1. Introduction
The GEYA G2R-63 Automatic Transfer Switch (ATS) is a PC class infrequent change-over switch designed for AC systems operating at 50-60Hz with a rated current of 6A-63A. It features a two-station design, typically using 'A' as the common power supply and 'B' as the standby power supply. Its primary function is to automatically switch to the backup power supply (B) when the main power (A) fails, ensuring uninterrupted power (switching speed <50 milliseconds). This effectively mitigates issues caused by power outages. When both power sources A and B are available, priority is given to using power source A.
This manual provides essential information for the safe and efficient installation, operation, and maintenance of your GEYA G2R ATS.
2. Safety Information
- Installation and maintenance should only be performed by qualified personnel.
- Ensure all power sources are disconnected before installation or maintenance to prevent electric shock.
- Verify correct phase sequence connection, especially for 4P ATS models, to prevent contact damage.
- Do not use 220V ATS with voltages lower than 185V, or 110V ATS with voltages lower than 90V, as this may cause the coil to overheat and burn out.
- Never manually switch the device when it is in automatic mode and powered, as this can damage the coil.
3. Product Overview
The GEYA G2R ATS is available in 2P (2-pole) and 4P (4-pole) configurations, supporting various rated currents including 25A, 40A, and 63A. It is designed for DIN rail mounting.

Figure 1: GEYA G2R Dual Power Automatic Transfer Switch (2P and 4P models)

Figure 2: Front view of GEYA G2R 2P ATS

Figure 3: Front view of GEYA G2R 4P ATS
4. Specifications
| Parameter | Value |
|---|---|
| Rated operating current Ie(A) | 06A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A |
| Rated insulation voltage Ui | 690V |
| Rated impulse withstand voltage Uimp | 8kV |
| Rated working voltage Ue | AC220V/AC110V |
| Rated frequency | 50/60Hz |
| Class | PC class: can be switched on and loaded without generating short-circuit current |
| Pole number | 2P, 4P |
| Rated short-circuit current Iq | 5kA |
| Short circuit protection device (fuse) | RT16-00-63A |
| Rated impulse withstand voltage | 8kV |
| Control circuit | Rated control voltage Us AC220V/110V, 50/60Hz Normal working conditions 85%-110%Us |
| Auxiliary circuit | AC220V/110V 50/60Hz Ie=5A |
| Overvoltage/Undervoltage protection range | 220V/50Hz undervoltage value: 175V, Recovery value: 195V (±5V), Overvoltage value: 260V, Recovery value: 240V (±5V) 110V/50Hz undervoltage value: 85V, Recovery value: 95V (±5V), Overvoltage value: 145V, Recovery value: 130V (±5V) |
| Mechanical life | ≥8000 times |
| Electrical life | ≥1500 times |
| Usage category | AC-31B |

Figure 4: Detailed Technical Specifications

Figure 5: Product Dimensions (2P: 108mm x 50.5mm x 78mm, 4P: 108mm x 82.5mm x 78mm)

Figure 6: Voltage Protection Details
5. Installation and Setup
5.1 Mounting
The GEYA G2R ATS is designed for DIN rail mounting. Ensure the DIN rail is securely fastened and the switch clicks firmly into place.
5.2 Wiring Instructions
Carefully follow the wiring diagrams below for your specific 2P or 4P model. Ensure all connections are tight and secure. The input power supply must be connected in the correct phase sequence.

Figure 7: Wiring Diagram for 2P ATS (Common Power Supply, Backup Power Supply, Load)

Figure 8: Wiring Diagram for 4P ATS (Common Power Supply, Backup Power Supply, Load)
5.3 Installation and Operation Video
Watch this video for a visual guide on wiring and operation:
Video 1: Wiring example and operation demonstration of GEYA G2R ATS.
6. Operation
6.1 Automatic Mode
In automatic mode, the ATS will continuously monitor both power sources. If the primary power source (A) fails, the switch will automatically transfer the load to the backup power source (B) within 50 milliseconds. When power is restored to source A, the switch will automatically revert to source A.
6.2 Manual Mode
For inspection and maintenance, the device can be operated manually. To do so, first ensure all power has been cut off. Then, shift the mode selection switch to the "Manual" position. You can then manually operate the switch. After manual operation is complete, always return the selector switch to the "Auto" position for normal operation.
Important: Do not attempt to manually switch the device when it is in automatic mode and power is supplied to either source. This can cause severe damage to the internal coil and the unit.
7. Maintenance
The GEYA G2R ATS is designed for minimal maintenance. Periodically inspect the wiring connections for tightness and signs of wear or corrosion. Ensure the area around the switch is clean and free from obstructions to allow for proper ventilation.
If the device needs to be manually operated for maintenance, always follow the safety precautions outlined in Section 6.2.
8. Troubleshooting
- Device not switching or coil burning out: Check the input voltage. Ensure 220V ATS is used with at least 185V, and 110V ATS with at least 90V. Lower voltages can cause coil damage.
- Contacts burning out (4P models): Verify that the phase sequence is correctly connected as per the wiring diagrams. Incorrect phase sequence can lead to contact damage.
- Manual operation issues: Ensure the mode selection switch is in the "Manual" position before attempting any manual operation. Operating manually while in "Auto" mode can damage the device.
- No power transfer: Check both primary and backup power sources for availability. Ensure all circuit breakers upstream are in the ON position.
9. User Tips
- Off-Grid Photovoltaic Panels: The GEYA G2R ATS can be used with off-grid photovoltaic panels for generator groups, provided the inverter used with the panels is a pure sine wave inverter and has a power output above 2000W to ensure stable operation and prevent damage to the ATS.
- Voltage Monitoring: Pay close attention to the voltage requirements. Consistent undervoltage can lead to premature failure of the ATS.
10. Warranty and Support
For warranty information, technical support, or service inquiries, please contact your authorized GEYA distributor or visit the official GEYA website. Keep your purchase receipt as proof of purchase.