User Manual: ELECTESLA ES280 Mini VFD Variable Frequency Drive

Model: ES280

Vector Variable Frequency Drive & Solar Inverter

Front view of the ELECTESLA ES280 Mini VFD

Front view of the ELECTESLA ES280 Mini VFD, showing the control panel and display.

1. Safety Information and Precautions

This guide provides essential information for the safe operation and installation of your Variable Frequency Drive (VFD). Please read carefully before proceeding.

1.1. Electrical Safety

  • Extreme care is required when working with or near the VFD. High voltages can cause severe electrical shock or burns and are potentially lethal.
  • Only authorized and qualified personnel should install and service the VFD.
  • The VFD contains high levels of stored electrical energy in DC bus capacitors even after power is off. These voltages are lethal.
  • Always disconnect the mains power supply using an electrical safety isolation device before accessing internal parts of the VFD.
  • Wait at least 10 minutes after disconnecting power for stored charge in DC bus capacitors to dissipate. Verify DC bus voltage with a VDC meter before proceeding.

1.2. Machine/System Design and Safety of Personnel

  • Installation, commissioning, and maintenance must be performed by personnel with the necessary training and experience.
  • The VFD's electronic "STOP & START" control circuits should not be solely relied upon for personnel safety.
  • A safety risk assessment of the machine or process system using the VFD must be conducted by the user or system integrator.
  • Ensure the complete system is safe and designed according to relevant safety standards.

1.3. Electrical Installation - Safety

  • Electrical shock risk is always present within the VFD and its output cabling.
  • If dynamic brake resistors are fitted, ensure cables from the VFD to these resistors are double insulated, as they carry high DC voltages (typically 300VDC to 650VDC).
  • A mains power supply isolation switch must be fitted to the VFD.

2. Product Overview and Specifications

The ELECTESLA ES280 is an economical mini VFD designed for motor speed control and solar inverter applications. It supports various power ratings and voltage configurations.

2.1. Key Features

  • Wide Voltage Input (AC200-240V / AC380-440V)
  • Easy Operation Removable Panel
  • Independent Cooling Fan
  • MPPT Function for Solar Inverter applications
  • Improved Machine Stability and Reduced Noise
  • Smart Screen Dual Display (Voltage, Current, Frequency)
  • RS485 Modbus Communication
  • Double Analog Input, Analog Output
Diagram illustrating key features and applications of the VFD

Diagram highlighting the key features and various industrial applications of the ELECTESLA ES280 VFD.

2.2. Technical Specifications

ELECTESLA ES280 VFD Specifications
AttributeValue
Brand NameELECTESLA
Model NumberES280
TypeDC/AC Inverters
Input Voltage220V (1ph220-240V or 3ph220-240V or 3ph380V-440V)
Output Voltage220V or 380V (depending on model)
Output Power0.75-7.5KW
Output Frequency0-400Hz
Output TypeTriple
Control ModelV/F control
Size186.5*86*143.5mm (varies by power)
Weight1.5kgs (approximate)
CertificationCE, FCC, RoHS

