ZL-7830A Humidity Controller Instruction Manual

Model: ZL-7830A | Brand: Lilytech

1. Introduction

The Lilytech ZL-7830A is a high-performance humidity controller designed for precise humidity management. Featuring a 30A output relay and a compact design with an IP65-rated front panel, it offers convenient operation and easy installation. This manual provides detailed instructions for the safe and effective use of your ZL-7830A humidity controller.

Lilytech ZL-7830A Humidity Controller with sensor
Figure 1: ZL-7830A Humidity Controller with its sensor.

2. Safety Information

  • Always disconnect power before installation, wiring, or maintenance.
  • Ensure all wiring is performed by a qualified electrician and complies with local electrical codes.
  • Do not expose the rear side of the controller to the controlled room to prevent dew formation on the PCB.
  • Operate the device within the specified environmental conditions (-20 to 45°C, 5 to 85% RH without dew).
  • Do not attempt to repair or modify the device yourself. Contact support for assistance.

3. Package Contents

Upon unpacking, please verify that all items are present and undamaged:

  • 1 x ZL-7830A Humidity Controller
  • 1 x Humidity Sensor (wire length 2 meters)
Product packaging box for ZL-7830A
Figure 2: Example of product packaging.

4. Setup and Installation

4.1 Physical Installation

The ZL-7830A is designed for panel mounting. Prepare an opening in your control panel with the following dimensions:

  • Drilling Template: 71 mm (Width) x 29 mm (Height)

Insert the controller into the opening and secure it using the provided mounting clips.

4.2 Wiring Diagram

Refer to the wiring diagram below for proper connection of power, load, and sensor. Ensure all connections are secure and correct before applying power.

Wiring diagram for ZL-7830A Humidity Controller
Figure 3: ZL-7830A Wiring Diagram.

Terminal Connections:

  • Terminals 1 & 2 (R1 COM): Relay output for humidity control (30A/250Vac). Connect your humidifying or dehumidifying device here.
  • Terminals 3 & 4 (L N): Power supply input (100-240Vac, 50/60Hz). Connect Live (L) and Neutral (N) wires.
  • Terminals 5, 6, 7, 8 (O B R Y): Humidity/Temperature Sensor input. Connect the sensor wires according to their color codes (Orange, Blue, Red, Yellow) to the corresponding terminals.

5. Operating Instructions

5.1 Product Version Check

After power is supplied, the display will briefly show all contents, including the model (7830), the software version (e.g., 4.0), and the sensor selection (e.g., 05 or 03).

5.2 Key Functions and Display

The controller features four buttons: P (Program), ▲ (Up), S (Set), and ▼ (Down).

When there is no key operation for 30 seconds, the display will dim to save power.

Display Icons and Their Meanings:

IconFunctionOnBlinking
Humidity load(R1)EnergizedWithin delay protection time (see U12 below)
Humidify modeHumidify modeSetting set-point
De-humidify modeDe-humidify modeSetting set-point
Alarm---Alarming
Display temperatureDisplaying temperature---
Display humidityDisplaying humidity---
E1Fault code---Sensor failure
E2Fault code---Over humidity up limit
E3Fault code---Over humidity low limit
UNLHintWill restore to factory default settings---

5.3 Setting the Set-Point

  1. Press and hold the S button for 3 seconds. The display will show the current set-point.
  2. Press the ▲ or ▼ button to adjust the value. Keeping the button pressed will change the value faster.
  3. Press the S button again to exit the setting. The new set-point will be saved.
  4. If there is no key operation for 30 seconds, the controller will exit the setting mode, and the new value will not be saved.

The factory default set-point is 50% RH.

5.4 Setting Parameters

  1. Press and hold the P button for 3 seconds.
  2. If the code displayed is not "0000", the display will show "----0".
  3. Press the ▲ or ▼ button to set the digit of the password.
  4. Press the P button to confirm. If the password is correct, you will enter the parameter status. Otherwise, it will exit.
  5. If the code is "0000", then the password is not necessary, and you will enter the parameter status directly.

At Parameter Set Status:

  1. Press the ▲ or ▼ button to select the parameter code (e.g., U10, U11).
  2. Press the P button to view or set the value of the selected code.
  3. Press the ▲ or ▼ button to adjust the value.
  4. Press the S button to return to the parameter code selection.
  5. To exit and save all settings, press and hold the P button for 3 seconds. If there is no key operation for 30 seconds, the controller will exit without saving.

5.5 Parameter Table

CodeFunctionRangeRemarkDefault
U10Humidity / de-humidifyH/PH: humidity, P: de-humidityP
U11Hysteresis0.1 ~ 20.0%RH5
U12R1 delay protection0 ~ 30 min0
U13Humidity calibration-9.9 ~ +9.9%RH0
U14Humidity up limit0 ~ 100%RH100
U15Humidity low limit0 ~ 100%RH0
U16Over limit alarm delay0 ~ 600 sec30
U17Display option0 ~ 10: Always display humidity value
1: Display humidity and temperature alternatively
0
U18Warning option0 ~ 30: Up limit warning, low limit no warning
1: Up limit no warning, low limit warning
2: Up limit no warning, low limit no warning
3: Up limit no warning, low limit no warning
0

6. Maintenance

  • Clean the front panel with a soft, damp cloth. Do not use abrasive cleaners or solvents.
  • Ensure the humidity sensor is kept clean and free from dust or debris for accurate readings.
  • Regularly check wiring connections for tightness and signs of wear.
  • No user-serviceable parts inside. For repairs, contact qualified service personnel.

7. Troubleshooting

The ZL-7830A controller displays error codes to indicate specific issues:

CodeDescriptionPossible Cause / Solution
E1Sensor failureCheck sensor wiring connections. Ensure the sensor is not damaged. Replace sensor if necessary.
E2Over humidity up limitThe measured humidity exceeds the upper limit set in parameter U14. Check environmental conditions or adjust U14.
E3Over humidity low limitThe measured humidity is below the lower limit set in parameter U15. Check environmental conditions or adjust U15.
UNLHint: Will restore to factory default settingsThis indicates a system reset or a prompt to restore default settings. Confirm if this action is intended.

8. Specifications

ModelZL-7830A
FunctionHumidify / De-humidify
Power Supply100-240Vac, 50/60Hz
Input Signal1 x Humidity Sensor (wire length 2 meters)
Output LoadR1: 30A/250Vac (resistive load)
Humidity Set Range0 ~ 100.0% RH
Humidity Resolution0.1% RH
Working Environment-20 ~ 45°C, 5 ~ 85% RH (without dew)
Device Dimensions (L x W x D)78 mm x 34.5 mm x 71 mm
Drilling Size (L x W)71 mm x 29 mm
Case MaterialsPC + ABS (fireproof)
Protection LevelIP65 (front panel)

8.1 Sensor Accuracy

Table showing accuracy and range for ZL-SH03A, ZL-SHr05A, ZL-SHr05B sensors
Figure 4: Sensor Accuracy and Range for various sensor types.
SensorAccuracyRange
TypicalMaximal
ZL-SH03A3.5%RH5%RH20 ~ 80%RH
5%RH8%RH<20%RH, >80%RH
ZL-SHr05A2.5%RH5%RH10 ~ 90%RH
4.5%RH8%RH<10%RH, >90%RH
ZL-SHr05B2.5%RH3%RH0 ~ 90%RH
2.5%RH4%RH>90%RH

9. User Tips

  • Upon receiving your ZL-7830A, it is recommended to test its functionality promptly.
  • Should you encounter any issues or require product changes, contact the seller's support. They are noted for providing excellent service in these areas.

10. Warranty and Support