1. Introduction
The SmartGen HEM8500 is an advanced CAN monitor designed for engine management systems. It features a 4.3-inch LCD display, CANBUS, and RS485 communication capabilities, operating within a DC(10-35)V power supply range. This manual provides detailed instructions for the installation, operation, and maintenance of your HEM8500 monitor.


2. Specifications
- Model Number: HEM8500
- Brand Name: SmartGen
- Display: 4.3-inch LCD
- Communication: CANBUS, RS485
- Working Power Supply: DC(10-35)V
- Origin: Mainland China
- High-concerned chemical: None
2.1 Overall Dimensions and Panel Cutout
The HEM8500 controller is suitable for a wide range of battery voltages from DC 10-35V. The negative terminal of the battery must be connected to the engine's shell. The wire diameter for the battery's positive and negative connections to the controller's B+ and B- power inputs must exceed 2.5mm².
If a floating charger is configured, first connect the charger's output wires directly to the battery's positive and negative terminals. Then, connect individual wires from the battery's positive and negative terminals to the controller's positive and negative input ports to prevent the charger from interfering with the controller's normal operation.

3. Installation
3.1 Installation Method
- The module is secured into the panel fascia using the supplied fixing bolts.
- Use 4 pieces of M4 screws and nuts, fixed on the 4 corresponding screw holes.
- Care should be taken not to overtighten the fixing screws.
3.2 Output and Expand Relays
All controller outputs are relay contact output type. If relay expansion is required, add a freewheel diode to both ends of the expand relay's coils (for DC current coils) or increase the resistance-capacitance return circuit (for AC current coils). This prevents disturbance to the controller or other equipment.
3.3 Withstand Voltage Test
If a high voltage test is required after the controller has been installed in the control panel, disconnect all terminal connections of the controller. This prevents high voltage from entering and damaging the controller.
4. Operation
4.1 Key Function Description


Table 4: Key Function Description
| Icons | Keys | Description |
|---|---|---|
| Stop | Stop the running engine; reset shutdown alarms when engine alarms occur. | |
| Start | Start engine in standby status. | |
| Power | In standby status, press longer to turn off the power; in power off status, press longer to turn on the power. | |
| Engine Diag | It can put the controller in diagnostic mode, and its indicator lights up. Press it again and it exits diagnostic mode, and its indicator lights off. | |
| Paging Up | In Diagnostic mode, if multiple ECU alarms occur, it can check the flashing status of the last alarm. | |
| Paging Down | In Diagnostic mode, if multiple ECU alarms occur, it can check the flashing status of the next alarm. | |
| Manual Throttle | After the engine starts, it can put the engine in manual throttle mode, its indicator lights up, and speed can be adjusted by throttle knob. Press it again and engine exits manual throttle mode, its indicator lights off, and speed cannot be adjusted at this moment. | |
| Subtotal Zero | Press it for 3s and "subtotal time", "subtotal fuel consumption" and "subtotal avg. fuel consumption" become "0". | |
| Home/Set | In Main menu page, it can enter parameter setting interface; in other pages, it can make it faster to return the main menu page. | |
| Up/Increase | 1) Screen scroll; 2) Move up cursor and increase value in setting menu. | |
| Down/Decrease | 1) Screen scroll; 2) Move down cursor and decrease value in setting menu. | |
| Throttle | In manual throttle mode, forward/backward rotate this knob to increase/decrease target speed. Press the knob and it can return to "Idle Speed". | |
| E-Stop | Press it, start output and ECU power will be disconnected and meanwhile stop process will be executed. |
Table 5: Indicator Description
| Indicators | Description |
|---|---|
| Engine shutdown alarm indication | When diagnostic mode is active, if ECU alarms occur, users can check corresponding fault alarm information through flicker times of this indicator. Or when E-stop button is pressed, engine stop indicator flashes quickly (engine red light). |
| Engine warning alarm indication | When controller detects warning alarm signals, this indicator flashes (engine yellow light). |
| Engine preheating indication | When engine preheat starts, ECU initiates corresponding preheating command. |
| Charging indication | After charging indication input accessing to the controller, when charge, it will light off, otherwise it will light on. |
4.2 LCD Display and Main Display
When system power is connected (controller has no power), press the power key for more than 2 seconds to power up. After entering the boot password, the controller will enter the normal running interface.
The initial boot password is 000, which can be changed in the password setting page of the module setting interface.
To enter the boot password: Use the Up/Increase keys to choose numbers, and the Home/Set key to set the next number. Press the Home/Set key after three password numbers are entered to access the normal display interface.
The interface display is divided into multiple pages: Main Screen Display, Engine Data Display, Alarm Data display, Event Log Data Display, and Other information display.