2.3. Power and Dimension Table

VFD Power, Output Current, and Dimensions
PowerPower SupplyOutput Current (A)Overall Dimension L*W*H (mm)Installation Dimension L*W - Mounting Screw
0.4KWSingle-phase AC 200V-240V 50Hz/60Hz2.1170*79*127160*60.5-M5
0.75KWSingle-phase AC 200V-240V 50Hz/60Hz3.8170*79*127160*60.5-M5
1.5KWSingle-phase AC 200V-240V 50Hz/60Hz7187*86*144173*68-M4
2.2KWSingle-phase AC 200V-240V 50Hz/60Hz9.0187*86*144173*68-M4
3.0KWSingle-phase AC 200V-240V 50Hz/60Hz13216*101*151204*83.5-M4
4.0KWSingle-phase AC 200V-240V 50Hz/60Hz15237*111*168216*88-M5
5.5KWSingle-phase AC 200V-240V 50Hz/60Hz20237*111*168216*88-M5
0.4KWThree-phase AC 200V-240V 50Hz/60Hz2.1170*79*127160*60.5-M5
0.75KWThree-phase AC 200V-240V 50Hz/60Hz3.8170*79*127160*60.5-M5
1.5KWThree-phase AC 200V-240V 50Hz/60Hz7187*86*144173*68-M4
2.2KWThree-phase AC 200V-240V 50Hz/60Hz9.0187*86*144173*68-M4
3.0KWThree-phase AC 200V-240V 50Hz/60Hz13216*101*151204*83.5-M4
4.0KWThree-phase AC 200V-240V 50Hz/60Hz15237*111*168216*88-M5
5.5KWThree-phase AC 200V-240V 50Hz/60Hz20237*111*168216*88-M5
0.4KWThree-phase AC 340V-440V 50Hz/60Hz1.5170*79*127160*60.5-M5
0.75KWThree-phase AC 340V-440V 50Hz/60Hz2.1170*79*127160*60.5-M5
1.5KWThree-phase AC 340V-440V 50Hz/60Hz3.8187*86*144173*68-M4
2.2KWThree-phase AC 340V-440V 50Hz/60Hz5.1187*86*144173*68-M4
3.0KWThree-phase AC 340V-440V 50Hz/60Hz7.1216*101*151204*83.5-M4
4.0KWThree-phase AC 340V-440V 50Hz/60Hz9.0216*101*151204*83.5-M4
5.5KWThree-phase AC 340V-440V 50Hz/60Hz12.6237*111*168216*88-M5
7.5KWThree-phase AC 340V-440V 50Hz/60Hz16.1237*111*168216*88-M5

3. Installation and Wiring

Proper installation and wiring are crucial for the safe and efficient operation of the VFD. Refer to the diagrams and instructions below.

3.1. Wiring Diagram

Wiring diagram for the ELECTESLA ES280 VFD

Detailed wiring diagram showing connections for power input (single-phase or three-phase AC), motor output (U, V, W), control terminals (X1-X5, GND, AVI, ACI, 10V), and relay outputs (TA, TB, TC).

3.2. Terminal Function Instruction

VFD Terminal Functions
TerminalFunctionSetting and Instruction
R, S, TVFD Power InputFor three-phase 220V/380V models, connect to R, S, T terminals. For single-phase 220V models, connect to L, N terminals. An air switch should be used as the over-current protection device.
U, V, WVFD Output to MotorConnect to the electrical machine. To reduce current leakage, the connection wire should not exceed 50 meters.
P+, PBBraking Resistor ConnectionConnect with a braking resistor. Choose an appropriate resistor from the braking resistor selection table.
PEGround ConnectionThe VFD must be properly grounded.
X1, X2, X3, X4/485+, X5/485-Digital InputsConfigurable for various functions like FWD, REV, multistage speed, RS485 communication, etc. Refer to parameters F5.02-F5.06.
GNDSignal Public TerminalZero potential for analog input signals.
AVI0-10V Signal InputInput resistance: >50KΩ. Can be connected to a potentiometer.
10VFrequency Setting Potentiometer Power Source+10V, maximum 10mA.
ACI0-20mA Analog InputInput resistance: 100Ω.
AOAnalog OutputSet according to parameter F6.10.
TA, TB, TCRelay OutputContact rating: AC 250V/3A, DC 24V/2A. Set according to parameter F5.07.

4. Operating Panel

The VFD features an intuitive keyboard panel for easy operation and parameter setting.

4.1. Keyboard Panel Layout

VFD with detachable keypad showing the control panel

The ELECTESLA ES280 VFD with its detachable keypad, illustrating the control buttons and digital display.

Keyboard Panel Functions
ItemSymbolFunction
Digital tube display8.8.8.8.Displays frequency, parameters, etc.
Parameter setting keyPRGUsed to read/modify parameter groups or display parameter values.
Enter keyENTEREnters the next level menu, confirms settings.
Increment▲Increases parameter number or set value.
Decrement▼Reduces parameter number or set value.
RUNRUNStarts the VFD in operating panel control mode.
STOPSTOPStops the VFD when running. Resets VFD in FAULT status.
Speed control knobDialAdjusts frequency.
Multifunction keysFUNCDefault for VFD jog operation.
Shift keys►Switches display units (units, tens, hundreds, thousands). Changes modification bit in programming state.

