SmartGen HEM8500 CAN Monitor User Manual

Model: HEM8500

1. Introduction

The SmartGen HEM8500 is an advanced CAN monitor designed for engine management systems. It features a 4.3-inch LCD display, CANBUS, and RS485 communication capabilities, operating within a DC(10-35)V power supply range. This manual provides detailed instructions for the installation, operation, and maintenance of your HEM8500 monitor.

SmartGen HEM8500 CAN Monitor Front View
Figure 1: Front view of the HEM8500 CAN Monitor.
SmartGen HEM8500 CAN Monitor Rear View with Connectors
Figure 2: Rear view of the HEM8500 CAN Monitor showing connector ports.

2. Specifications

  • Model Number: HEM8500
  • Brand Name: SmartGen
  • Display: 4.3-inch LCD
  • Communication: CANBUS, RS485
  • Working Power Supply: DC(10-35)V
  • Origin: Mainland China
  • High-concerned chemical: None

2.1 Overall Dimensions and Panel Cutout

The HEM8500 controller is suitable for a wide range of battery voltages from DC 10-35V. The negative terminal of the battery must be connected to the engine's shell. The wire diameter for the battery's positive and negative connections to the controller's B+ and B- power inputs must exceed 2.5mm².

If a floating charger is configured, first connect the charger's output wires directly to the battery's positive and negative terminals. Then, connect individual wires from the battery's positive and negative terminals to the controller's positive and negative input ports to prevent the charger from interfering with the controller's normal operation.

HEM8500 Overall Dimension and Panel Cutout Diagram
Figure 3: Overall dimensions and panel cutout for HEM8500.

3. Installation

3.1 Installation Method

  1. The module is secured into the panel fascia using the supplied fixing bolts.
  2. Use 4 pieces of M4 screws and nuts, fixed on the 4 corresponding screw holes.
  3. Care should be taken not to overtighten the fixing screws.

3.2 Output and Expand Relays

All controller outputs are relay contact output type. If relay expansion is required, add a freewheel diode to both ends of the expand relay's coils (for DC current coils) or increase the resistance-capacitance return circuit (for AC current coils). This prevents disturbance to the controller or other equipment.

3.3 Withstand Voltage Test

If a high voltage test is required after the controller has been installed in the control panel, disconnect all terminal connections of the controller. This prevents high voltage from entering and damaging the controller.

4. Operation

4.1 Key Function Description

HEM8500 Front Panel with Labeled Controls
Figure 4: HEM8500 Front Panel with labeled controls.
Table of Key Functions and Indicator Descriptions
Figure 5: Key Function and Indicator Descriptions.

Table 4: Key Function Description

IconsKeysDescription
StopStop the running engine; reset shutdown alarms when engine alarms occur.
StartStart engine in standby status.
PowerIn standby status, press longer to turn off the power; in power off status, press longer to turn on the power.
Engine DiagIt can put the controller in diagnostic mode, and its indicator lights up. Press it again and it exits diagnostic mode, and its indicator lights off.
Paging UpIn Diagnostic mode, if multiple ECU alarms occur, it can check the flashing status of the last alarm.
Paging DownIn Diagnostic mode, if multiple ECU alarms occur, it can check the flashing status of the next alarm.
Manual ThrottleAfter the engine starts, it can put the engine in manual throttle mode, its indicator lights up, and speed can be adjusted by throttle knob. Press it again and engine exits manual throttle mode, its indicator lights off, and speed cannot be adjusted at this moment.
Subtotal ZeroPress it for 3s and "subtotal time", "subtotal fuel consumption" and "subtotal avg. fuel consumption" become "0".
Home/SetIn Main menu page, it can enter parameter setting interface; in other pages, it can make it faster to return the main menu page.
Up/Increase1) Screen scroll; 2) Move up cursor and increase value in setting menu.
Down/Decrease1) Screen scroll; 2) Move down cursor and decrease value in setting menu.
ThrottleIn manual throttle mode, forward/backward rotate this knob to increase/decrease target speed. Press the knob and it can return to "Idle Speed".
E-StopPress it, start output and ECU power will be disconnected and meanwhile stop process will be executed.

