1. Introduction
The MESTEK IT20G and IT200G are high-precision digital insulation resistance testers designed for measuring insulation resistance, AC/DC voltage, and calculating Polarization Index (PI) and Absorption Ratio (DAR). These megohmmeters are essential tools for the maintenance, repair, testing, and inspection of various electrical equipment, including transformers, motors, cables, switches, and electrical appliances. They feature a clear LCD display, data storage capabilities, and a robust, shockproof design.

2. Safety Information
Please read and understand all safety instructions before operating the device. Failure to follow these instructions may result in electric shock, fire, or serious injury.
- Always use the tester in accordance with local and national safety codes.
- Do not use the tester if it appears damaged or if the test leads are compromised.
- Ensure the device is powered off and disconnected from any power source before performing battery installation or maintenance.
- Avoid contact with live circuits during measurements.
- Wear appropriate personal protective equipment (PPE), such as insulated gloves and safety glasses.
- Do not operate the tester in wet environments or in the presence of explosive gases or dust.
- Keep the device away from children.
3. Package Contents
Verify that all items listed below are included in your package:
- MESTEK Digital Insulation Resistance Tester (IT20G or IT200G)
- 1.2m Lantern Silicone Test Leads (Red and Black)
- 10cm Large Alligator Clips (Red and Black)
- Carrying Bag
- User Manual
- 8 x 1.5V AA Batteries (may be included separately)


4. Product Features
The MESTEK Digital Insulation Resistance Tester offers a range of advanced features for comprehensive electrical testing:
- AC/DC Voltage Measurement: Measures voltage from 10V to 600V.
- Insulation Resistance Measurement: High-precision measurement up to 20GΩ (IT20G) or 200GΩ (IT200G).
- Data Retention (HOLD): Freezes the current measurement on the display.
- Polarization Index (PI): Calculates PI to assess insulation quality.
- Absorption Ratio (DAR): Calculates DAR to determine equipment dampness.
- Data Storage: Stores up to 100 sets of measurement data.
- Automatic Shut-down: Conserves battery life.
- Backlight: LCD HD backlight for working in dark environments.
- Low Voltage Alert: Indicates when batteries need replacement.
- ABS Shockproof Material: Double-layer insulation, shockproof, and wear-resistant casing.
- Adjustable Support Frame: 45° inner angle support frame for convenient measurement.



5. Components Overview

- Insulation resistance measurement high voltage output jack L
- AC/DC voltage measurement positive terminal
- Voltage measurement input negative shield terminal G (ie shield terminal)
- Insulation resistance measurement sampling jack E
- Display LCD screen
- Insulation resistance measurement high voltage start button
- Insulation resistance voltage selection button (Up arrow)
- Insulation resistance voltage selection button (Down arrow)
- Data hold/backlight button (HOLD*)
- Data read/save button (MEM READ)
- Function selection button: choose between insulation resistance/AC voltage/DC voltage function (SELECT)
- Polarization Index DAR and Absorption Ratio PI buttons (PI/DAR)
- Power switch button: press and hold for more than 2 seconds to turn on, then press and hold for more than 2 seconds to turn off
6. Setup
6.1. Battery Installation
The MESTEK Insulation Resistance Tester requires 8 x 1.5V AA batteries for operation. Follow these steps to install the batteries:
- Locate the battery compartment on the back of the tester.
- Use a screwdriver to open the battery compartment cover.
- Insert 8 AA 1.5V batteries, ensuring correct polarity (+/-).
- Replace the battery compartment cover and secure it with the screw.
6.2. Power On/Off
To power on the device, press and hold the power switch button (
) for more than 2 seconds. To power off, press and hold the same button for more than 2 seconds.
7. Operating Instructions
7.1. Insulation Resistance Measurement
This function measures the insulation resistance of electrical equipment. It is crucial for assessing the health of insulation materials.
- Connect the test leads to the high voltage output jack L and the sampling jack E on the tester.
- Connect the other ends of the test leads to the two ends of the circuit or component you wish to test (e.g., motor windings).
- Use the Up/Down arrow buttons to select the desired testing voltage (e.g., 250V, 500V, 1000V, 2000V, 2500V).
- Press the TEST button to initiate the measurement.
- The insulation resistance value will be displayed on the LCD screen.


7.2. AC/DC Voltage Measurement
The tester can measure both AC and DC voltages within a range of 10V to 600V.
- In the standby interface, short press the SELECT key to enter AC voltage measurement mode.
- Press the SELECT key again to switch to DC voltage measurement mode.
- Connect the test leads to the AC/DC voltage measurement positive terminal (V) and the negative shield terminal (G).
- Connect the other ends of the test leads to the circuit where you want to measure voltage.
- The voltage value will be displayed on the LCD screen.

