PowMr POW-HVM10.2M, POW-HVM6.2M-48V-N, POW-HVM4.2M-24V-N, POW-HVM3.2H-24V-N

Contents

PowMr Hybrid Solar Inverter User Manual

Models: POW-HVM10.2M, POW-HVM6.2M-48V-N, POW-HVM4.2M-24V-N, POW-HVM3.2H-24V-N

1. Introduction

This manual provides detailed instructions for the assembly, installation, operation, and troubleshooting of the PowMr Hybrid Solar Inverter. Please read this manual thoroughly before installation and operation, and keep it for future reference. This inverter/charger combines the functions of an inverter, solar charger, and battery charger to provide uninterruptible power support in a compact size. Its comprehensive LCD display allows for user-configurable settings such as battery charging current, AC/solar charger priority, and acceptable input voltage ranges for various applications.

1.1 Key Features

  • Pure sine wave output.
  • Configurable input voltage range for home appliances and personal computers via LCD settings.
  • Configurable battery charging current based on application needs via LCD settings.
  • Configurable AC/Solar Charger priority via LCD settings.
  • Compatible with mains voltage or generator power.
  • Automatic restart upon AC recovery.
  • Integrated overload, over-temperature, and short-circuit protection.
  • Smart battery charger design for optimized battery performance.
  • Cold start function.
  • Equipped with three cooling fans for efficient heat dissipation.
  • Anti-dust kit to protect internal components.
  • Real-time display of information data, including mode, voltage, current, and error codes.
  • Remote monitoring and control via the "SMARTESS" app (optional WiFi module required).

1.2 Basic System Architecture

The inverter/charger is designed to integrate with a generator or utility power source and PV modules to form a complete hybrid power system. It can power various appliances in home or office environments, including motor-type appliances like tube lights, fans, refrigerators, and air conditioners.

Hybrid Power System Diagram
Figure 1: Basic Hybrid Power System Architecture. This diagram illustrates how the solar inverter connects to solar panels, a generator or utility grid, external battery packs, and home appliances.

2. Safety Instructions

WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  • Before using the unit, read all instructions and cautionary markings on the unit, the batteries, and all appropriate sections of this manual.
  • CAUTION: To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
  • Do not disassemble the unit. Take it to a qualified service center when service or repair is required. Incorrect re-assembly may result in a risk of electric shock or fire.
  • To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning. Turning off the unit will not reduce this risk.
  • CAUTION: Only qualified personnel can install this device with battery.
  • NEVER charge a frozen battery.
  • For optimum operation, select appropriate cable sizes as per specifications.
  • Be very cautious when working with metal tools on or around batteries. A potential risk exists to drop a tool to spark or short circuit batteries or other electrical parts and could cause an explosion.
  • Strictly follow installation procedures when disconnecting AC or DC terminals. Refer to the INSTALLATION section.
  • A 150A fuse is provided for over-current protection for the battery supply.
  • GROUNDING INSTRUCTIONS: This inverter/charger should be connected to a permanent grounded wiring system. Comply with local requirements and regulations.
  • NEVER cause AC output and DC input short circuits. Do NOT connect to the mains when DC input short circuits.
  • Warning! Only qualified service persons are able to service this device. If errors persist after troubleshooting, send the inverter/charger back to a local dealer or service center.

3. Product Overview

The PowMr Hybrid Solar Inverter features a user-friendly interface with an LCD display, status indicators, and function buttons for easy operation and monitoring.

Inverter Front and Side View with Labeled Components
Figure 2: Inverter Front and Side View. This image labels the LCD display, status indicators, charging indicator, fault indicator, touch function buttons, power on/off switch, AC input, main output, second output, PV1 and PV2 input, communication ports (WIFI/RS-232, RS-485), battery input, and anti-dust kit.

3.1 Components and Controls

  1. LCD display
  2. Status indicator
  3. Charging indicator
  4. Fault indicator
  5. Touch Function buttons
  6. Power on/off switch
  7. AC input
  8. Main output
  9. Second output
  10. PV1 and PV2 input
  11. WIFI communication/RS-232 port
  12. Battery communication/RS-485 port
  13. Battery input
  14. Anti-dust kit
Inverter Display and Buttons
Figure 3: Close-up of Inverter Display and Function Buttons. The display shows various operational parameters, and the buttons (ESC, UP, DOWN, ENTER) are used for navigation and settings.