Table 6: Display Content Description
| Main Screen Display Content | Description | Data Sources |
|---|---|---|
| Speed | Engine fuel level indication | Fuel level sensor data |
| Torque | Engine running speed | ECU data analysis |
| Coolant Temp | Engine Torque | ECU data analysis |
| Oil Pressure | Engine coolant temp display | ECU data analysis |
| Battery Voltage | Engine oil pressure display | ECU data analysis |
| Instant. FC | System power supply voltage | Controller gathered battery voltage |
| Accum. FC | Engine instant fuel consumption | ECU data analysis |
| Fuel used after engine start | Engine total fuel consumption | ECU data analysis |
| Total Time | FC calculation after engine start | |
| Subtotal Time | Engine running time accumulation | Engine running time accumulation |
| At Rest | Time accum. after engine start | |
| Engine Status | ||
| Oil filter running time | Run time after new oil filter changed. | |
| Diesel filter running time | Run time after new diesel filter changed. |
Engine Page Display Content
| Display | Description | Data Sources |
|---|---|---|
| Oil Pressure Sensor | Current type sensor | |
| Temp Sensor | Current type sensor | |
| Aux. Sensor 3 | ECU data analysis | |
| Aux. Sensor 4 | ECU data analysis | |
| Oil Temp | ECU data analysis | |
| Fuel Temp | ECU data analysis | |
| Fuel Pressure | ECU data analysis | |
| Inlet Temp | ECU data analysis | |
| Outlet Temp | ECU data analysis |
4.3 User Menu and Parameter Settings
Press the Home/Set key to enter the user menu.
Parameter Settings
After entering the correct password (factory default password is 00318), you can access the parameter settings interface. Available settings include:
- Module settings
- Timer settings
- Engine settings
- Sensor settings (flexible sensor 1~2, fuel level sensor setting, flexible sensor 3~4 (current type sensor) settings)
- Input port settings
- Output port settings
- 4~20mA output settings

Table 7: Parameter Setting Example (Screen 1)
| Submenu | Screen 1 |
|---|---|
| Module | Use Up/Increase to change settings and Home/Set to enter settings. |
| Timer | Screen 2 |
| Engine | |
| Sensor | |
| Inputs | |
| Outputs | |
| 4~20mA Output | |
| Return | |
| Pre-heat Delay | |
| Cranking Time | |
| Crank Rest Time | |
| Safety On Time | |
| Cooling Time | |
| ETS Solenoid Hold | |
| Fail to Stop Delay | |
| Power Off Delay |
5. Wiring Connection
If CAN 1 requires a 120Ω resistance match, short connect outside CAN(H) and CAN(L) 120Ω, which is short connect B14 and B5.

