiries, please contact your retailer or the manufacturer directly. Keep your purchase receipt as proof of purchase.


Documents and downloads

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.

After a successful submission, we securely hash the supplied account or form email before sending it to Microsoft Advertising for conversion attribution. Privacy details.