1. Introduction

The MUST PV3500 TLV Series is a low frequency off-grid pure sine wave solar inverter. This multi-function inverter combines the capabilities of an inverter, an MPPT solar charger controller, and a battery charger. It is designed to provide uninterruptible power support in a portable size, suitable for various solar power system home applications.

2. Key Features

  • Low Frequency Pure Sine Wave Inverter
  • Integrated MPPT Solar Charger Controller (100A/200A options)
  • Built-in Battery Charger
  • Large LCD display for user-friendly operation and monitoring
  • Clear battery information (Gel U.S.A, A.G.M. 1, A.G.M. 2, Sealed Lead Acid, Gel European) and charge/float voltages printed on the case for easy reference.
  • Two large cooling fans for efficient heat dissipation, with speed controlled by temperature and load power.
  • Comprehensive protection features including Overload Protection.
  • Communication options: WIFI / RS485.
  • Supports various battery types: Lead Acid, Lithium, Gel.
  • Input Voltage: 220/230/240VAC
  • Output Voltage: 110/120V
  • Output Frequency: 50Hz/60Hz
  • High Inverter Efficiency: 95%

3. Product Overview

3.1 Product Video

This video provides a visual overview of the PV3500 PRO series inverter, highlighting its design, display, cooling fans, and various connection ports.

3.2 Inverter Components

The inverter features a user-friendly design with a clear LCD display and accessible connection terminals. Below are images illustrating different views of the inverter.

Top-front view of the MUST PV3500 TLV inverter, showing the LCD display and 'Solar Inverter' branding.
Top-front view of the inverter
Side view of the MUST PV3500 TLV inverter, showing mounting brackets and ventilation.
Side view of the inverter
Rear-top view of the MUST PV3500 TLV inverter, showing the back panel connections and cooling fans.
Rear-top view of the inverter
Rear-bottom view of the MUST PV3500 TLV inverter, showing the back panel connections and cooling fans.
Rear-bottom view of the inverter

3.3 Back Panel Description

Detailed diagram of the inverter's back panel, labeling all ports and indicators.
Back Panel Layout and Connections

The back panel of the inverter provides all necessary connection points and indicators for operation. Refer to the diagram above for the location of each component:

  1. Switch ON/OFF
  2. LCD display
  3. AC/Inverter indicator
  4. Charging indicator
  5. Fault indicator
  6. BAT- (Battery Negative Terminal)
  7. BAT+ (Battery Positive Terminal)
  8. USB communication port
  9. AC input/Bypass breaker
  10. AC output breaker
  11. Remote control port
  12. Fan
  13. BTS (Battery Temperature Sensor)
  14. AGS (Automatic Generator Start)
  15. AC input terminals
  16. AC output terminals
  17. Ground terminal
  18. PV input terminals

4. Installation & Connections

Proper installation and connection are crucial for the safe and efficient operation of your inverter. Always ensure the inverter is turned OFF before making any connections.

4.1 Battery Connection

Connect your battery bank to the BAT+ and BAT- terminals on the back panel. Ensure correct polarity (red for positive, black for negative). The inverter supports 48VDC battery systems. Use appropriate cable gauges for your battery bank capacity.

4.2 AC Input/Output Connections

Connect your AC input source (grid or generator) to the AC input terminals. Connect your AC loads to the AC output terminals. Ensure all connections are secure and protected by the integrated AC input/bypass and AC output breakers.

4.3 PV Input Connections

Connect your solar panel array to the PV input terminals. The inverter features an MPPT solar charger controller, so ensure your PV array voltage and current are within the specified limits (refer to specifications table).

4.4 Grounding

Connect the inverter to a reliable earth ground using the designated Ground terminal to ensure safety and prevent electrical hazards.

5. Operation

5.1 Powering On/Off

Use the ON/OFF switch on the back panel to power the inverter on or off. Ensure all connections are made before powering on.

5.2 LCD Display and Indicators

The large LCD display provides real-time information about the inverter's status, battery levels, and power flow. The AC/Inverter, Charging, and Fault indicators provide quick visual status updates.

5.3 Battery Information

The inverter's case includes printed information on various battery types (Gel U.S.A, A.G.M. 1, A.G.M. 2, Sealed Lead Acid, Gel European) and their corresponding charge and float voltages. This helps in selecting the correct battery settings for optimal performance and longevity.