5.1 A Plug Terminal (Back Panel)
Table 13: A Plug Terminal Wiring Description
| No. | Functions | Cable Size | Remark |
|---|---|---|---|
| 1 | Ground Loop | 1.0mm² | ECU ground loop |
| 2 | 4~20mA Output- | 1.0mm² | 4~20mA output negative |
| 3 | Aux. Input 5 | 1.0mm² | Discrete input port |
| 4 | Aux. Input 4 | 1.0mm² | Discrete input port |
| 5 | GND | 1.0mm² | GND |
| 6 | Aux. Input 3 | 1.0mm² | Discrete input port |
| 7 | Aux. Input 2 | 1.0mm² | Discrete input port |
| 8 | Air Filter Block Alarm Input | 1.0mm² | Air filter block alarm input |
| 9 | Charging Indicator Input | 1.0mm² | Discrete input port |
| 10 | Shutdown Indicator Input (red light) | 1.0mm² | Discrete input port |
| 11 | Warning Indicator Input (yellow light) | 1.0mm² | Discrete input port |
| 12 | Waiting for Start Indicator Input | 1.0mm² | Discrete input port |
| 13 | Diagnosis Output | 1.0mm² | Output port control |
| 14 | 4~20mA Output+ | 1.0mm² | 4~20mA output positive |
| 15 | NC | 1.0mm² | NC |
| 16 | GND | 1.0mm² | GND |
| 17 | NC | 1.0mm² | NC |
| 18 | Aux. Sensor 3 Input (4~20mA) | 1.0mm² | Analog input port |
| 19 | Aux. Sensor 4 Input (4~20mA) | 1.0mm² | Analog input port |
| 20 | Aux. Input 1 | 1.0mm² | Discrete input port |
| 21 | Low Water Level Warning | 1.0mm² | Low water level input port |
| 22 | GND | 1.0mm² | GND |
| 23 | Aux. Sensor 2 Input | 1.0mm² | Analog input port |
| 24 | Diagnosis Output | 1.0mm² | Output after diagnosis is active |
| 25 | Diagnosis Paging Down Output | 1.0mm² | Diagnosis paging down output |
| 26 | NC | 1.0mm² | NC |
| 27 | RS485 (B) | 0.5mm² | RS485 (B) |
| 28 | RS485 (A) | 0.5mm² | RS485 (A) |
| 29 | RS485 120Ω | 0.5mm² | RS485 (SCR) |
| 30 | NC | 1.0mm² | NC |
| 31 | 32/33 Relay Output COM | 1.5mm² | 32/33 relay output common port |
| 32 | Aux. Output 1 | 1.5mm² | Output port control, the max contact capacity is 7A |
| 33 | Aux. Output 2 | 1.5mm² | Output port control, the max contact capacity is 7A |
| 34 | Fuel Level Sensor Input | 1.0mm² | Analog input port |
| 35 | Aux. Sensor 1 Input | 1.0mm² | Analog input port |
5.2 B Plug Terminal (Back Panel)
Table 13: B Plug Terminal Wiring Description (Continued)
| No. | Functions | Cable Size | Remark |
|---|---|---|---|
| 1 | Crank | 1.5mm² | Connecting with starting output capacity 1.6A |
| 2 | CAN2 120Ω | 0.5mm² | Standby CANBUS |
| 3 | CAN2 (L) | 0.5mm² | Standby CANBUS |
| 4 | CAN2 (H) | 0.5mm² | Standby CANBUS |
| 5 | CAN1 120Ω | 0.5mm² | Engine J1939 CANBUS |
| 6 | Crank | 1.5mm² | Connecting with starting output capacity 1.6A |
| 7 | B+ | 1.5mm² | Working power supply DC B+ |
| 8 | B- | 1.5mm² | Working power supply DC B- |
| 9 | CAN1(L) | 0.5mm² | Engine J1939 CANBUS |
| 10 | ECU Power | 1.5mm² | Connecting with ECU power output capacity 1.6A |
| 11 | ECU Power | 1.5mm² | Connecting with ECU power output capacity 1.6A |
| 12 | B+ | 1.5mm² | Working power supply DC B+ |
| 13 | B- | 1.5mm² | Working power supply DC B- |
| 14 | CAN1 (H) | 0.5mm² | Engine J1939 CANBUS |
5.3 Connections for J1939 Engines