3.2 LED Indicators and Function Keys

LED IndicatorColorStateMessage
INV/ACGreenSolid OnOutput is powered by utility in Line mode.
FlashingOutput is powered by battery or PV in battery mode.
CHGGreenSolid OnBattery is fully charged.
FlashingBattery is charging.
FAULTRedSolid OnFault occurs in the inverter.
FlashingWarning condition occurs in the inverter.
Function KeyDescription
ESCTo exit setting mode
UPTo go to previous selection
DOWNTo go to next selection
ENTERTo confirm the selection in setting mode or enter setting mode

4. Installation

4.1 Unpacking and Inspection

Before installation, carefully inspect the unit for any damage. The package should contain:

  • The inverter unit x 1
  • User manual x 1
  • Ring terminal x 1
  • MC4 terminal head x 2

4.2 Preparation and Mounting

Before connecting any wires, remove the screws under the machine and detach the bottom cover plate.

Mounting Considerations:

  • Do not mount the inverter on flammable construction materials.
  • Mount on a solid surface.
  • Install at eye level for easy LCD display readability.
  • Allow approximately 20 cm clearance to the sides and above/below for proper air circulation and heat dissipation.
  • The ambient temperature should be between 0°C and 55°C for optimal operation.
  • Adhere the unit vertically to the wall.
  • Ensure sufficient space around the unit for heat dissipation and wiring access.

WARNING: SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.

Install the unit by screwing two M4 or M5 screws into the wall.

4.3 Battery Connection

CAUTION: For safety and regulation compliance, install a separate DC over-current protector or disconnect device between the battery and inverter. Refer to the table below for recommended fuse or breaker size.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for battery connection to reduce risk of injury.

ModelWire SizeCable (mm²)Torque Value (max)
8.2KW/10.2KW1 x 2AWG252 Nm

Battery Connection Steps:

  1. Remove 18 mm of insulation sleeve from positive and negative conductors.
  2. Suggest using bootlace ferrules on the ends of positive and negative wires with a proper crimping tool.
  3. Connect all battery packs as shown in the diagram below.
  4. Insert battery wires flatly into inverter battery connectors and tighten bolts with a torque of 2 Nm. Ensure correct polarity.
Battery Connection Diagram
Figure 4: Battery Connection Diagram. Illustrates connecting multiple 12V battery packs in series to the inverter for 48V systems.

WARNING: Shock Hazard. Installation must be performed with care due to high battery voltage in series.

CAUTION! Before making the final DC connection or closing DC breaker/disconnector, ensure positive (+) is connected to positive (+) and negative (-) to negative (-).

4.4 AC Input/Output Connection

CAUTION! Install a separate AC breaker between the inverter and AC input power source. This ensures secure disconnection during maintenance and over-current protection. Recommended AC breaker for 8.2KW/10.2KW is 63A.

CAUTION! There are two terminal blocks: "IN" and "OUT". Do NOT mis-connect input and output connectors.

WARNING! All wiring must be performed by qualified personnel. Use appropriate cable for AC input connection.

Suggested Cable Requirement for AC Wires:

ModelGaugeCable (mm²)Torque Value
8.2KW/10.2KW10 AWG61.2 Nm

AC Input/Output Connection Steps:

  1. Before making AC input/output connections, open the DC protector or disconnector.
  2. Remove 10mm insulation sleeve for six conductors. Shorten phase L and neutral conductor N by 3mm.
  3. Insert AC input wires according to polarities (Ground: yellow-green, LINE: brown or black, Neutral: blue) and tighten terminal screws.

WARNING: Ensure AC power source is disconnected before attempting to hardwire it to the unit.

  1. Insert AC output wires according to polarities (LINE: brown or black, Neutral: blue) and tighten terminal screws.
  2. Ensure all wires are securely connected.

CAUTION: Appliances like air conditioners require 2-3 minutes to restart. If a power shortage occurs and recovers quickly, it can damage connected appliances. Check if your appliance has a time-delay function. Otherwise, the inverter will trigger an overload fault to protect the appliance, but internal damage may still occur.

