1. Introduction
This manual provides instructions for the installation, operation, and maintenance of the AISET NBE-3000 Series Temperature Controllers. These controllers are designed for precise temperature regulation in various industrial and laboratory applications. Please read this manual thoroughly before installation and operation to ensure safe and efficient use.
2. Safety Precautions
- Ensure the power supply voltage matches the controller's specifications.
- Disconnect power before performing any wiring or maintenance.
- Do not operate the controller in environments with excessive dust, moisture, corrosive gases, or high vibration.
- Only qualified personnel should install and service this device.
- Ensure proper grounding to prevent electric shock.
3. Product Overview and Components
The NBE-3000 series temperature controller features a clear digital display for process value (PV) and set value (SV), along with indicators for output and alarms.

Front Panel Indicators and Buttons:
- PV Display (Red): Shows the current process value (e.g., actual temperature).
- SV Display (Green): Shows the set value (e.g., desired temperature).
- OUT Indicator (Green LED): Illuminates when the control output is active.
- ALM1 Indicator (Red LED): Illuminates when Alarm 1 is active.
- ALM2 Indicator (Red LED): Illuminates when Alarm 2 is active.
- AT Indicator (Green LED): Illuminates when the auto-tuning function is active.
- SET Button: Used to enter parameter setting mode and confirm selections.
- Left Arrow Button: Used to shift cursor position during parameter setting.
- Down Arrow Button: Used to decrease values or navigate menu options.
- Up Arrow Button: Used to increase values or navigate menu options.


Video Overview:
Video 3.1: A brief overview of the NBE-3000 series temperature controller, showcasing its physical appearance and basic display functions.
4. Specifications
| Feature | Specification |
|---|---|
| Model Series | NBE-3421, NBE-3430, NBE-3412, NBE-3410B, NBE-3400G |
| Temperature Range | 0 ~ 400°C |
| Sensor Type | K-type Thermocouple |
| Accuracy | Class 0.5 |
| Power Supply | 100-240VAC, 50Hz, 5VA |
| Certification | CE |
| Origin | Mainland China |
5. Installation and Wiring
Before installation, ensure the power is disconnected. Mount the controller in a suitable panel cutout, ensuring adequate ventilation.
5.1 Wiring Instructions
Refer to the wiring diagram on the back of the unit (Figure 3.3) and the detailed breakdown below:
- Power Input (100-240VAC): Connect your AC power supply to terminals 1 and 2.
- Control Output (OUT): Connect your heating/cooling element or other controlled device to terminals 5 and 6. These are relay contacts.
- Alarm 1 Output (ALM1): Connect your Alarm 1 device to terminals 9 and 10. These are relay contacts.
- Alarm 2 Output (ALM2): Connect your Alarm 2 device to terminals 3 and 4. These are relay contacts.
- Thermocouple Input (TC): Connect your K-type thermocouple to terminals 13 and 14. Ensure correct polarity (+ to 13, - to 14) for accurate readings.
Warning: Incorrect wiring can damage the device and pose a safety hazard. If unsure, consult a qualified electrician.
6. Operating Instructions
6.1 Power On
Once wired correctly, apply power. The PV display will show the current temperature, and the SV display will show the last set temperature.
6.2 Setting the Temperature (SV)
- Press the SET button once. The SV display will start flashing.
- Use the Up and Down arrow buttons to adjust the desired temperature.
- Use the Left arrow button to shift the cursor for faster adjustment of individual digits.
- Press the SET button again to confirm the new SV. The display will stop flashing.
6.3 Auto-Tuning (AT)
Auto-tuning helps the controller optimize its PID parameters for stable and accurate temperature control. This is recommended after initial setup or if the controlled system changes significantly.
- Ensure the system is at a stable temperature, preferably near the desired set value.
- Press and hold the SET button for approximately 3-5 seconds until the parameter menu appears.
- Navigate through the parameters using the Up or Down arrow buttons until you find the auto-tuning parameter (often labeled 'AT' or similar).
- Change the value of the AT parameter to '1' (or 'ON') using the Up arrow button.
- Press SET to initiate auto-tuning. The AT indicator LED will illuminate.
- The controller will cycle the output to determine optimal PID values. This process may take some time, and the temperature will fluctuate.
- Once auto-tuning is complete, the AT indicator LED will turn off, and the controller will resume normal operation with the new parameters.
6.4 Alarm Settings
The controller supports two alarms (ALM1, ALM2). Specific alarm types (e.g., high limit, low limit, deviation) and values are typically configured within the parameter menu. Refer to the full product manual for detailed alarm parameter settings.
7. Maintenance
- Cleaning: Regularly wipe the front panel with a soft, dry cloth. Do not use abrasive cleaners or solvents.
- Inspection: Periodically check wiring connections for tightness and signs of wear or corrosion.
- Ventilation: Ensure the controller's ventilation slots are clear of obstructions to prevent overheating.
- Sensor Check: If temperature readings are erratic, inspect the thermocouple for damage or loose connections.
8. Troubleshooting
| Problem | Possible Cause | Solution |
|---|---|---|
| No display after power on | No power supply; incorrect wiring; internal fault. | Check power connections (terminals 1 & 2). Verify voltage. If wiring is correct, contact support. |
| PV display shows "HHHH" or "LLLL" | Thermocouple open circuit (HHHH) or short circuit/reverse connection (LLLL); temperature out of range. | Check thermocouple wiring (terminals 13 & 14) for breaks or incorrect polarity. Ensure temperature is within 0-400°C. |
| Temperature control is unstable or inaccurate | PID parameters not optimized; sensor issue; external disturbances. | Perform auto-tuning (Section 6.3). Check thermocouple for proper placement and connection. Minimize drafts or sudden temperature changes around the sensor. |
| Output (OUT) indicator not working as expected | Incorrect control mode setting; faulty output relay; wiring issue. | Verify control mode (e.g., PID, ON/OFF) in parameter settings. Check wiring to the controlled device. If still problematic, contact support. |
9. User Tips
- For best control performance, always perform auto-tuning after initial installation or if the heating/cooling system characteristics change.
- Mount the controller away from strong electromagnetic interference sources to ensure stable operation.
- Consider using shielded thermocouple wires in noisy electrical environments.
10. Warranty and Support
This product is manufactured by Shanghai Yatai Instrument Co., Ltd. and carries a standard manufacturer's warranty against defects in materials and workmanship. For warranty claims, technical support, or service inquiries, please contact your local distributor or the manufacturer directly, providing your product model (e.g., NBE-3421) and serial number (if applicable).
Please retain your purchase receipt as proof of purchase for warranty purposes.