SmartGen HGM6120N

Contents

SmartGen HGM6120N AMF Generator Auto Start Stop Controller User Manual

Model: HGM6120N

Introduction

The SmartGen HGM6120N is an Automatic Mains Failure (AMF) generator controller designed for single unit automation and monitoring. It integrates digital, intelligent, and network techniques, providing functions such as automatic start/stop, data measurement, alarm protection, and three remote functions (remote control, remote measurement, and remote communication). This controller is suitable for various types of diesel genset applications.

Safety Information

  • Always disconnect power before installation or maintenance.
  • Ensure all wiring is performed by qualified personnel and complies with local electrical codes.
  • Do not operate the controller if it is damaged or malfunctioning.
  • Keep the controller dry and away from extreme temperatures.

Setup and Installation

1. Physical Installation

Mount the HGM6120N controller in a secure, vibration-free location, typically within the generator control panel. Ensure adequate ventilation and protection from environmental elements.

Front view of SmartGen HGM6120N controller with LCD display and control buttons.
Front view of the HGM6120N controller.

2. Wiring Connections

Refer to the wiring diagram below for proper connection of power, sensors, and control signals. All connections should be secure and properly insulated.

Detailed wiring diagram for the SmartGen HGM6120N controller, showing terminals for emergency stop, fuel, crank, auxiliary outputs, magnetic pickup, temperature, oil pressure, fuel level, auxiliary inputs, current, CAN bus, RS485, mains voltage, gens voltage, USB, and Ethernet ports.
Back view and wiring diagram of the HGM6120N controller.

Terminal Connections:

Terminal No. Function Notes
1Emergency Stop (TOP)Connect to emergency stop circuit.
2Fuel Output16A rated.
3Crank Output16A rated.
4Auxiliary Output 17A/250VAC rated.
5Auxiliary Output 27A/250VAC rated.
6Auxiliary Output 316A/250VAC rated.
7Auxiliary Output 4 (Charger D+)Connect to battery charger D+ terminal.
15, 16Magnetic PickupEngine speed sensing.
17Temperature Sensor InputFor engine temperature monitoring.
18Oil Pressure Sensor InputFor engine oil pressure monitoring.
19Fuel Level Sensor InputFor fuel tank level monitoring.
20-22Auxiliary Inputs 1-3Configurable inputs for various sensors/switches.
23-26Current Inputs (IA, IB, IC)Rated 5A. For current transformer connections.
27-30RS485 (ISOLATION)For remote communication.
31-34Mains Voltage InputsFor monitoring utility power.
35-37Gens Voltage InputsFor monitoring generator output voltage.
38-43CAN SCR, CAN H, CAN LCAN bus communication.
USB PortPC ConnectionFor PC connection and configuration.
Ethernet PortNetwork ConnectionFor network communication.

3. Initial Power-Up

After all connections are verified, apply power to the controller. The LCD display should illuminate, and the controller will perform a self-test. Follow any on-screen prompts for initial setup or calibration.

Operating Instructions

1. Control Panel Overview

The HGM6120N features an intuitive control panel with an LCD display and various buttons for operation and navigation.

  • LCD Display: Shows generator parameters (voltage, frequency, current, power, RPM, temperature, oil pressure, fuel level), alarms, and operational status.
  • Alarm Button: Indicates active alarms.
  • Status Button: Displays current operational status.
  • Load Buttons (Close/Open): Manually control the load breaker.
  • Mains Buttons (Close/Open): Manually control the mains breaker.
  • Genset Buttons (Close/Open): Manually control the genset breaker.
  • Auto Button: Activates Automatic Mains Failure (AMF) mode.
  • Manual Button: Activates Manual mode.
  • Start Button: Initiates generator start sequence (in Manual mode).
  • Stop Button: Initiates generator stop sequence.
  • Navigation Buttons (Up, Down, Left, Right, OK): Used for menu navigation and parameter adjustment.

2. Operating Modes

  • Manual Mode:

    Press the Manual button to enter manual mode. In this mode, the generator can be started and stopped manually using the Start and Stop buttons. Breakers can also be controlled manually.

  • Automatic Mode (AMF):

    Press the Auto button to enter automatic mode. In this mode, the controller continuously monitors the mains power supply. If a mains failure is detected, the controller will automatically start the generator, transfer the load, and stop the generator when mains power is restored.

3. Monitoring Parameters

The LCD display provides real-time monitoring of various generator and mains parameters. Use the navigation buttons to scroll through different screens and view detailed information such as:

  • Generator Voltage (V)
  • Generator Frequency (Hz)
  • Generator Current (A)
  • Generator Power (kW)
  • Engine RPM
  • Engine Temperature (°C)
  • Oil Pressure (kPa)
  • Battery Voltage (V)
  • Fuel Level
  • Mains Voltage and Frequency

Maintenance

  • Regular Cleaning: Keep the controller's display and buttons clean using a soft, dry cloth. Avoid abrasive cleaners or solvents.
  • Connection Checks: Periodically inspect all wiring connections for tightness and signs of corrosion. Ensure all terminals are secure.
  • Firmware Updates: Check the manufacturer's website for any available firmware updates to ensure optimal performance and access to new features.
  • Battery Check: Ensure the generator's battery, which powers the controller, is in good condition and properly charged.

Troubleshooting

This section provides guidance for common issues. For complex problems, contact technical support.

Problem Possible Cause Solution
Controller display is blank. No power supply, loose connections, faulty controller. Check battery connections and voltage. Verify power supply to the controller.
Generator fails to start in Auto mode. Mains power present, low fuel, low battery, engine fault, incorrect parameters. Check mains status. Verify fuel level and battery charge. Check engine for faults. Review controller parameters.
Generator starts but does not take load. Breaker issue, load transfer settings, generator fault. Check load breaker status. Verify load transfer parameters. Check generator output.
Alarm indicator is active. Engine fault, sensor error, operational issue. Press the Alarm button to view the specific alarm message on the LCD. Address the underlying cause.

Specifications

Feature Detail
Model NumberHGM6120N
Brand NameSmartGen (also listed as ezhiyuan)
OriginMainland China
High-concerned chemicalNone
Auxiliary Output 1, 27A/250VAC
Fuel, Crank, Auxiliary Output 316A rated
Current Inputs5A rated
CommunicationRS485, CAN bus, USB, Ethernet
DisplayLCD

User Tips

  • Authenticity Check: Always verify the authenticity of your SmartGen HGM6120N controller to ensure full compatibility, reliable performance, and access to official support and firmware updates.
  • Configuration Assistance: For advanced parametrization and specific application configurations, it is recommended to consult the manufacturer's official documentation or contact their technical support for expert guidance.
  • Regular Monitoring: Periodically check the LCD display for generator parameters and any active alarms to ensure smooth operation and prevent potential issues.

Warranty and Support

For warranty information, technical support, or service inquiries, please contact the manufacturer or your authorized dealer. Keep your purchase records handy when seeking support.

Manufacturer: SmartGen (or ezhiyuan)

Origin: Mainland China