4.5 PV Connection

CAUTION: Before connecting to PV modules, install a separate DC circuit breaker between the inverter and PV modules.

WARNING! Use appropriate cable for PV module connection to reduce risk of injury.

Suggested Cable Requirement for PV Wires:

ModelWire SizeCable (mm²)Torque Value (max)
8.2KW/10.2KW1 x 10AWG61.2 Nm

PV Module Selection:

When selecting PV modules, consider the following parameters:

  • Open circuit Voltage (Voc) of PV modules must not exceed the inverter's max. PV array open circuit voltage.
  • Open circuit Voltage (Voc) of PV modules should be higher than the min. battery voltage.
INVERTER MODELMax. PV Array Open Circuit VoltagePV Array MPPT Voltage Range
8.2KW/10.2KW500Vdc90Vdc~450Vdc

PV Module Wire Connection Steps:

  1. Disconnect the DC circuit breaker.
  2. Assemble PV connectors with PV modules using the provided components (female connector housing, female terminal, male connector housing, male terminal, crimping tool, spanner). Strip 8mm of cable insulation.
  3. Check correct polarity of connection cable from PV modules and PV input connectors. Connect positive (+) to positive (+) and negative (-) to negative (-).

CAUTION: Exceeding the maximum input voltage can destroy the unit! Check the system before wire connection.

4.6 Final Assembly

After connecting all wirings, replace the bottom cover and secure it with two screws.

4.7 Communication Connection

Wi-Fi Cloud Communication (Optional):

Use the supplied communication cable to connect to the inverter and Wi-Fi module. Download the "SMARTESS" app from the App Store or Google Play. Refer to the "Wi-Fi Plug Quick Installation Guideline" for network setup and registration. The inverter status can then be monitored via the mobile app or a computer webpage.

Remote Monitoring App and WiFi Module
Figure 5: Remote Monitoring and Control via the "SMARTESS" App. Shows the optional WiFi module connected to the inverter and the mobile app interface for monitoring.

GPRS Cloud Communication (Optional):

Use the supplied communication cable to connect to the inverter and GPRS module. Apply external power to the GPRS module. Download the app and refer to the "GPRS RTU Quick Installation Guideline" for setup. Inverter status can be viewed via the mobile app or webpage.

Battery Communication:

Communication between the battery and inverter is achieved through the battery communication interface, allowing information exchange (Baud rate: 9600).

Lithium Battery and Inverter Connection:

Use power cables and communication cables for lithium batteries and inverters. Ensure correct polarity for lithium battery and inverter positive/negative positions. The RJ45 connector of the communication cable connects to the BMS port of the inverter, and the other RJ45 connector connects to the RS485 port of the lithium battery. Before connecting, ensure both the lithium battery and inverter are turned off. It is recommended to install a circuit breaker for the power cables to prevent sparks.

Lithium Battery Communication Cable Interface
Figure 6: Lithium Battery Communication Cable Interface. Details the connection method for RJ45 cables to the BMS port on the inverter and the RS485 port of the lithium battery.

To communicate with the lithium battery BMS, press the "ENTER" button for a long time and set the battery type as "LIB-485" in program 05. Then select the matching battery protocol in Program 43.

ProgramSettingOptions
05Battery typeAGM (default), Flooded, User Defined, LIB (for Lithium)
43Lithium battery protocolPYLON, PACE

CAUTION: When battery type is "LIB-485", items 12, 13, and 29 are displayed in percentage. The user cannot modify the maximum charging current. If communication fails, the inverter will cut off the output.

5. Operation

5.1 Power ON/OFF

Once the unit is properly installed and batteries are connected, press the On/Off switch (located on the side of the unit) to turn on the inverter.

5.2 LCD Display Icons

The LCD displays various icons to indicate the system's status and information.