To return to the original interface after setting parameters:

  1. Power off, then power on again.
  2. Press the PRG button two or three times.

4.2. Basic Operation of Panel

The panel displays output frequency and current. Use the Shift keys to navigate between digits for precise adjustments.

4.3. VFD Running Command Mode Setting

The VFD operation command mode is set by parameter F0.02. There are three types:

  1. Panel control start and stop (F0.02=0): Press the green RUN button to start (default forward rotation) and the red STOP button to stop. Forward/reverse rotation can be set via input terminals X1-X5.
  2. Terminal start/stop (F0.02=1): Control the VFD using external terminals.
    • Two-wire control mode: Connect X1 to GND for forward run, X2 to GND for reverse run.
    • Three-wire control mode: Connect X1 to GND for forward run, X2 to GND for reverse run, X3 to GND for disconnect stop.
  3. Communication control start/stop: Control via communication protocols (e.g., RS485).

4.4. VFD Frequency Setting Method Selection

The VFD frequency setting mode is configured via parameter F0.03:

  • F0.03=4: Frequency set by potentiometer on the panel.
  • F0.03=2: Frequency input via AVI (0-10V, e.g., external potentiometer).
  • F0.03=3: Frequency input via ACI (0-20mA).
  • F0.03=1: Frequency controlled by external terminal (digital value for increase/decrease).

5. Function Parameter Specifications

The VFD offers a wide range of configurable parameters organized into groups (F0, F1, F2, F3, F4, F5, F6, F7, F8, F9, FA, FB, FC). These parameters allow fine-tuning of the VFD's behavior for specific applications. Below are examples of key parameter groups. For a complete list and detailed descriptions, please refer to the full PDF user manual: User Manual (PDF).

5.1. F0 Group: Basic Running Parameters

This group covers fundamental operational settings.

  • F0.00 VF Power: Displays the current power of the VFD.
  • F0.01 Control Mode: Selects between V/F Control (0) and SVC mode (1).
  • F0.02 Running order channel selection: Determines how the VFD receives start/stop commands (Keyboard, Terminal, Communication).
  • F0.03 Frequency given source channel A: Sets the primary source for frequency command (e.g., potentiometer, AVI, ACI, digital setting).
  • F0.08 Max frequency output: Defines the highest frequency the inverter can output (0-400Hz).

5.2. F1 Group: V/F Control Parameters

Settings related to Voltage/Frequency control characteristics.

  • F1.00 V/F curve set: Selects the V/F curve type (e.g., Beeline, square curve, custom).
  • F1.01 Torque boost: Adjusts low frequency torque compensation.

5.3. F2 Group: Vector Control Parameters

Parameters for advanced vector control, if applicable.

5.4. F3 Group: Auxiliary Operation Parameters

Settings for start-up, braking, and other auxiliary functions.

  • F3.00 Start-up mode: Defines how the VFD starts (e.g., start frequency, DC brake + start frequency).
  • F3.05 Stop mode: Configures how the VFD stops (e.g., decelerate stop, free stop).

5.5. F5 Group: Digital Input and Output Parameters

Configuration for digital input terminals (X1-X5) and relay outputs.

5.6. F6 Group: Analog Input and Output Parameters

Settings for analog input (AVI, ACI) and analog output (AO).

5.7. F7 Group: PLC, Multi-speed Parameters

Parameters for multi-speed operation and PLC functions.

5.8. F8 Group: PID Control, MPPT And PV Pump Parameters

Settings for PID control, Maximum Power Point Tracking (MPPT), and specific parameters for PV pump applications, including water shortage detection.

5.9. F9 Group: Motor Parameters

Motor-specific parameters for optimal VFD performance.

5.10. FA Group: Protect Parameters

Various protection settings for the VFD and motor, including overload, overvoltage, and undervoltage protection.

5.11. FB Group: Display And Special Parameters

Settings related to display monitoring and other special functions.

