1. Introduction
This manual provides essential information for the safe and efficient operation, installation, and maintenance of the SmartGen HGM6010K, HGM6020K, HGM6110K, HGM6120K, and HGM6100 series Generator Set Controllers. These controllers are designed for automatic control and monitoring of generator sets, offering features such as automatic start/stop, data measurement, alarm protection, and remote control capabilities. Please read this manual thoroughly before installation and operation.
Video 1: General product introduction (may feature various industrial components).
2. Setup and Installation
2.1 Safety Precautions
- Ensure all power is disconnected before attempting any installation or wiring.
- Only qualified personnel should perform installation and wiring.
- Verify all connections are secure and correctly polarized.
- Proper grounding is essential for safety and optimal performance.
2.2 Mounting
The controller is typically panel-mounted. Ensure adequate space for ventilation and access to wiring terminals. Secure the controller using the provided mounting hardware.
2.3 Wiring Diagram
Refer to the detailed wiring diagram below for proper connection of the controller to the generator set and external systems. Incorrect wiring can cause damage to the controller or the generator set.

Image 2: Rear view of the SmartGen HGM6110K controller showing wiring terminals and diagram.
Terminal Connections Overview:
| Terminal No. | Description | Notes |
|---|---|---|
| B- | Battery Negative | |
| B+ | Battery Positive | |
| EMERGENCY STOP | Emergency Stop Input | |
| FUEL (16A) | Fuel Output | Rated 16A |
| CRANK (16A) | Crank Output | Rated 16A |
| AUX. OUTPUT 1 (7A) | Auxiliary Output 1 | Rated 7A |
| AUX. OUTPUT 2 (7A/250VAC) | Auxiliary Output 2 | Rated 7A/250VAC |
| AUX. OUTPUT 3 (16A/250VAC) | Auxiliary Output 3 | Rated 16A/250VAC |
| AUX. OUTPUT 4 (16A/250VAC) | Auxiliary Output 4 | Rated 16A/250VAC |
| CHARGER (D+) | Charger Excitation Input | |
| GENS VOLTAGE (U, V, W, N2) | Generator Voltage Inputs | Phases U, V, W, Neutral N2 |
| MAINS VOLTAGE (R, S, T, N1) | Mains Voltage Inputs | Phases R, S, T, Neutral N1 |
| MAGNETIC PICKUP | Magnetic Pickup Input | For engine speed sensing |
| OIL PRESSURE | Oil Pressure Sensor Input | |
| ENGINE TEMP | Engine Temperature Sensor Input | |
| AUX. INPUT 1-5 | Auxiliary Digital Inputs | Configurable inputs |
| LCD CONTRAST ADJUST | LCD Contrast Adjustment | Potentiometer for display clarity |
| PROGRAM PORT | Programming Port | For connecting to PC for configuration |
| RS485 GND | RS485 Ground | |
| RS485 (ISOLATION) | RS485 Communication Interface | Isolated for protection |
| CURRENT (RATED 5A) IA, IB, IC, ICOM | Current Transformer Inputs | Rated 5A for phases A, B, C and Common |
Additional features indicated on the diagram include checkboxes for 'Remote start module', 'AMF module', and 'RS485 communication', suggesting these are optional or configurable functionalities.
3. Operating Instructions
3.1 Front Panel Overview
The controller features an intuitive front panel with an LCD display, buttons, and indicator lights for easy operation and monitoring.

Image 3: Front panel of the SmartGen HGM6110K controller with English labels.
Button Functions:
- STOP (Red Circle): Stops the generator set and resets any active alarms.
- MAN (Hand Icon): Activates Manual mode, allowing manual control of the generator set.
- AUTO (AUTO Icon): Activates Automatic mode, enabling the controller to automatically start/stop the generator based on configured conditions (e.g., mains failure).
- MENU (Three Lines Icon): Accesses the controller's menu for parameter settings and system information.
- START (Green 'I' Icon): Initiates the generator start sequence (typically in Manual mode).
