1. Product Overview
The HGM4000N series genset controllers integrate digitization, intelligentization, and network technology for genset automation and monitor control systems of single units. These controllers enable automatic start/stop, data measurement, and alarm protection functions.
Featuring an LCD display with selectable language interfaces (Chinese, English, Spanish, Russian, Turkish, French, Portuguese, and Polish), the HGM4000N series is designed for reliability and ease of use. It utilizes micro-processor technology for precise parameter measurement, fixed value adjustment, and time setting. All parameters can be configured from the front panel or via a programmable interface (USB or RS485) using a PC. Its compact structure, advanced circuits, simple connections, and high reliability make it suitable for various automatic genset control systems.
The HGM4000N series includes two main types:
- HGM4010N/HGM4010NC/HGM4010CAN: Automatic Start Module (ASM), controlling generator start/stop via remote signal.
- HGM4020N/HGM4020NC/HGM4020CAN: Auto Mains Failure (AMF), which builds upon the ASM functionality by adding mains electric quantity monitoring and automatic mains/generator transfer control, ideal for systems involving both a generator and mains power.
2. Key Features and Characteristics
- Display: 132x64 LCD with backlight and push-button operation.
- Durability: Hard-screen acrylic material for wear and scratch resistance; silicone panel and pushbuttons for extreme temperatures.
- Communication: RS485 interface for remote control, measuring, and communication (MODBUS protocol).
- CANBUS Support: Equipped with CANBUS port for J1939 genset communication, monitoring ECU data (water temperature, oil pressure, speed, fuel consumption) and controlling start/shutdown, speed adjustments.
- System Compatibility: Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems (120/240V, 50/60Hz).
- Parameter Measurement: Collects and displays 3-phase voltage, current, power, and frequency for both generator and mains.
- Mains/Generator: Line voltage (Uab, Ubc, Uca), Phase voltage (Ua, Ub, Uc), Frequency (Hz), Phase sequence.
- Load: Current (Ia, Ib, Ic in A), Each phase and total active power (P in kW), Reactive power (Q in kvar), Apparent power (S in kVA), Power factor (PF), Accumulated total generator power (W in kWh, kVarh, kVAh), Output percentage with load (%).
- Protection Functions:
- Mains: Over/under voltage, loss of phase detection.
- Generator: Over/under voltage, over/under frequency, over current, over power detection.
- Automatic start/stop, ATS (Auto Transfer Switch) control with comprehensive fault indication and protection.
- Engine Control: ETS (energize to stop), idle control, pre-heat control, and rise/drop speed control functions (all via relay outputs).
- Parameter Configuration: Parameters can be modified and stored in internal FLASH memory (non-volatile); adjustable via front panel or PC (USB/RS485).
- Flexible Inputs: Multiplex input ports 4 and 5 configurable as switch inputs, fuel level sensors, or programmable sensors for flexible application.
- Sensor Compatibility: Supports multiple temperature, pressure, and oil pressure sensors, with direct self-definition. One programmable sensor can be configured for temperature, pressure, or liquid level, enabling double detection.
- Crank Disconnect: Multiple crank disconnect conditions are optional (speed sensor, oil pressure, generator frequency).
- Emergency Start: Includes an emergency start function.
- Flywheel Recognition: Automatic flywheel tooth number recognition.
- Power Supply: Wide DC(8~35)V power supply range, compatible with various starting battery voltages.
- Digital Adjustment: All parameters use digital adjustment for enhanced reliability and stability, replacing conventional analog modulation.
- Maintenance Function: Configurable maintenance types (date and running time) and actions (warning, shutdown, or trip and stop) upon maintenance timeout.
- Logging & Scheduling: Event log (up to 99 events), real-time clock, and scheduled generator start/stop (daily/weekly/monthly, with or without load).
- Environmental Protection: IP55 waterproof security level with a rubber seal between the enclosure and panel fascia.
- Mounting: Metal fixing clips for high-temperature environments; modular design, anti-flaming ABS plastic enclosure, pluggable connection terminals, and embedded installation for compact and easy mounting.