5.12. FC Group: Communication Control Function Parameter

Parameters for RS485 communication settings, including baud rate and Modbus data format.

6. Troubleshooting

This section provides common fault codes, their possible reasons, and recommended troubleshooting steps. For a comprehensive list of fault codes and detailed solutions, refer to the full user manual.

Common Fault Codes and Troubleshooting
Fault CodeFault DescriptionPossible ReasonsTroubleshooting
OU1(1)Over voltage in Acc processAbnormal supply voltage, VFD restarted with rotating motorCheck power supply, start after setting as DC braking or rotational.
OU1(2)Over voltage in Dec processToo short Dec time, abnormal supply voltageProlong Dec time, check power supply.
OCC1(4)Hardware Over-current in Acc processToo short Acc time, VFD power too small, V/F curve not suitable, IGBT module damagedProlong Acc time, select higher power drive, adjust V/F curve or torque boost, contact suppliers.
EFO(10)Power module failureControl board abnormal, serious interference, damaged power deviceContact suppliers for service.
LU(13)UndervoltageAbnormal input voltage, contactor not picking upCheck power supply voltage, contact suppliers.
OH(14)OverheatAmbient temperature too high, small space around VFD, air duct blocked, cooling fan not runningImprove environment, adjust space, clean airways, check fan.
FBL(19)PID feedback is lower than the lower limitLoose PID feedback line, feedback amount less than disconnection detection valueCheck feedback connection, adjust detection input threshold.
SPOOutput phase loss faultUnbalanced three-phase output, abnormal drive board, module abnormalTroubleshoot wiring, check motor winding, contact suppliers.

7. Maintenance

Regular maintenance ensures the longevity and optimal performance of your ELECTESLA ES280 VFD. Always ensure power is disconnected and capacitors are discharged before performing any maintenance.

  • Cleaning: Periodically clean the VFD's exterior and cooling fan to prevent dust buildup, which can lead to overheating. Ensure air ducts are clear.
  • Connections: Regularly check all wiring connections for tightness and signs of wear or corrosion. Loose connections can cause intermittent faults or damage.
  • Environmental Check: Ensure the operating environment remains within specified temperature and humidity ranges. Avoid excessive vibration or exposure to corrosive gases.
  • Parameter Backup: It is recommended to record or back up your VFD's parameter settings, especially after initial setup or significant changes, to facilitate quick restoration if needed.
  • Firmware Updates: Check with ELECTESLA Official Store for any available firmware updates that might improve performance or address known issues.

8. User Tips

  • Parameter Initialization: If you encounter persistent issues or wish to reset all settings, use parameter F0.17 to restore factory defaults. Be aware that this will erase all custom configurations.
  • External Keypad: The VFD features an easy-operation removable panel. Consider using an external keypad for convenient parameter setting and monitoring, especially if the VFD is installed in a hard-to-reach location.
  • Braking Resistor Selection: When dynamic braking is required, select the appropriate braking resistor based on your VFD's power and input supply from the provided table in the appendix to ensure effective and safe deceleration.

9. Warranty and Support

Your ELECTESLA ES280 VFD comes with an 18-month warranty. For any technical assistance, warranty claims, or to obtain the full user manual PDF, please contact the ELECTESLA Official Store.

Official Seller Video:

Play video
Watch video online

Product overview and demonstration by the ELECTESLA Official Store.

Item Guides & Documents:

A detailed user manual in PDF format is available for download. This document contains comprehensive information on all parameters, advanced settings, and communication protocols.

Download the full user manual (PDF): ELECTESLA ES280 User Manual (PDF)

For direct support, you can contact the seller:

  • WhatsApp: +8618656102087
  • Email: alex@jinqu-electric.com

10. Appendix: RS485 Communication

The ELECTESLA ES280 VFD supports Modbus-RTU slave communication protocol via its RS485 interface, allowing centralized control and monitoring through a computer or PLC.

10.1. Product Parameter Data

Parameters are organized into groups (F0-FP). Communication addresses are defined for reading and writing parameters. For example, F0-16 has a communication address of 0010H.