Table 5: Indicator Description

IndicatorsDescription
Engine shutdown alarm indicationWhen diagnostic mode is active, if ECU alarms occur, users can check corresponding fault alarm information through flicker times of this indicator. Or when E-stop button is pressed, engine stop indicator flashes quickly (engine red light).
Engine warning alarm indicationWhen controller detects warning alarm signals, this indicator flashes (engine yellow light).
Engine preheating indicationWhen engine preheat starts, ECU initiates corresponding preheating command.
Charging indicationAfter charging indication input accessing to the controller, when charge, it will light off, otherwise it will light on.

4.2 LCD Display and Main Display

When system power is connected (controller has no power), press the power key for more than 2 seconds to power up. After entering the boot password, the controller will enter the normal running interface.

The initial boot password is 000, which can be changed in the password setting page of the module setting interface.

To enter the boot password: Use the Up/Increase keys to choose numbers, and the Home/Set key to set the next number. Press the Home/Set key after three password numbers are entered to access the normal display interface.

The interface display is divided into multiple pages: Main Screen Display, Engine Data Display, Alarm Data display, Event Log Data Display, and Other information display.

HEM8500 LCD Main Display and Start Interface
Figure 6: HEM8500 LCD Main Display and Start Interface.

Table 6: Display Content Description

Main Screen Display ContentDescriptionData Sources
SpeedEngine fuel level indicationFuel level sensor data
TorqueEngine running speedECU data analysis
Coolant TempEngine TorqueECU data analysis
Oil PressureEngine coolant temp displayECU data analysis
Battery VoltageEngine oil pressure displayECU data analysis
Instant. FCSystem power supply voltageController gathered battery voltage
Accum. FCEngine instant fuel consumptionECU data analysis
Fuel used after engine startEngine total fuel consumptionECU data analysis
Total TimeFC calculation after engine start
Subtotal TimeEngine running time accumulationEngine running time accumulation
At RestTime accum. after engine start
Engine Status
Oil filter running timeRun time after new oil filter changed.
Diesel filter running timeRun time after new diesel filter changed.

Engine Page Display Content

DisplayDescriptionData Sources
Oil Pressure SensorCurrent type sensor
Temp SensorCurrent type sensor
Aux. Sensor 3ECU data analysis
Aux. Sensor 4ECU data analysis
Oil TempECU data analysis
Fuel TempECU data analysis
Fuel PressureECU data analysis
Inlet TempECU data analysis
Outlet TempECU data analysis

4.3 User Menu and Parameter Settings

Press the Home/Set key to enter the user menu.

Parameter Settings

After entering the correct password (factory default password is 00318), you can access the parameter settings interface. Available settings include:

  • Module settings
  • Timer settings
  • Engine settings
  • Sensor settings (flexible sensor 1~2, fuel level sensor setting, flexible sensor 3~4 (current type sensor) settings)
  • Input port settings
  • Output port settings
  • 4~20mA output settings
Table of Parameter Setting Example (Screen 1)
Figure 7: Parameter Setting Example (Screen 1).

Table 7: Parameter Setting Example (Screen 1)

SubmenuScreen 1
ModuleUse Up/Increase to change settings and Home/Set to enter settings.
TimerScreen 2
Engine
Sensor
Inputs
Outputs
4~20mA Output
Return
Pre-heat Delay
Cranking Time
Crank Rest Time
Safety On Time
Cooling Time
ETS Solenoid Hold
Fail to Stop Delay
Power Off Delay

5. Wiring Connection

If CAN 1 requires a 120Ω resistance match, short connect outside CAN(H) and CAN(L) 120Ω, which is short connect B14 and B5.

Table of Terminal Wiring Description for A and B Plugs
Figure 8: Terminal Wiring Description for A and B Plugs (Back Panel).