IconFunction Description
(AC Input Icon)Indicates the AC input.
(PV Input Icon)Indicates the PV input.
(Voltage/Current Display)Indicates input voltage, input frequency, PV voltage, charger current, charger power, battery voltage.
(Setting Program Icon)Indicates the setting programs.
(Warning/Fault Code Icon)Indicates warning and fault codes. Flashing for warning, solid for fault.
(Output Information Icon)Indicates output voltage, output frequency, load percent, load in VA, load in Watt, and discharging current.
(Overload Icon)Indicates overload.
(Mains Connection Icon)Indicates unit connects to the mains.
(PV Panel Connection Icon)Indicates unit connects to the PV panel.
(AC Bypass Icon)Indicates load is supplied by utility power.
(Utility Charger Circuit Icon)Indicates the utility charger circuit is working.
(DC/AC Inverter Circuit Icon)Indicates the DC/AC inverter circuit is working.
(Mute Icon)Indicates unit alarm is disabled.

5.3 LCD Settings

To enter setting mode, press and hold the "ENTER" button for 3 seconds. Use "UP" or "DOWN" to select programs, then "ENTER" to confirm or "ESC" to exit.

Key Settings:

  • Program 00 (Exit Setting Mode): Options for one-button restore (GOE, GOH).
  • Program 01 (Output Source Priority): Configures load power source priority.
    • Utility first (01 USE): Utility provides power first. Solar and battery energy used only when utility is unavailable.
    • Solar first (01 SOL): Solar energy provides power first. If insufficient, utility supplies power.
    • SBU priority (01 SBU): Solar energy first. If insufficient, battery energy used. Utility used only when battery voltage drops below a set point (Program 12).
    • MKS priority (01 MKS): Solar energy first. If insufficient, utility supplies power. Battery only for backup.
  • Program 02 (Maximum Charging Current): Configures total charging current for solar and utility chargers.
  • Program 03 (AC Input Voltage Range): Sets acceptable AC input voltage range (Appliances or UPS).
  • Program 05 (Battery Type): Selects battery type (AGM, Flooded, User-Defined, LIB).
  • Program 06 (Auto Restart when Overload Occurs): Enables/disables auto restart after overload.
  • Program 07 (Auto Restart when Over Temperature Occurs): Enables/disables auto restart after over temperature.
  • Program 09 (Output Frequency): Sets output frequency (50Hz or 60Hz).
  • Program 10 (Output Voltage): Sets output voltage (220V, 230V, 240V).
  • Program 11 (Maximum Utility Charging Current): Sets maximum charging current from utility.
  • Program 12 (Setting Voltage Point Back to Utility Source): For SBU or Solar first modes, sets the battery SOC point for switching to utility.
  • Program 13 (Setting Voltage Point Back to Battery Mode): For SBU or Solar first modes, sets the battery SOC point for switching to battery mode.
  • Program 16 (Charger Source Priority): Configures charger source priority (Solar first, Solar and Utility, Only Solar).
  • Program 18 (Alarm Control): Enables/disables buzzer alarm.
  • Program 19 (Auto Return to Default Display Screen): Sets display to return to default or stay on last screen.
  • Program 20 (Backlight Control): Enables/disables backlight.
  • Program 22 (Beeps while Primary Source is Interrupted): Enables/disables beeps when primary source is interrupted.
  • Program 23 (Overload Bypass): Enables/disables transfer to line mode during overload in battery mode.
  • Program 25 (Record Fault Code): Enables/disables fault code recording.
  • Program 26 (Bulk Charging Voltage): Sets bulk charging voltage (C.V voltage).
  • Program 27 (Floating Charging Voltage): Sets floating charging voltage.
  • Program 29 (Low DC Cut-off Voltage): Sets low DC cut-off voltage.
  • Program 30 (Battery Equalization): Enables/disables battery equalization.
  • Program 31 (Battery Equalization Voltage): Sets battery equalization voltage.
  • Program 33 (Battery Equalized Time): Sets battery equalized time.
  • Program 34 (Battery Equalized Timeout): Sets battery equalized timeout.
  • Program 35 (Equalization Interval): Sets equalization interval.
  • Program 36 (Equalization Activated Immediately): Activates equalization immediately.
  • Program 37 (GRID-tie Operation): Sets inverter operation mode (Off grid, Hybrid).
  • Program 38 (GRID-tie Current): Sets GRID-tie current.
  • Program 39 (LED Pattern Light): Sets LED pattern light (on/off).
  • Program 41 (Dual Output): Enables/disables dual output.
  • Program 42 (Enter the Dual Output Functional Voltage Point): Sets dual output functional voltage point.
  • Program 45 (Maximum Second Load): Sets maximum second load percentage (20%-70%).