- UP/DOWN Arrows (Triangle/Inverted Triangle): Navigates through menu options or adjusts parameter values.
- OK (Circle): Confirms selections or enters sub-menus.
Indicator Lights:
- ALARM (Bell Icon): Illuminates when an alarm condition is detected.
- RUNNING (Engine Icon): Illuminates when the generator set is running.
- GENERATOR (Generator Icon): Indicates generator status.
- CLOSE/OPEN (Switch Icon): Indicates the status of the generator breaker (closed or open).
- LOAD (Building Icon): Indicates load status.
3.2 Basic Operation Sequence
- Power On: Ensure the controller is powered by the battery (B+ and B- terminals). The LCD display should light up.
- Select Mode: Press the AUTO button for automatic operation or the MAN button for manual control.
- Manual Start (if in MAN mode): Press the START button. The controller will initiate the cranking sequence.
- Manual Stop (if in MAN mode): Press the STOP button.
- Alarm Reset: After resolving an alarm condition, press the STOP button to reset the alarm.
4. Maintenance
Regular maintenance ensures the longevity and reliable operation of your SmartGen controller.
- Cleaning: Periodically clean the controller's exterior with a soft, dry cloth. Do not use abrasive cleaners or solvents. Ensure the display is clear of dust and debris.
- Connection Checks: Annually, or as needed, inspect all wiring connections to ensure they are tight and free from corrosion. Loose connections can lead to intermittent operation or damage.
- Environmental Conditions: Ensure the operating environment remains within specified temperature and humidity ranges to prevent damage.
- Firmware Updates: Check the manufacturer's website for any available firmware updates. Follow the provided instructions carefully if performing an update.
5. Troubleshooting
This section provides guidance for common issues. For complex problems, contact technical support.
5.1 Common Issues and Solutions
- Controller Not Powering On:
- Check battery connections (B+ and B-).
- Verify battery voltage is within the controller's operating range.
- Inspect fuses in the power supply circuit.
- Generator Not Starting in AUTO Mode:
- Check if the mains supply is present and stable (if AMF function is enabled).
- Ensure all safety interlocks are satisfied (e.g., emergency stop not active).
- Verify fuel level and engine oil pressure.
- Check for active alarms on the display.
- Alarm Indicator Active:
- Read the alarm message on the LCD display to identify the fault.
- Address the underlying cause of the alarm (e.g., low oil pressure, high engine temperature).
- Press the STOP button to reset the alarm after the fault is cleared.
- Incorrect Readings on Display:
- Verify sensor connections (Oil Pressure, Engine Temp, Magnetic Pickup).
- Check CT (Current Transformer) connections for current readings.
- Ensure voltage inputs (GENS VOLTAGE, MAINS VOLTAGE) are correctly wired.
6. Specifications
| Feature | Specification |
|---|---|
| Product Type | Generator Set Controller |
| DIY Supplies Category | Electrical |
| Origin | Mainland China |
| Package Length | 22 cm |
| Package Width | 22 cm |
| Package Height | 11 cm |
| Package Weight | 2.0 kg |
| Current Transformer Inputs | Rated 5A |
| Auxiliary Outputs | Various ratings up to 16A/250VAC |
| Communication | RS485 (Isolated) |
7. User Tips
- Consult Full Documentation: Always refer to the comprehensive user manual (if available from the manufacturer) for detailed wiring diagrams, parameter settings, and advanced features specific to your exact model.
- Proper Grounding: Ensure the controller and the generator set are properly grounded to prevent electrical hazards and ensure stable operation.
- Battery Health: Regularly check the generator's battery voltage and connections. A weak battery can lead to starting issues or erratic controller behavior.
- Environmental Protection: Protect the controller from direct sunlight, excessive moisture, and extreme temperatures to prolong its lifespan.
- Test Regularly: Periodically test the automatic start/stop function and alarm systems to ensure they are working correctly.
8. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your original seller or the manufacturer directly. Keep your purchase records handy when seeking support.