1. Product Overview
The YHDC SCT010T-D is a split core current transformer designed for non-invasive current measurement. It provides galvanic separation between the primary AC current circuit and the secondary 0-5V DC output circuit, ensuring safety and accuracy.

Key Features:
- Small and easy to open design.
- Galvanic separation for safety.
- Easy installation without disturbing main cables.
- Safety lock buckle.
- Built-in rectifier with screw terminal output.
2. Applications
This current transformer is suitable for various applications, including:
- Remote control of current measurement in distributed PLC for SCADA systems.
- Monitoring load trends of critical motors (e.g., compressors, fuel pumps) and other loads up to 150A.
- Connecting to power consumption submeters for energy monitoring.

3. Specifications
Technical Index:
- Mounting Type: Free hanging (In-Line)
- Core Material: Ferrite
- Applicable Standards: GB20840-2014
- Operating Temperature: -25ºC to +60ºC
- Storage Temperature: -30ºC to +90ºC
- Frequency Range: 50Hz-1KHz
- Waterproof Grade: IP00
- Dielectric Strength:
- Input (bare conductor)/Output: AC 800V/1min 50Hz
- Output/Housing: AC 3.5KV/1min 50Hz
Detailed Product Parameters:
| Parameter | Value |
|---|---|
| Model | SCT010T-D |
| Rated Input Current | 0-100A |
| Rated Output | 0-5V |
| Ratio | 100A/5V |
| Accuracy | ±1% |
| Linearity | ≤0.2% |
| Phase Error | ≤1° |
| Insulation Voltage | 3000V |
| Flame Retardant Rating | UL94-V0 |
| Weight | 50g |
| Opening Size | 10mm |
| Lead Length | 1m |
| Output Mode | Screw terminal |
| Output Wire | 0.5mm² |
| Max Primary Current | 150A |
| Max Primary Voltage | 600V |
| Max Primary Conductor Size | 10mm |


4. Setup and Installation
The SCT010T-D current transformer features a split-core design for easy installation without interrupting the primary circuit.
Installation Steps:
- Ensure the power to the primary conductor is disconnected before installation for safety.
- Open the current transformer by pressing the safety lock buckle.
- Place the primary conductor (the wire carrying the current to be measured) through the 10mm opening of the transformer.
- Close the current transformer, ensuring the safety lock buckle is securely fastened.
- Connect the output wires from the screw terminals to your monitoring or protection device. Refer to the wiring diagram for correct polarity.


5. Operating Instructions
Once installed and connected, the SCT010T-D will convert the AC current in the primary conductor into a proportional 0-5V DC output signal. This signal can then be read by a PLC, data logger, or other monitoring equipment.
Wiring Diagram:

Ensure that the monitoring device is configured to accept a 0-5V DC input and is calibrated according to the transformer's ratio (100A/5V).
6. Maintenance
The YHDC SCT010T-D current transformer is designed for long-term, maintenance-free operation. However, periodic checks are recommended:
- Visual Inspection: Periodically inspect the transformer for any signs of physical damage, such as cracks in the housing or damage to the output wires.
- Connection Integrity: Ensure that the screw terminal connections remain tight and free from corrosion.
- Environmental Conditions: Verify that the operating environment remains within the specified temperature range (-25ºC to +60ºC) and that the IP00 waterproof grade is respected (avoid direct exposure to water).
- Cleaning: If necessary, gently clean the exterior of the transformer with a dry, soft cloth. Do not use abrasive cleaners or solvents.
7. Troubleshooting
If you encounter issues with your SCT010T-D current transformer, consider the following:
| Problem | Possible Cause | Solution |
|---|---|---|
| No output signal or incorrect reading |
|
|
| Inaccurate readings |
|
|
| Transformer not closing properly |
|
|
8. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your vendor or the manufacturer directly. Ensure you have your product model (SCT010T-D) and purchase details available.
The product is certified with CE, indicating compliance with health, safety, and environmental protection standards for products sold within the European Economic Area.