5.4 Operating Mode Description

The inverter supports various operating modes, each indicated by RGB light patterns and LCD display information.

RGB Light for Different Working Modes:

  • Stationary Mode: White Light
  • Battery Mode: Red Light
  • Utility Mode: Blue Light
  • PV Mode: Purple Light
RGB Light Working Modes
Figure 7: RGB Light for Different Working Modes. Shows the inverter's logo light changing color to indicate its current operational mode (Stationary, Battery, Utility, PV).

Multiple Charging and Output Modes:

The inverter offers flexible charging and output priority settings to optimize energy usage.

Multiple Charging and Output Modes Diagram
Figure 8: Multiple Charging and Output Modes. Illustrates different priority settings for charging (Solar priority, Solar+Utility, Only solar, Utility/AC Power first) and output (Utility Source first, Solar power first, Solar+battery power load at the same time).

5.5 Battery Equalization Description

Battery equalization reverses negative chemical effects like stratification and removes sulfate crystals, extending battery life. It can be applied by setting an equalization interval (Program 35) or activating immediately (Program 36).

In the float stage, when the equalization interval is reached or activated, the controller enters the Equalize stage. The controller charges the battery until it reaches the equalization voltage, then maintains it. If the battery voltage is still low after the equalized time and timeout, the controller stops equalization and returns to float stage.

5.6 Mains and Lithium Battery Activation Function

  • The inverter connects to the mains and starts working 90 seconds after mains power connection.
  • If the inverter is in lithium battery mode (Program 05 is LIP or LIL) and the battery is not connected, the mains activation function is automatically enabled upon mains connection.

6. Maintenance

6.1 Anti-Dust Kit Clearance and Maintenance

The inverter comes with a pre-installed anti-dust kit. This kit helps protect the inverter from dust and improves reliability in harsh environments. It also activates an internal thermal sensor to adjust internal temperature.

Maintenance Steps:

  1. Loosen the screw on the top of the inverter in a counterclockwise direction.
  2. Remove the dustproof case and take out the air filter foam.
  3. Clean the air filter foam and dustproof case. Re-assemble the dust-kit back to the inverter.

NOTICE: The anti-dust kit should be cleaned every one month.

Intelligent Cooling Fan
Figure 9: Intelligent Cooling Fan. The solar inverter has a built-in sensor chip that intelligently adjusts the fan rotation speed according to the ambient temperature and the quality of the environment.

7. Troubleshooting

This section provides guidance for common issues. If problems persist, contact customer support.

7.1 Fault Reference Codes

The inverter displays fault codes on the LCD to indicate specific issues.

Fault CodeFault EventPossible Cause / What to do
01Fan is locked when inverter is off.Replace the fan.
02Over temperatureCheck air flow, ambient temperature.
03Battery voltage is too highCheck battery specifications.
04Battery voltage is too lowRe-charge or replace battery.
05Output short circuited or over temperature detected by internal converter components.Check wiring, remove abnormal load.
06Output voltage is too high.Reduce connected load.
07Overload time outReduce connected load.
08Bus voltage is too highReturn to repair center.
09Bus soft start failedReturn to repair center.
51Over current or surgeRestart unit, if error persists, return to repair center.
52Bus voltage is too lowRestart unit, if error persists, return to repair center.
53Inverter soft start failedReturn to repair center.
55Over DC voltage in AC outputRestart unit, if error persists, return to repair center.
57Current sensor failedReturn to repair center.
58Output voltage is too lowReduce connected load.
59PV voltage is over limitationReturn to repair center.

7.2 Battery Fault Codes (Lithium Battery Mode)

Fault CodeFault EventFault Condition
02Battery temperature is too highLithium battery charging temperature ≥65°C; discharge temperature >70°C.
03Battery voltage is too highLithium battery maximum single cell voltage >3.65V; total voltage >54.6V (48V lithium battery).
04Battery voltage is too lowMinimum voltage of a lithium battery cell <2.71V; total voltage <40.4V (48V lithium battery).