10.2. Non-Parametric Data

This includes status data (monitoring parameters, fault descriptions, running status) and control parameters. Status data addresses are fixed (e.g., fault description at 8000H, running status at 3000H).

10.3. Modbus Communication Protocol

The VFD uses Modbus-RTU. Users can read/write Word-type parameters (0x03 command) and byte/bit operations. The serial communication protocol defines the format for information transmission, including host polling, encoding, and error checking.

10.4. Communication Data Structure

Data frames include a header, slave address, command code, parameter address, number of parameters, and data. Data is transmitted with the high byte first.

10.5. Parameter Address Marking Rules

Parameter addresses are represented by group number and label (e.g., F3-12 corresponds to 0x030C). Some parameters cannot be changed during VFD operation.

10.6. FC Group Communication Parameters

This group sets communication-specific parameters:

  • FC.00 Communication baud rate: Sets the data transmission rate (e.g., 9600, 19200). Host and inverter baud rates must match.
  • FC.01 Modbus data format: Configures data length and stop position (e.g., no parity, 8 data bits, 1 stop bit).
  • FC.02 485 communication address: Sets the unique address for the VFD in a Modbus network (1-247).
  • FC.03 Modbus communication overtime fault time: Sets the timeout for communication.
  • FC.05 Communication error handling: Defines how the VFD reacts to communication errors (no operation, alarm, fault stop).

11. Appendix: Braking Resistor Selection

The following table provides guidelines for selecting an appropriate braking resistor based on the VFD's power and input supply. This is crucial for applications requiring rapid deceleration.

Braking Resistor Selection Guide
ModelPowerInput Power SupplyPower of Braking ResistorResistance of Braking Resistor
ZQ280S0D40.4KWSingle-phase AC 200V-240V 50Hz/60Hz100W250 Ω
ZQ280S0D70.75KWSingle-phase AC 200V-240V 50Hz/60Hz100W200 Ω
ZQ280S1D51.5KWSingle-phase AC 200V-240V 50Hz/60Hz300W100 Ω
ZQ280S2D22.2KWSingle-phase AC 200V-240V 50Hz/60Hz300W100 Ω
ZQ280S3D3.0KWSingle-phase AC 200V-240V 50Hz/60Hz500W75 Ω
ZQ280S4D4.0KWSingle-phase AC 200V-240V 50Hz/60Hz500W75 Ω
ZQ280S5D55.5KWSingle-phase AC 200V-240V 50Hz/60Hz1000W75 Ω
ZQ280S0D4-P30.4KWThree-phase AC 200V-240V 50Hz/60Hz100W250 Ω
ZQ280S0D7-P30.75KWThree-phase AC 200V-240V 50Hz/60Hz100W200 Ω
ZQ280S1D5-P31.5KWThree-phase AC 200V-240V 50Hz/60Hz300W100 Ω
ZQ280S2D2-P32.2KWThree-phase AC 200V-240V 50Hz/60Hz300W100 Ω
ZQ280S3D-P33.0KWThree-phase AC 200V-240V 50Hz/60Hz500W75 Ω
ZQ280S4D-P34.0KWThree-phase AC 200V-240V 50Hz/60Hz500W75 Ω
ZQ280S5D5-P35.5KWThree-phase AC 200V-240V 50Hz/60Hz1000W75 Ω
ZQ280T0D40.4KWThree-phase AC 340V-440V 50Hz/60Hz100W750 Ω
ZQ280T0D70.75KWThree-phase AC 340V-440V 50Hz/60Hz100W750 Ω
ZQ280T1D51.5KWThree-phase AC 340V-440V 50Hz/60Hz300W400 Ω
ZQ280T2D22.2KWThree-phase AC 340V-440V 50Hz/60Hz300W250 Ω
ZQ280T3D3.0KWThree-phase AC 340V-440V 50Hz/60Hz500W150 Ω
ZQ280T4D4.0KWThree-phase AC 340V-440V 50Hz/60Hz500W150 Ω
ZQ280T5D55.5KWThree-phase AC 340V-440V 50Hz/60Hz800W100 Ω
ZQ280T7D57.5KWThree-phase AC 340V-440V 50Hz/60Hz1000W75 Ω