5.3.1 CUMMINS QSL9
Suitable for CM850 engine control module.
Table 23: 50-Pin Connector
| Terminals of controller | 50 pins connector | Remark |
|---|---|---|
| ECU Power | 39 | Connected to starter coil directly. |
| Starting Relay Output | - | - |
5.3.2 CUMMINS QSX15-CM570
Suitable for CM570 engine control module. Engine type is QSX15 etc.
Table 25: 50-Pin Connector
| Terminals of controller | 50 pins connector | Remark |
|---|---|---|
| ECU Power | 38 | Injection switch. |
| Starting Relay Output | - | Connected to starter coil directly. |
Table 26: 9-Pin Connector
| Terminals of controller | 9 pins connector | Remark |
|---|---|---|
| CAN(H) | SAE J1939 shield-E | CAN communication shielding line. |
| CAN(L) | SAE J1939 signal-C | Using impedance 120Ω connecting line. |
| CAN(-) | SAE J1939 return-D | Using impedance 120Ω connecting line. |
5.3.3 CUMMINS QSM11
Table 27: Engine OEM Connector
| Terminals of controller | OEM connector of engine | Remark |
|---|---|---|
| ECU Power | 38 | Connected with starter coil directly. |
| Starting Relay Output | - | CAN communication shielding line. |
| CAN(H) | 46 | Using impedance 120Ω connecting line. |
| CAN(L) | 37 | Using impedance 120Ω connecting line. |
5.3.4 DETROIT DIESEL DDCC III/IV
Table 28: Engine CAN Port
| Terminals of controller | CAN port of engine | Remark |
|---|---|---|
| ECU Power | Expansion 30A relay, proving battery voltage for ECU. | |
| Starting Relay Output | - | Connected to starter coil directly. |
| CAN(H) | CAN(H) | CAN communication shielding line. |
| CAN(L) | CAN(L) | Using impedance 120Ω connecting line. |
| CAN(-) | CAN(-) | Using impedance 120Ω connecting line. |


6. Troubleshooting
6.1 Shutdown Alarms
When shutdown alarm inhibition is enabled, for alarms No. 1-9, if shutdown alarms occur, the controller only displays shutdown alarm information but does not control ECU shutdown. If stopping is needed, press the stop button. Alarm No. 10 controls ECU shutdown. When shutdown alarm inhibition is disabled, shutdown alarms will cause the controller to control ECU shutdown.
Table 12: Shutdown Alarms
| No. | Type | Description |
|---|---|---|
| 1 | ECU Shutdown | When the controller receives engine shutdown signals via J1939, it will initiate a shutdown alarm signal and display the fault code and name. |
| 2 | ECU Comm. Failure | If the engine starts but the controller does not receive engine shutdown signals via J1939, it will initiate a shutdown alarm signal. |
| 3 | Aux. Sensor 1~2 High | After sensors are enabled, if the controller detects that the sensor value has exceeded the pre-set upper limit, it will initiate a shutdown alarm signal. |
| 4 | Aux. Sensor 1~2 Low | After sensors are enabled, if the controller detects that the sensor value has fallen below the pre-set lower limit, it will initiate a shutdown alarm signal. |
| 5 | Aux. Sensor 3~4 High Shutdown (current type) | After sensors are enabled, if the controller detects a sensor value above the pre-set upper shutdown value, it will initiate a sensor high shutdown alarm signal. |
| 6 | Aux. Sensor 3~4 Low Shutdown (current type) | After sensors are enabled, if the controller detects a sensor value below the pre-set lower shutdown value, it will initiate a sensor low shutdown alarm signal. |
| 7 | Input 1~5 Shutdown | If a digital input port is configured as "shutdown" and becomes active, it will initiate a shutdown alarm signal. |
| 8 | High Temp Shutdown (ECU) | If the controller detects the ECU temperature is above the pre-set upper shutdown value, it will initiate a high temperature shutdown alarm signal. |
| 9 | Low OP Shutdown (ECU) | If the controller detects oil pressure has fallen below the pre-set lower shutdown value, it will initiate a low oil pressure shutdown alarm signal. |
| 10 | Emergency Stop | When active, starting output and ECU power will be disconnected, and the stop process will be executed. |
7. Maintenance
The HEM8500 is designed for durability and minimal maintenance. Regular checks should include:
- Ensuring all wiring connections are secure and free from corrosion.
- Keeping the display screen clean and free from dust or debris.
- Periodically checking for any visible damage to the unit or its casing.
For detailed maintenance procedures or if you encounter any issues not covered in the troubleshooting section, please refer to the official SmartGen documentation or contact technical support.
8. User Tips
- Always ensure the power supply is within the specified DC(10-35)V range to prevent damage.
- Double-check all wiring connections, especially CANBUS and RS485, to ensure proper communication and data accuracy.
- Familiarize yourself with the key functions and indicator meanings to quickly diagnose and respond to engine conditions.
- Regularly monitor the main display for critical engine parameters and alarm indications.
- When configuring parameters, always note down the default password (00318) and any changes you make for future reference.