7.3. Polarization Index (PI) Measurement
PI helps assess the deterioration of insulator quality. It is calculated using insulation resistance values at 1 minute and 10 minutes.
- Perform insulation resistance measurements at 1 minute and 10 minutes.
- Press the PI/DAR button to calculate and display the PI value.
Judgement Standard for PI:
| PI (Polarization Index Measurement) | ≥4 | 4~2 | 2.0~1.0 | ≤1.0 |
|---|---|---|---|---|
| Judgement standard | Most | Good | Warn | Bad |

7.4. Absorption Ratio (DAR) Measurement
DAR helps determine if equipment is affected by dampness. It is calculated using insulation resistance values at 15 seconds and 60 seconds.
- Perform insulation resistance measurements at 15 seconds and 60 seconds.
- Press the PI/DAR button to calculate and display the DAR value.
Judgement Standard for DAR:
| DAR (Absorption ratio measurement) | ≥1.4 | 1.25~1.0 | ≤1.0 |
|---|---|---|---|
| Judgement standard | Most | Good | Bad |

7.5. Data Storage
The tester can store up to 100 groups of measurement data.
- After measuring an insulation resistance value, press the HOLD* key to retain the data. The screen will display a "HOLD" symbol.
- Press the MEM READ button to save the data.
- To delete a single set of data, press the PI/DAR button.

7.6. Backlight Function
Long press the HOLD* button to turn on the LCD backlight. This allows for clear readings in dark environments. Long press again to turn off the backlight.

8. Maintenance
- Cleaning: Use a soft, dry cloth to clean the tester. Do not use abrasive cleaners or solvents.
- Storage: When not in use for extended periods, remove the batteries to prevent leakage. Store the device in its carrying bag in a cool, dry place, away from direct sunlight and extreme temperatures.
- Casing: The tester is made of ABS shockproof material, providing good protection against drops and wear. However, avoid unnecessary impacts to prolong its lifespan.
9. Troubleshooting
If you encounter issues with your MESTEK Insulation Resistance Tester, try the following:
- No Power: Check if the batteries are correctly installed and have sufficient charge. Replace batteries if necessary.
- Inaccurate Readings: Ensure test leads are securely connected and not damaged. Verify the correct measurement mode and voltage range are selected. Clean the test points on the device being measured.
- Display Issues: If the display is dim, activate the backlight. If the display is blank or erratic, try replacing the batteries.
- Low Voltage Alert: If the low voltage alert appears, replace all 8 AA batteries immediately.
10. Specifications
The following table outlines the technical parameters for the IT20G and IT200G models:
| Feature | IT20G | IT200G |
|---|---|---|
| Testing Voltage | 50V/100V/250V/500V/1000V | 250V/500V/1000V/2000V/2500V |
| Measuring Range (50V) | 0.1MΩ~200MΩ | N/A |
| Measuring Range (100V) | 0.1MΩ~200MΩ | N/A |
| Measuring Range (250V) | 0.4MΩ~20GΩ | 2MΩ~20GΩ |
| Measuring Range (500V) | 1MΩ~20GΩ | 1MΩ~20GΩ |
| Measuring Range (1000V) | 2MΩ~20GΩ | 3MΩ~20GΩ |
| Measuring Range (2000V) | N/A | 3MΩ~200GΩ |
| Measuring Range (2500V) | N/A | 5MΩ~200GΩ |
| AC/DC Voltage Measure | 10~600V | |
| Data Storage | 100 Groups | |
| Screen Backlight | √ | |
| Absorption Ratio DAR | √ | |
| Polarization Index PI | √ | |
| Auto Range | √ | |
| Auto Discharge | √ | |
| Auto Shut-down | √ | |
| Data Retention | √ | |
| Low Voltage Alert | √ | |
| Test Voltage Display | √ | |
| High Voltage Indication | √ | |
| Measure Time Display | √ | |
| Battery | 8*1.5V AA batteries | |
| Weight | 700g | |
| Size | 180*140*70mm | |
| Operating Temperature | 0~40°C | |
| Accuracy Class | High | |
| Display Type | Digital Only | |
| DIY Supplies | Electrical | |
| Certification | CE, RoHS | |
Note: The above data is for reference only; specific data is subject to actual measurement and product variations.



11. User Tips
- Always ensure the test leads are in good condition and properly connected before any measurement.
- For accurate insulation resistance readings, ensure the test environment is stable and free from excessive humidity.
- Utilize the data storage function to keep a record of your measurements for analysis and comparison over time.
12. Warranty and Support
For warranty information, technical support, or service inquiries, please refer to the contact information provided by your retailer or the official MESTEK website. Keep your purchase receipt as proof of purchase.