3. Specifications
Refer to the table below for detailed technical parameters of the SmartGen HGM4010N controller.
| Item | Contents |
|---|---|
| Operating Voltage | DC8.0V to DC35.0V, Continuous Power Supply |
| Power Consumption | <3W (standby ≤2W) |
| Alternator Volt Input Range (ph-N) | AC15V-AC360V |
| Alternator Volt Input Range (ph-ph) | AC30V-AC620V |
| Single Phase 2Wire | AC15V-AC360V (ph-N) |
| 2Phase 3Wire | AC15V-AC360V (ph-N) |
| Alternator Frequency | 50Hz/60Hz |
| Speed Sensor Voltage | 1.0V to 24.0V (RMS) |
| Speed Sensor Frequency | 10,000 Hz (max.) |
| Starting Relay Output | 5A DC28V at supply output |
| Fuel Relay Output | 5A DC28V at supply output |
| Programmable Relay Output 1 | 1A DC28V at supply output |
| Programmable Relay Output 2 | 1A DC28V at supply output |
| Programmable Relay Output 3 | 1A DC28V at supply output |
| Programmable Relay Output 4 | 1A DC28V at supply output |
| Case Dimensions | 135mm x 110mm x 44mm |
| Panel Cutout | 116mm x 90mm |
| CT Secondary Current | 5A rated |
| Working Conditions | Temperature: (-25~+70)℃; Relative Humidity: (20~93)%RH |
| Storage Condition | Temperature: (-25~+70)℃ |
| Protection Level | IP65; rubber seal installed between the controller enclosure and panel fascia |
| Insulating Intensity | Apply AC2.2kV voltage between high voltage terminal and low voltage terminal; The leakage current is not more than 3mA within 1min. |
| Net Weight | 0.32kg |

4. Installation and Setup
4.1 Physical Installation
The HGM4010N controller features a modular design for embedded installation. Ensure the panel cutout dimensions are precisely followed for a secure fit.
- Case Dimensions: 135mm x 110mm x 44mm
- Panel Cutout: 116mm x 90mm
Use the provided metal fixing clips to secure the controller in place, especially in high-temperature environments. A rubber seal ensures IP55 waterproof protection when installed correctly between the controller enclosure and the panel fascia.

4.2 Electrical Connections
The controller uses pluggable connection terminals for easy wiring. Refer to the detailed wiring diagram below for proper electrical connections. Ensure all connections are secure and follow local electrical codes.

Important Wiring Notes (based on Figure 4.2):
- Terminals 1-20 (Bottom Row): These typically handle DC power, fuel, crank, auxiliary outputs, sensors (oil pressure, engine temp), ECU, magnetic pickup, and RS485 communication.
- 1-2: B- (Ground)
- 3: FUEL (5A)
- 4: CRANK (5A)
- 5: CHARGER D+
- 6-9: AUX OUTPUT 1-4 (1A each)
- 10-14: AUX SENSOR 1-2, ENGINE TEMP, OIL PRESSURE
- 15-17: ECU (J1939) CAN H, CAN L, SCR
- 18-20: RS485 (ISOLATION) A+, B-, ICOM
- Terminals 21-36 (Top Row): These are for Gens AC Voltage, Mains AC Voltage, and Current (Rated 5A).
- 21-24: AUX INPUT 1-3, GENS AC VOLTAGE (U, V, W, N2)
- 25-28: GENS AC VOLTAGE (U, V, W, N2)
- 29-32: MAINS AC VOLTAGE (R, S, T, N1)
- 33-36: CURRENT (RATED 5A) (IA, IB, IC, ICOM)
Always double-check the wiring against the diagram and ensure proper insulation and grounding to prevent damage to the controller or connected equipment.