6. Specifications

The following table details the technical specifications for the PV3500 TLV series inverters (PV35-8048 TLV, PV35-10048 TLV, PV35-12048 TLV models):

Table of detailed technical specifications for PV3500 TLV series inverters.
Technical Specifications
FeaturePV35-8048 TLVPV35-10048 TLVPV35-12048 TLV
Nominal Battery System Voltage48V
INVERTER OUTPUT
Rated power8.0KW10.0KW12.0KW
Surge rating24000VA30000VA36000VA
Capable of starting electric motor4HP5HP6HP
WaveformPure sine wave / same as input (bypass mode)
Nominal output voltage RMS100V/110V/120V/200V/220V/240V
Output frequency50Hz / 60Hz ± 0.3Hz
Inverter efficiency (peak)>95%
Line mode efficiency>95%
Power factor1.0
Typical transfer time20ms (max)
AC INPUT
Selectable voltage range90-280 VAC (APL)
Frequency range50Hz / 60Hz
BATTERY
Low battery voltage cutoff40-48VDC for 48VDC mode
Low battery voltage recover42-50VDC for 48VDC mode
High battery voltage cutoff60VDC for 48VDC mode
High battery voltage recover57VDC for 48VDC mode
Idle consumption-search mode< 60W when power saver on
Output voltageDepends on battery type
AC CHARGER
Overcharge protection S.D.31.4VDC for 24VDC mode / 62.8VDC for 48VDC mode
Maximum charge current60A70A80A
Continuous output powerYes (Variances in charging voltage & S.D. voltage base on the battery temperature)
BYPASS
Input voltage waveformSine wave (grid or generator)
Nominal input frequency50Hz or 60Hz
Overload protection (SMPS Load)Circuit breaker
Output short circuit protectionCircuit breaker
Bypass breaker rating63A63A63A
Max bypass current80Amp
SOLAR CHARGER
Maximum PV charge current100A
DC voltage48V
Maximum PV array power5000W (10000W for 200A optional)
MPPT range @ operating voltage (VDC)64-145VDC
Maximum PV array open circuit voltage145VDC
Maximum efficiency>98%
Standby power consumption<2W
MECHANICAL SPECIFICATIONS
MountingWall mount
Dimensions (W*H*D)670*410*215mm
Net weight (Solar CHG) (kg)69 ± 2.575.75 ± 2.575.75 ± 2.5
Shipping dimensions (W*H*D)884*618*443mm
Shipping Weight (Solar CHG) (kg)82.5 ± 2.589 ± 2.592 ± 2.5
OTHER
Operation temperature range0°C to 40°C
Storage temperature-15°C to 60°C
Audible noise60dB MAX
DisplayLED + LCD
Loading (20GP/40GP/40HQ)140pcs / 280pcs / 320pcs

The technical specifications of this document are subject to change without notice.

7. Maintenance

To ensure the longevity and optimal performance of your inverter, regular maintenance is recommended:

  • Cooling Fans: The inverter is equipped with two large cooling fans. Ensure that the air vents are not obstructed to allow for proper airflow. Periodically check and clean the fans to prevent dust buildup, which can impair cooling efficiency.
  • Connections: Periodically inspect all electrical connections (battery, AC input/output, PV input) to ensure they are tight and free from corrosion.
  • Environment: Keep the inverter in a clean, dry, and well-ventilated area within the specified operating temperature range (0°C to 40°C).

8. Troubleshooting

If you encounter issues with your inverter, please refer to the following general troubleshooting steps. For complex problems, contact technical support.

  • No Power: Check the ON/OFF switch, battery connections, and input AC/PV sources. Ensure breakers are not tripped.
  • Fault Indicator On: Note the specific fault code on the LCD display (if available) and consult the full product manual for detailed error descriptions and solutions. Common faults include overload, short circuit, or battery issues.
  • No Output: Verify that loads are correctly connected and within the inverter's capacity. Check AC output breaker.

9. Warranty & Support

The MUST PV3500 TLV Series Inverter comes with a 1-year warranty. For warranty claims, technical support, or any product-related inquiries, please contact your vendor or the manufacturer directly.

For immediate assistance, you may contact the sales team via WhatsApp: +86 13925760216.

10. Packaging & Logistics

To ensure the safety of your goods during transit, professional, environmentally friendly, convenient, and efficient packaging services are provided. Due to the heavy nature of these products, air or sea freight through a nominated freight forwarder is recommended. The product package dimensions are approximately 60cm (Length) x 40cm (Width) x 25cm (Height) with a weight of 30.0 kg.

Image showing a product being prepared for shipping, emphasizing professional packaging.
Professional Packaging
Image depicting various modes of logistics including air, sea, and land transport for product delivery.
Logistics Options

Ask a question about this manual

Ask about setup, troubleshooting, compatibility, parts, safety, or missing instructions. Manuals+ will review the question and use this page’s manual context to help answer it.