5.1 A Plug Terminal (Back Panel)

Table 13: A Plug Terminal Wiring Description

No.FunctionsCable SizeRemark
1Ground Loop1.0mm²ECU ground loop
24~20mA Output-1.0mm²4~20mA output negative
3Aux. Input 51.0mm²Discrete input port
4Aux. Input 41.0mm²Discrete input port
5GND1.0mm²GND
6Aux. Input 31.0mm²Discrete input port
7Aux. Input 21.0mm²Discrete input port
8Air Filter Block Alarm Input1.0mm²Air filter block alarm input
9Charging Indicator Input1.0mm²Discrete input port
10Shutdown Indicator Input (red light)1.0mm²Discrete input port
11Warning Indicator Input (yellow light)1.0mm²Discrete input port
12Waiting for Start Indicator Input1.0mm²Discrete input port
13Diagnosis Output1.0mm²Output port control
144~20mA Output+1.0mm²4~20mA output positive
15NC1.0mm²NC
16GND1.0mm²GND
17NC1.0mm²NC
18Aux. Sensor 3 Input (4~20mA)1.0mm²Analog input port
19Aux. Sensor 4 Input (4~20mA)1.0mm²Analog input port
20Aux. Input 11.0mm²Discrete input port
21Low Water Level Warning1.0mm²Low water level input port
22GND1.0mm²GND
23Aux. Sensor 2 Input1.0mm²Analog input port
24Diagnosis Output1.0mm²Output after diagnosis is active
25Diagnosis Paging Down Output1.0mm²Diagnosis paging down output
26NC1.0mm²NC
27RS485 (B)0.5mm²RS485 (B)
28RS485 (A)0.5mm²RS485 (A)
29RS485 120Ω0.5mm²RS485 (SCR)
30NC1.0mm²NC
3132/33 Relay Output COM1.5mm²32/33 relay output common port
32Aux. Output 11.5mm²Output port control, the max contact capacity is 7A
33Aux. Output 21.5mm²Output port control, the max contact capacity is 7A
34Fuel Level Sensor Input1.0mm²Analog input port
35Aux. Sensor 1 Input1.0mm²Analog input port

5.2 B Plug Terminal (Back Panel)

Table 13: B Plug Terminal Wiring Description (Continued)

No.FunctionsCable SizeRemark
1Crank1.5mm²Connecting with starting output capacity 1.6A
2CAN2 120Ω0.5mm²Standby CANBUS
3CAN2 (L)0.5mm²Standby CANBUS
4CAN2 (H)0.5mm²Standby CANBUS
5CAN1 120Ω0.5mm²Engine J1939 CANBUS
6Crank1.5mm²Connecting with starting output capacity 1.6A
7B+1.5mm²Working power supply DC B+
8B-1.5mm²Working power supply DC B-
9CAN1(L)0.5mm²Engine J1939 CANBUS
10ECU Power1.5mm²Connecting with ECU power output capacity 1.6A
11ECU Power1.5mm²Connecting with ECU power output capacity 1.6A
12B+1.5mm²Working power supply DC B+
13B-1.5mm²Working power supply DC B-
14CAN1 (H)0.5mm²Engine J1939 CANBUS

5.3 Connections for J1939 Engines

Tables for J1939 Engine Connector Details
Figure 9: J1939 Engine Connector Details.

5.3.1 CUMMINS QSL9

Suitable for CM850 engine control module.

Table 23: 50-Pin Connector
Terminals of controller50 pins connectorRemark
ECU Power39Connected to starter coil directly.
Starting Relay Output--

5.3.2 CUMMINS QSX15-CM570

Suitable for CM570 engine control module. Engine type is QSX15 etc.

Table 25: 50-Pin Connector
Terminals of controller50 pins connectorRemark
ECU Power38Injection switch.
Starting Relay Output-Connected to starter coil directly.
Table 26: 9-Pin Connector
Terminals of controller9 pins connectorRemark
CAN(H)SAE J1939 shield-ECAN communication shielding line.
CAN(L)SAE J1939 signal-CUsing impedance 120Ω connecting line.
CAN(-)SAE J1939 return-DUsing impedance 120Ω connecting line.