7.3 Warning Indicators

The inverter provides audible alarms and flashing icons for various warning conditions.

Warning CodeWarning EventAudible Alarm
01Fan is locked when inverter is on.Beep three times every second.
03Battery is over-chargedBeep once every second.
04Low batteryBeep once every second.
07OverloadBeep once every 0.5 second.
10Output power deratingBeep twice every 3 seconds.
15PV energy is low.Beep twice every 3 seconds.
E9Battery equalizationNone.
6PBattery is not connectedNone.

7.4 Battery Warning Codes (Lithium Battery Mode)

Warning CodeWarning EventWarning Condition
04Battery voltage is too lowMinimum voltage of a lithium battery cell <2.85V; total voltage <42V (48V lithium battery).
05Battery voltage is too highLithium battery maximum single cell voltage >3.55V; total voltage >54V (48V lithium battery).
06Battery is low warningRemaining battery capacity ≤10%.

8. Specifications

8.1 Line Mode Specifications

Parameter8.2KW10.2KW
Input Voltage WaveformSinusoidal (utility or generator)
Nominal Input Voltage230Vac
Low Loss Voltage (UPS)170Vac±7V
Low Loss Voltage (Appliances)90Vac±7V
Low Loss Return Voltage (UPS)180Vac±7V
Low Loss Return Voltage (Appliances)100Vac±7V
High Loss Voltage280Vac±7V
High Loss Return Voltage270Vac±7V
Max AC Input Voltage300Vac
Nominal Input Frequency50Hz / 60Hz (Auto detection)
Low Loss Frequency40±1Hz
Low Loss Return Frequency42±1Hz
High Loss Frequency65±1Hz
High Loss Return Frequency63±1Hz
Output Short Circuit ProtectionCircuit Breaker
Efficiency (Line Mode)>95% (Rated R load, battery full charged)
Transfer Time (UPS)10ms typical
Transfer Time (Appliances)20ms typical

8.2 Inverter Mode Specifications

Parameter8.2KW10.2KW
Rated Output Power8.2KW10.2KW
Output Voltage WaveformPure Sine Wave
Output Voltage Regulation230Vac±5%
Output Frequency50Hz
Peak Efficiency93%
Overload Protection3s@≥150% load; 5s@101%~150% load
Surge Capacity2* rated power for 5 seconds
Nominal DC Input Voltage48Vdc
Cold Start Voltage46.0Vdc
Low DC Warning Voltage (@load < 50%)44.0Vdc
Low DC Warning Voltage (@load ≥ 50%)42.0Vdc
Low DC Warning Return Voltage (@load < 50%)45.0Vdc
Low DC Warning Return Voltage (@load ≥ 50%)44.0Vdc
Low DC Cut-off Voltage (@load < 50%)41.0Vdc
Low DC Cut-off Voltage (@load ≥ 50%)40.0Vdc
High DC Recovery Voltage62Vdc
High DC Cut-off Voltage63Vdc
No Load Power Consumption70W75W

8.3 Two Load Output Power

Parameter8.2KW10.2KW
Full Load8200W10200W
Maximum Main Load8200W10200W
Second Load Range1640W~5740W2040W~7140W
Main Load Cut Off Voltage52VDC
Main Load Return Voltage54VDC

8.4 Charge Mode Specifications

Utility Charging Mode:

Parameter8.2KW10.2KW
Charging Algorithm3-Step
AC Charging Current (Max)140Amp
Bulk Charging Flooded Battery Voltage58.4V
Bulk Charging AGM / Gel Battery Voltage56.4V
Floating Charging Voltage54Vdc

MPPT Solar Charging Mode:

Parameter8.2KW10.2KW
Max. PV Array Power (PV1 Channel)5400W
Max. PV Array Power (PV2 Channel)5400W
IMax.PV (PV1 Channel)18A
IMax.PV (PV2 Channel)18A
Nominal PV Voltage360Vdc
PV Array MPPT Voltage Range90Vdc~450Vdc
Max. PV Array Open Circuit Voltage500Vdc
Max Charging Current (AC charger plus solar charger)160Amp