5. Operating Instructions
The HGM4010N controller features an intuitive interface with dedicated buttons for various functions. Below is a description of each key function:
| Icon Description | Function | Description |
|---|---|---|
| Red circle with 'O' | Stop/Reset | Stops the running generator in Auto/Manual mode. In case of an alarm, pressing this button will reset the alarm. In stop mode, pressing and holding for 3 seconds will test indicator lights. During the stopping process, pressing again will stop the generator immediately. |
| Green rectangle with 'I' | Start | In Manual mode, pressing this button will start the genset. During genset start-up, it will jump to the next status and enable quick start. |
| Hand icon | Manual | Pressing this key sets the module into manual mode. |
| Swirl icon | Auto | Pressing this key sets the module into auto mode. |
| Circuit breaker icon | C/O | Pressing this key toggles the display C/O and the main page. Use Up or Down keys to control switch close or open in C/O interface under manual mode. |
| Gear icon | Set/Confirm | Pressing this key will enter the Main Menu. In parameter setting status, pressing this key will shift the cursor or confirm the setting value. |
| Up arrow icon | Up/Increase | Scrolls the screen up; shifts the cursor up or increases the set value in parameter setting menu. In C/O interface under manual mode, this button can control mains close or open (HGM4020 series); this button can control gen close (HGM4010 series). |
| Down arrow icon | Down/Decrease | Scrolls the screen down; shifts the cursor down or decreases the set value in parameter setting menu. In C/O interface under manual mode, this button can control gen close or open (HGM4020 series); this button can control gen open (HGM4010 series). |

5.1 Parameter Setting
Parameters can be adjusted directly from the controller's front panel using the navigation buttons and the Set/Confirm button. For more comprehensive configuration, connect the controller to a PC via the USB or RS485 interface and use the dedicated software. All settings are stored in internal FLASH memory and are retained even during power outages.
6. Maintenance
The HGM4010N controller includes a maintenance function to help manage the genset's service schedule. Maintenance types can be configured based on date or running time. When the set maintenance interval is exceeded, the controller can trigger various actions:
- Warning: An alert will be displayed or logged.
- Shutdown: The genset will be safely shut down.
- Trip and Stop: The genset will be tripped and stopped.
Regular visual inspection of the controller and its connections is recommended. Ensure the panel fascia and buttons are clean and free from debris. The IP55 protection level ensures resistance against dust and water splashes, but avoid direct high-pressure water jets.
7. Troubleshooting
The controller provides comprehensive alarm protection and fault indication functions. In case of an issue, the LCD display will show relevant alarm messages. Refer to the specific alarm codes and their meanings in the full product manual (if available) for detailed troubleshooting steps.
- Alarm Reset: Press the Stop/Reset button to clear active alarms after addressing the underlying issue.
- Event Log: The controller stores up to 99 event logs. Access this log through the menu to review past alarms and operational events, which can assist in diagnosing intermittent problems.
- Common Issues:
- Genset fails to start: Check fuel level, battery voltage, and crank disconnect conditions. Verify all wiring connections are secure.
- Incorrect readings: Ensure sensors are correctly installed and calibrated. Check for loose sensor connections.
- Communication errors (RS485/CANBUS): Verify cable integrity and proper termination. Check communication settings on both the controller and the connected PC/ECU.
If an issue persists, consult a qualified technician or contact customer support.
8. User Tips
No specific user tips were available from reviews or Q&A content. However, general best practices for generator controllers include:
- Regular Checks: Periodically check all wiring connections for tightness and signs of wear.
- Firmware Updates: If available, keep the controller's firmware updated to ensure optimal performance and access to new features.
- Environmental Protection: While rated IP55, avoid exposing the controller to direct sunlight for prolonged periods or extreme moisture to maximize its lifespan.
- Backup Settings: Before making significant parameter changes, consider backing up your current configuration if the software allows.
9. Warranty and Support
The SmartGen HGM4010N controller comes with a 1-year warranty from the date of purchase.
For technical support, troubleshooting assistance, or warranty claims, please contact the manufacturer or your authorized distributor. When contacting support, please have your product model number (HGM4010N) and purchase details ready.
Manufacturer: HIWELL Generator Parts Factory Store
10. Product Visuals
10.1 Unboxing Video
Watch this video for an unboxing experience of the SmartGen HGM4010N controller.
10.2 Product Images
Below are additional images of the SmartGen HGM4010N controller for visual reference.