5.3.3 CUMMINS QSM11

Table 27: Engine OEM Connector
Terminals of controllerOEM connector of engineRemark
ECU Power38Connected with starter coil directly.
Starting Relay Output-CAN communication shielding line.
CAN(H)46Using impedance 120Ω connecting line.
CAN(L)37Using impedance 120Ω connecting line.

5.3.4 DETROIT DIESEL DDCC III/IV

Table 28: Engine CAN Port
Terminals of controllerCAN port of engineRemark
ECU PowerExpansion 30A relay, proving battery voltage for ECU.
Starting Relay Output-Connected to starter coil directly.
CAN(H)CAN(H)CAN communication shielding line.
CAN(L)CAN(L)Using impedance 120Ω connecting line.
CAN(-)CAN(-)Using impedance 120Ω connecting line.
HEM8500 Controller Back Panel and Wiring Connection Diagram
Figure 10: HEM8500 Controller Back Panel and Wiring Connection Diagram.
HEM8500 Typical Application Diagram
Figure 11: HEM8500 Typical Application Diagram.

6. Troubleshooting

6.1 Shutdown Alarms

When shutdown alarm inhibition is enabled, for alarms No. 1-9, if shutdown alarms occur, the controller only displays shutdown alarm information but does not control ECU shutdown. If stopping is needed, press the stop button. Alarm No. 10 controls ECU shutdown. When shutdown alarm inhibition is disabled, shutdown alarms will cause the controller to control ECU shutdown.

Table 12: Shutdown Alarms

No.TypeDescription
1ECU ShutdownWhen the controller receives engine shutdown signals via J1939, it will initiate a shutdown alarm signal and display the fault code and name.
2ECU Comm. FailureIf the engine starts but the controller does not receive engine shutdown signals via J1939, it will initiate a shutdown alarm signal.
3Aux. Sensor 1~2 HighAfter sensors are enabled, if the controller detects that the sensor value has exceeded the pre-set upper limit, it will initiate a shutdown alarm signal.
4Aux. Sensor 1~2 LowAfter sensors are enabled, if the controller detects that the sensor value has fallen below the pre-set lower limit, it will initiate a shutdown alarm signal.
5Aux. Sensor 3~4 High Shutdown (current type)After sensors are enabled, if the controller detects a sensor value above the pre-set upper shutdown value, it will initiate a sensor high shutdown alarm signal.
6Aux. Sensor 3~4 Low Shutdown (current type)After sensors are enabled, if the controller detects a sensor value below the pre-set lower shutdown value, it will initiate a sensor low shutdown alarm signal.
7Input 1~5 ShutdownIf a digital input port is configured as "shutdown" and becomes active, it will initiate a shutdown alarm signal.
8High Temp Shutdown (ECU)If the controller detects the ECU temperature is above the pre-set upper shutdown value, it will initiate a high temperature shutdown alarm signal.
9Low OP Shutdown (ECU)If the controller detects oil pressure has fallen below the pre-set lower shutdown value, it will initiate a low oil pressure shutdown alarm signal.
10Emergency StopWhen active, starting output and ECU power will be disconnected, and the stop process will be executed.

7. Maintenance

The HEM8500 is designed for durability and minimal maintenance. Regular checks should include:

  • Ensuring all wiring connections are secure and free from corrosion.
  • Keeping the display screen clean and free from dust or debris.
  • Periodically checking for any visible damage to the unit or its casing.

For detailed maintenance procedures or if you encounter any issues not covered in the troubleshooting section, please refer to the official SmartGen documentation or contact technical support.

8. User Tips

  • Always ensure the power supply is within the specified DC(10-35)V range to prevent damage.
  • Double-check all wiring connections, especially CANBUS and RS485, to ensure proper communication and data accuracy.
  • Familiarize yourself with the key functions and indicator meanings to quickly diagnose and respond to engine conditions.
  • Regularly monitor the main display for critical engine parameters and alarm indications.
  • When configuring parameters, always note down the default password (00318) and any changes you make for future reference.

9. Warranty and Support