8.5 Grid-Tie Operation

Parameter8.2KW10.2KW
Nominal Output Voltage220/230/240 VAC
Feed-in Grid Voltage Range195~253VAC
Feed-in Grid Frequency Range50±1Hz/60±1Hz
Nominal Output Current35.6A44.3A
Power Factor Range>0.99
Maximum Conversion Efficiency (DC/AC)98%

8.6 General Specifications

Parameter8.2KW10.2KW
Safety CertificationCE
Operating Temperature Range-10°C to 50°C
Storage Temperature-15°C~60°C
Humidity5% to 95% Relative Humidity (Non-condensing)
Dimension (D*W*H), mm500*390*136mm
Net Weight, kg14.514.7

8.7 Approximate Back-up Time Table

Load (W)Backup Time @ 48Vdc 100Ah (min)Backup Time @ 48Vdc 200Ah (min)
5006131288
1000268613
1500158402
2000111271
250090215
320076182
350065141
400050112
450044100
50004090
62003680
72003270
82002860
92002450
102002040

Note: Backup time depends on the quality, age, and type of battery. Specifications may vary between manufacturers. The final interpretation right of this product belongs to the company.

9. User Tips

  • Battery Compatibility: This inverter is compatible with various 48V batteries, including Flooded, Gel, Sealed (default), LiFePO4, and user-customized battery types. For lithium batteries, ensure the correct battery type ("LIB-485") and protocol (PYLON or PACE) are set in programs 05 and 43 respectively.
  • Battery-less Operation: Some models of this inverter can work without a battery, but this depends on the specific model and configuration. Refer to the manual's specifications and operating modes for details.
  • PV Panel Connection: When connecting photovoltaic panels, ensure the total open circuit voltage (Voc) of the PV array does not exceed the inverter's maximum limit (e.g., 500Vdc for 8.2KW/10.2KW models). Also, ensure the Voc is higher than the minimum battery voltage.
  • Monitoring: Utilize the optional WiFi module and the "SMARTESS" app for remote monitoring and control of the inverter's status and performance.
  • Cooling and Dust: Regularly clean the anti-dust kit (monthly) to ensure efficient cooling and extend the inverter's lifespan, especially in dusty environments. The intelligent cooling fan adjusts speed based on temperature.
  • 110V Output: If you have a single-phase 110V output requirement, you will need to connect a transformer for conversion, as this inverter is a single-phase 220V inverter.

10. Frequently Asked Questions (FAQ)

Q: Can the PowMr 10200W 48V Solar Inverter work with a lithium battery?
A: Yes, the inverter is compatible with lithium batteries. You need to set the battery type to "LIB-485" in program 05 and select the appropriate lithium battery protocol (PYLON or PACE) in program 43. Refer to section 4.7 for detailed instructions.
Q: Can the 3.2KW inverter work without a battery?
A: The manual indicates that the inverter can operate in "Only solar" charging mode and "SBU mode" which prioritizes solar. While it can function without a battery in certain configurations (e.g., directly powering loads from solar), continuous operation without a battery might be limited depending on the specific model and load requirements. For detailed information, consult the operating mode descriptions and system architecture in the manual.
Q: Does the 4.2KW inverter have plugs for connecting photovoltaic panel strings?
A: Yes, the inverter has PV input terminals (PV1 and PV2 input) designed for connecting photovoltaic panel strings. The manual provides detailed instructions on how to prepare and connect the PV wires using MC4 terminal heads. Refer to section 4.5 for PV connection details.
Q: I need a display for my PowMr 10200W 48V Solar Inverter. Can you help?
A: The inverter comes with a built-in LCD display for operation and monitoring. If you are referring to an external display or a replacement, please contact PowMr customer support directly for assistance with parts or service. The manual does not specify external display options beyond the integrated LCD and app monitoring.

11. Warranty and Support

For technical support, warranty claims, or service, please contact PowMr directly using the information below. Only qualified service personnel should attempt repairs.

  • Tel/Fax: +86 755-28219903
  • Email: support@powmr.com
  • Web: www.powmr.com
  • Address: Henggang Street, Longgang District, Shenzhen, Guangdong, China